MODULE SPECIFICATIONS REC Solar REC420AA PURE-R DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS <br /> RATED POWER(STC) 420 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMPI MICROINVERTER TO MAX.SHORT CIRCUIT CURRRENT(ISC) = 10.5 A AC <br /> MODULE VOC 59.4 V DC STATE Washington JUNCTION BOX(1) MAX.CURRENT(ISC X1.25)= 13.1 A AC <br /> MODULE VMP 50 V DC CITY Everett CONDUCTOR(TC-ER,COPPER(90'C))= 12 AWG BLUE RAVE N <br /> MODULE IMP 8.4 A DC WEATHER STATION SNOHOMISH CO! CONDUCTOR RATING= 30 A <br /> MODULE ISC 8.88 A DC ASHRAE EXTREME LOW TEMP('C) -51 AMB.TEMP.AMP.CORRECTION = I <br /> VOC CORRECTION -0.24%/'C JASHRAE 2%AVG.HIGH TEMP('C) 30 ADJUSTED AMP.= 30 > 13.1 1403 N. Research Way <br /> VMP CORRECTION -0.24%/'C JUNCTION BOX TO MAX.SHORTCIRCUIT CURRRENT(ISC)= 10.5 AAC Orem, UT 84097 <br /> SERIES FUSE RATING 25 A DC SYSTEM ELECTRICAL SPECIFICATIONS CIR 1 CIR 2 CIR 3 CIR 4 CIR 5 CIR 6 JUNCTION BOX(2) MAX.CURRENT(ISC X1.25)= 13.1 A AC 8ERAV.4480 <br /> W W W.BLU RAVENSOLAR.COM <br /> ADJ. MODULE VOC @ ASHRAE LOW TEMP 63.7 V DC NUMBER OF MODULES PER MPPT 8 7 CONDUCTOR(UF-B,COPPER(60-C))= 10 AWG <br /> CONFIDENTIAL-THE INFORMATION <br /> ADI MODULE VMP @ ASHRAE 2%AVG.HIGH TEMP 45.6 V DC DC POWER RATING PER CIRCUIT(STC) 336 F29400 _ t CONDUCTOR RATING= 30 A HEREIN CONTAINED SHALL NOT BE <br /> TOTAL MODULE NUMBER 15 CONDUIT FILL DERATE= 1 USED FOR THE A EOA NE <br /> NO <br /> RAR <br /> EXCEPT BLUE RVENN SOL <br /> AR NOR <br /> MICROINVERTER SPECIFICATIONS Enphase IQ7X Microinverters STC RATING OF ARRAY 6300 AMB.TEMP.AMP.CORRECTION= 1 SHALL IT BE DISCLOSED IN WHOLE OR <br /> IN PART TO OTHERS OUTSIDE <br /> POWER POINT TRACKING(MPPT)MIN/MAX 53 - 64 V DC AC CURRENT @ MAX POWER POINT(IMP 10.5 9.2 ADJUSTED AMP.= 30 > 13.1 RECIPIENTS ORGANIZATION,EXCEPT <br /> MAXIMUM INPUT VOLTAGE 79.5 V DC MAX CURRENT(IMP X1.25) 13.1 11.4625 JUNCTION BOX TO MAX SHORT CIRCUIT CURRRENT(ISC)= 10.5 A AC IN CONNECTION WITH THE SALE AND <br /> USE OF THE RESPECTIVE EQUIPMENT, <br /> MAXIMUM DC SHORT CIRCUIT CURRENT 10 A DC OCPD CURRENT RATING PER CIRCUIT 20 20 COMBINER BOX(3) MAX.CURRENT(ISC X1.25)= 13.1 A AC WITHOUT THE WRITTEN PERMISSION <br /> MAXIMUM USABLE DC INPUT POWER 460 W MAX.COMB.ARRAY AC CURRENT(IMP) 19.7 CONDUCTOR(UF-B,COPPER(60-C))= 10 AWG OF BLUE RAVEN SOLAR LLC. <br /> MAXIMUM OUTPUT CURRENT 1.31 A AC MAX.ARRAY AC POWER 4725W AC CONDUCTOR RATING= 30 A <br /> ACOVERCURRENT PROTECTION 20 A CONDUIT FILL DERATE= 0.8 NABCEP <br /> MAXIMUM OUTPUT POWER 315 W AC VOLTAGE RISE CALCULATIONS DIST(FT) COND. VRISE(V) VEND(V) %VRISE AMB.TEMP.AMP.CORRECTION= 1 CERTIFIED <br /> CEC WEIGHTED EFFICIENCY 9750% VRISE SEC. 1(MICRO TO 160X) 28.8 12 Cu. 0.93 240.93 0.39% ADJUSTED AMP.= 24 > 13.1 <br /> VRISE SEC 2(JBOX TO COMBINER BOX) 30 10 Cu 0.80 240.80 0.33% COMBINER BOX TO INVERTER RATED AMPS= 19.7 A AC PV INSTALLATION <br /> AC PHOTOVOLATIC MODULE MARKING(NEC 690.52) VRISE SEC.3(COMBINER BOX TO P01) 5 10 Cu. 0-25 240.25 0.10% MAIN PV OCPD(15) MAX.CURRENT(RATED AMPS X1.25)= 24.56 A AC PROFESSIONAL <br /> NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 1.98 241.98 0.82% CONDUCTOR(THWN-2,COPPER(75-C TERM.))= 10 AWG Scott Gurney <br /> #PV-011719-015866 <br /> NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC CONDUCTOR RATING= 35 A <br /> MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL(NEC 690.54) CONDUIT FILL DERATE= I CONTRACTOR: <br /> MAXIMUM AC CURRENT 1.0 A AC AC OUTPUT CURRENT 19.7 A AC AMB.TEMP.AMP.CORRECTION= 1 BRS FIELD OPS <br /> MAXIMUM OCPD RATING FOR AC MODULE 20 A AC INOMINALAC VOLTAGE 240 V AC ADJUSTED AMP.= 35 > 24.6 800-377-4480 <br /> U <br /> a <br /> GROUNDING NOTES WIRING &CONDUIT NOTES Z 0 <br /> 1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.47]AND[NEC 250.50-60]SHALL BE 1. ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE 0 Y <br /> PROVIDED. PER[NEC 690.47],THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. CD LO <br /> N <br /> USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR(USE N <br /> INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE POLARIS BLOCK OR NEUTRAL BAR). CC pQ ~ co <br /> USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE C 0) (0 <br /> 2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED <br /> THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER) IF SMALLER THAN#6 AWG COPPER WIRE 4.UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF O W W <br /> PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)]. LL - N N <br /> SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)]. 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE Z y (J)3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. <br /> COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6. ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2,AND SINGLE-CONDUCTOR CABLE LISTED AND L <br /> 4.PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.21],[NEC TABLE 250.122],AND ALL METAL IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS E n a I n E E R 9 LUQ a (u LU W <br /> PARTS OR MODULE FRAMES ACCORDING TO[NEC 690.461. REQUIRED. N <br /> 5.MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC 690.42]. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE 657 W.GALENA PARK BLVD.STE. IO7 PHONE(80 7)990-7775 <br /> 6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS. DRAPER, UTAH 84D20 WWW.VECTORSE.COM Ui Cu U) (/) <br /> MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8"ABOVE O N o y ' <br /> 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE ELECTRICAL ONLY (n <br /> MANUFACTURER'S INSTALLATION INSTRUCTIONS. 310.15(B)(3)(A)],&[NEC 310.15(13)(3)(C)]. N >'r <br /> 8.ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9.EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90-C RATED,WET AND UV RESISTANT,AND UL = (b M V V <br /> GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP U N W> Q in <br /> 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES. <br /> EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHNrrHWN-2 INSULATED, 90°C RATED, �7 <br /> 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V 1 DRAWING BY: <br /> EXPOSED. 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND f�, •!£ i <br /> 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. t,t` i Brendan Fillmore <br /> MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION 1' 0 \rJ <br /> DAMAGE). 13.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS12. PLOT DATE: <br /> GREEN F 4 G DIN AND BONDING <br /> LARGER). OSDC <br /> CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED NEGATIVE <br /> OR MARKED RED),SYSTEMS <br /> SNDC CONDUCTORS <br /> SHALL BE MARKED GREY) <br /> COLOR CODED AS FOLLOWS: DC i / + <br /> 13.ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE 15.POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: �'� August 22, 2023 <br /> GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK) <br /> 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.661, DC SYSTEM GEC SIZED 16.AC CONDUCTORS>4AWG COLOR CODED OR MARKED: PHASE A OR L1-BLACK,PHASE B OR L2-RED, PROJECT NUMBER: <br /> ACCORDING TO[NEC 250.166],MINIMUM 8 AWG WHEN INSULATED,6 AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAY (113959 7 .t <br /> 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND 'USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE yii k�GJyl(tTt� Q <br /> CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] "USE-2 IS AVAILABLE AS UV WHITE 0982 7 <br /> �`'t�7U�t1-F��` lJ 9lJ I <br /> REGARDLESS OF VOLTAGE. 17.RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES. <br /> 18. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, SHEET NAME: <br /> FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.31], [NEC 250.118(10)]. DISCONNECTING <br /> MEANS SHALL COMPLY WITH[NEC 690.13]AND[NEC 690.151. EXPIRES: 06/05/2025 ELEC CALCS <br /> 19.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE COMPLYING WITH[NEC 08/23/2023 <br /> 230.6(4)]AND SECURED NO GREATER THAN 6'APART PER[NEC 330.30(B)]. REVISION: PAGE NUMBER: <br /> Firm License Number:2202 <br /> VSE Project Number:U2001.3013.231 0 PV6 <br />