HVAC <br />GENERAL <br />NOTES <br />DUCT <br />NOTES <br />1. <br />VERIFY SITE CONDITIONS. <br />1. <br />DUCT CONSTRUCTION AND INSTALLATION PER LATEST SMACNA STANDARDS AND THE <br />2. <br />THERMOSTAT LOCATIONS: VERIFY ALL WALL MOUNTED CONTROL LOCATIONS WITH ARCHITECT/GC. <br />2018 SMC AS REQUIRED BY THE LOCAL CODE. PROVIDE METAL DUCT, EXCEPT AS <br />3. <br />CODES: COMPLY WITH ALL LOCAL & STATE GOVERNING CODES. <br />NOTED. <br />4. <br />COORDINATE DUCTWORK AND GRILLE LOCATIONS WITH LIGHTING AND OTHER RELATED TRADES WITH <br />2. <br />BALANCING DAMPERS: PROVIDE ON ALL SUPPLY RUN OUT DUCTS UP STREAM OF <br />ARCHITECT APPROVAL. VERIFY CLEARANCES & CEILING ELEVATIONS BEFORE INSTALLATION. <br />DIFFUSERS. <br />5. <br />DRAWINGS ARE SCHEMATIC IN SOME AREAS AND MAY NOT SHOW EXACT ROUTING OR EVERY <br />3. <br />DUCT INSULATION: DUCTS, SHAFTS AND PLENUMS SHALL BE INSULATED TO MINIMUM <br />OFFSET WHICH MAY BE REQUIRED. <br />OF R-8 AND IN ACCORDANCE WITH THE SECTION C403.2.8 OF 2018 SEC. <br />6. <br />SEISMIC BRACING: PROVIDE TO MEET LOCAL CODE REQUIREMENTS. REFER TO THE ASHRAE <br />4. <br />DUCT SEALING —GENERAL: 0 TO 2" STATIC PRESSURE — SEAL ALL TRANSVERSE <br />STANDARDS "PRACTICAL GUIDE TO SEISMIC RESTRAINT". <br />JOINTS AND LONGITUDINAL SEAMS ON ALL DUCTS, ABOVE 2"—SEAL SEAMS, JOINTS <br />7. <br />EXHAUST FAN TERMINATION: SHALL NOT BE LESS THAN 3 FEET FROM A PROPERTY LINE OR <br />AND WALL PENETRATIONS. INSIDE BUILD: DURODYNE "DDS-181" GRAY OR <br />OPENINGS INTO A BUILDING, E.G., OPERABLE WINDOWS AND DOORS, OR DISTANCE AS REQUIRED <br />APPROVED EQUAL PER ILL 181 A—M, 1818—M USTED. OUTSIDE: POLYURETHANE, <br />PER LOCAL CODE. <br />MAMECO VULKEM 116. OR APPROVED EQUAL. <br />8. <br />TEST, ADJUST, & BALANCE: PROVIDE PROPER SYSTEM TESTING, ADJUSTING, AND BALANCING, <br />5. <br />TURN VANES: PROVIDE SINGLE THICKNESS TURN VANES (SEE DETAIL) IN ALL MAJOR <br />INCLUDING WRITTEN REPORTS TO BE PROVIDED TO OWNER. BALANCE TO WITHIN 10% OF DESIGN. <br />SQUARE DUCT ELBOWS, TEES, OR TURNS WITH INSIDE RADIUS LESS THAN 3/4 <br />9. <br />OPERATION & MAINTENANCE BOOKLET: PROVIDE 0 & M MANUAL TO OWNER. INCLUDE CUT SHEETS <br />DUCT WIDTH. SQUARE BRANCH DUCT TAPS SHALL BE 45 DEGREE TYPE PER <br />ON MAIN EQUIPMENT AND CONTROLS, MAINTENANCE INSTRUCTIONS, AND MARKED UP AS —BUILT <br />SMACNA STANDARD. <br />DRAWING. <br />6. <br />FLEX DUCT (INSULATED): FOR GRILLE RUN OUTS UP TO 6 FT. LONG, EXCEPT AS <br />10. <br />COMMISSIONING: PRIOR TO PASSING THE FINAL INSPECTION OR OBTAINING A CERTIFICATE OF <br />NOTED. PROVIDE ADJUSTABLE METAL ELBOWS ON ALL TURNS, UNLESS A SMOOTH <br />OCCUPANCY, PROVIDE THE EVIDENCE OF SYSTEM COMMISSIONING AND COMPLETION IN ACCORDANCE <br />FULL RADIUS TURN IS MADE. SECURE CORE WITH APPROVED NYLON OR METAL <br />WITH THE PROVISIONS OF SECTION C408 OF THE 2018 SEC <br />WORM DRIVE CLAMPS. NO DUCT TAPE JOINTS & SCREWS ALLOWED. <br />11. <br />WALK—THRU INSTRUCTION: PROVIDE ON SITE WALK—THRU FOR CUSTOMER TO DEMONSTRATE <br />7, <br />SOUND LINER: PROVIDE SOUND UNED METAL SUPPLY & RETURN DUCTS AS SHOWN <br />OPERATION OF SYSTEM AND ANSWER QUESTIONS. <br />ON PLANS. MANVILLE PERMACOTE LINACOUSTIC FLEXIBLE FIBERGLASS LINER, WITH <br />12. <br />ROOF TOP UNITS ON CURB: SEAL HOLES AND CRACKS BETWEEN DUCT AND ROOF DECK INSIDE <br />ACRYLIC SURFACE TREATMENT OR EQUAL. FABRICATE AND INSTALL PER DUCT LINER <br />FACTORY ROOF CURB FOR NOISE CONTROL. <br />STANDARD OF NORTH AMERICAN INSULATION MANUFACTURER'S ASSOC. <br />13. <br />GAS PIPE: SCHEDULE 40, BLACK STEEL. PAINT PIPE EXPOSED TO WEATHER. <br />OUTSIDE AIR DUCT IS NOT INSULATED THROUGH UNCONDITIONED AREA. <br />14. <br />SIZES: ALL PIPE SIZES SHOWN ARE MINIMUM. <br />8. <br />FLEX CONNECTORS: PROVIDE ON ALL DUCT HOOK—UPS TO ISOLATE AIR HANDLING <br />15. <br />PIPE HANGERS: SWIVEL LOOP STYLE, MICHIGAN NO.100 OR CLEVIS STYLE, NO.400 OR EQUAL <br />EQUIPMENT. (NEOPRENE COATED FIBERGLASS FABRIC TYPE) <br />BRAND, WITH ALTHERED STEEL ROD SIZED PER INDUSTRY STANDARDS. <br />9, <br />DUCT SIZE CHANGES: ROUND GALVANIZED DUCTS MAY BE SUBSTITUTED FOR <br />16. <br />ELECTRICAL: ALL EQUIPMENT TO HAVE A POSITIVE MEANS OF DISCONNECT ADJACENT TO AND IN <br />RECTANGULAR DUCTS THAT ARE NOT LINED. PROVIDE CIRCULAR EQUIVALENT OF <br />SIGHT FROM EQUIPMENT SERVED. PROVIDE A 120 VOLT RECEPTACLE LOCATED WITHIN 25 FEET OF <br />RECTANGULAR DUCT. OTHER EQUIVALENT RECTANGULAR DUCT SIZES MAY BE <br />EQUIPMENT FOR SERVICE & MAINTENANCE PURPOSES (2018 SMC SECTION 301.10). LINE VOLTAGE <br />SUBSTITUTED TO BETTER FIT SPACE. <br />WORK BY OTHERS. <br />10. <br />TEMPORARY DUCT CLOSURE: SEAL OFF DUCTWORK DURING CONSTRUCTION TO <br />17. <br />SUSPENDED MECHANICAL EQUIPMENT AND APPLIANCES SHALL HAVE RIGID VERTICAL HANGERS AND <br />KEEP OUT CONSTRUCTION DUST, ESPECIALLY FLOOR BOOTS AND LOW WALL <br />BE BRACED IN BOTH HORIZONTAL DIRECTIONS. <br />OPENINGS. <br />DIFFUSERS/CLILLS SCHEDULE <br />TAG <br />NUMBER <br />MAKE <br />MODEL <br />SIZE <br />NOTE <br />SD-1 <br />3 <br />SHOEMAKER <br />700MA <br />24X24 <br />1 <br />RG-1 <br />2 <br />SHOEMAKER <br />EGGCRATE <br />24X24 <br />- <br />NOTES: <br />1. NECK COLLAR SIZES PER PRINT <br />LEGAL DESCRIPTION: <br />Section 18 Township 29 Range 05 Quarter SE LOT A14 OF BSP <br />FOR DIV 3 OF PORT OF EV N MARINA BSP16-004 REC UND AFN <br />201708075002& AS CORR BY AFN 201812265002 BEING A PEN OF <br />SE1/4 SD SEC EX BLDG (HOTEUNDIGO) ON 29051800402401 <br />TAX PARCEL NUMBER: 29051800402400 <br />VICINITY MAP <br />(15 NTS <br />AREA OF WORK <br />FREEDOM BOAT CLUB AREA OF WORK <br />15 NTS <br />DRAWING INDEX <br />M-1 <br />LEGEND & <br />ABBREVIATIONS, <br />VICINITY MAP, <br />NOTES, <br />EQUIPMENT SCHEDULE <br />M-2 <br />NEW HVAC <br />PLAN <br />LEGEND & ABBREVIATIONS <br />SYMBOL <br />ABBREV. <br />DESCRIPTION <br />SYMBOL <br />ABBREV. DESCRIPTION <br />® ® <br />SUPPLY DUCT <br />♦ <br />FIRE DAMPERED DUCT <br />0 z <br />RETURN/EXHAUST DUCT <br />PENETRATION OF A <br />HORIZONTAL SEPARATION <br />SL <br />SOUNDLINED DUCT <br />�y <br />FlRE DAMPERED DUCT <br />sus <br />VD <br />MANUAL VOLUME DAMPER <br />PENETRATION OF A <br />FC <br />FLEX CONNECTOR <br />VERTICAL SEPARATION <br />h <br />TV <br />TURNING VANES <br />o <br />TIMER 0-4 HR ADJUSTABLE <br />EC <br />END CAP <br />O <br />THERMOSTAT/HVAC UNIT # <br />® <br />SO <br />SUPPLY DIFFUSER, CEILING <br />O <br />SENSOR/HVAC UNIT # <br />® <br />MG <br />MAKEUP GRILLE <br />OO <br />SENSOR (CEILING MOUNT) <br />z <br />RG <br />RETURN GRILLE, CEILING <br />O <br />EXHAUST FAN <br />z <br />EG <br />EXHAUST GRILLE, CEILING <br />—0-0 <br />PIPE/DUCT UP <br />z <br />TG <br />TRANSFER GRILLE, CEILING <br />PIPE/DUCT DOWN <br />—1 -- <br />SIDEWALL SUPPLY/MAKEUP <br />PIPE TEE DOWN <br />SIDEWALL RETURN/EXHAUST <br />PIPE TEE UP <br />ll -_271 <br />EQUIPMENT TAG <br />EXIST DUCTWORK, EQUIP <br />AFF <br />ABOVE FINISHED FLOOR <br />NEW DUCTWORK, EQUIP <br />BD, BDD <br />BACKDRAFT DAMPER <br />CEILING RADIATION DAMPER <br />VALVE <br />BS <br />BIRDSCREEN <br />BALANCING VALVE <br />ON <br />DOWN <br />EA <br />EXHAUST AIR <br />ADJ <br />ADJACENT <br />OA, OSA <br />OUTSIDE AIR <br />BSC <br />BIOLOGICAL SAFETY CABINET <br />RA <br />RETURN AIR <br />CFH <br />CHEMICAL FUME HOOD <br />SA <br />SUPPLY AIR <br />CFM <br />CUBIC FEET PER MINUTE <br />(N) <br />NEW <br />DB <br />DUCT BOARD <br />(E)/EXIST <br />EXISTING <br />L,S <br />LIQUID, SUCTION <br />(R) <br />RELOCATED <br />N <br />NECK <br />BWG <br />BOTTOM WALL GRILLE <br />NIC <br />NOT IN CONTRACT <br />TWG <br />TOP WALL GRILLE <br />CAI <br />OUTSIDE AIR INTAKE <br />TYR <br />TYPICAL <br />RD <br />ROUND DIFFUSER <br />VD <br />VOLUME DAMPER <br />SHC <br />SENSIBLE HEATING CAPACITY <br />DEMO <br />SR <br />SUPPLY REGISTER <br />TC <br />TOTAL COOLING <br />REVISIONS <br />VEL <br />VELOCITY <br />WH <br />WATER HEATER <br />SC <br />SOUND CAN <br />AIR <br />TERMINAL <br />LEGEND <br />GRILLE, REGISTER, XX 8X8NECK SIZE (INCHES) <br />DIFFUSER IN LEGEND 140 SQUARE OR RECTANGULAR <br />AIR QUANTITY (CFM) <br />XX 8"0 NECK SIZE (INCHES) <br />140 ROUND <br />Air Quantity (CFM) <br />ARROWS INDICATE AIR PATTERN FOR CEILING DIFFUSERS <br />NO ARROWS INDICATE FOUR WAY PATTERN <br />FIRE SPRINKLER HEADS TO BE FAST REACTION TYPE BY OTHERS. <br />DESCRIPTION OF WORK: <br />�rlmJW,LNI:Lrai!un,fyynn�nn,�rar,K �nal� <br />2. INSTALL TWO (3) DIFFUSERS AND (3) GRILLES <br />3. AIR BALANCE <br />U <br />W <br />0 <br />o- <br />o_ <br />0 <br />w <br />0 <br />0 <br />d <br />0 <br />0' <br />a <br />M <br />Z <br />a { <br />O N <br />O 00 <br />J O <br />Q <br />H <br />LU <br />J_ W <br />LU <br />O <br />N <br />a) <br />Wl <br />of 2 <br />