Laserfiche WebLink
A B I C D E F G I H <br /> COMBINER BOX PANEL SIZE CALCS CONDUCTOR SCHEDULE <br /> NUMBER OF NUMBER OF NOMINAL OUTPUT TOTAL 125% TOTAL BREAKER SIZE COMBINED CURRENT FOR HM-1200 600.300 CONDUCTORS GROUND <br /> CIRCUIT# MODULES MICROINVERTERS CURRENT TOTAL INVERTER NUMBER OF IOMINAL OUTPU COMBINED <br /> TOTAL WIRES IN MINIMUM MINIMUM <br /> CIRCUIT 1(1 of 2) 2 1 X 2.46A = 2.46A x 1.25 = 3.08A = 9.33A = 20A TYPE INVERTERS CURRENT TOTAL TAG ID CONDUIT WIRE SIZE TYPE,MATERIAL WIRE SIZE TYPE,MATERIAL <br /> CIRCUIT 1(2 of 2) 4 1 5.OA - 5.00A x 1.25 = 6.25A HM-1200 2 x 5.OA = 10.00A <br /> CIRCUIT 2(1 of 3) 1 1 X 1.23A - 1.23A - 1.54A HM-600 2 x 2.46A = 4.92A = 16.15A A" 6 #12 AWG PV CABLE,CU #6 AWG BARE,CU <br /> CIRCUIT 2(2 of 3) 2 1 X 2.46A - 2.46A X 1.25 = 3.08A = 10.86A = 20q HM-300 t X 1.23A = 1.23A gTAG <br /> 5 #12 AWG THWN-2,CU #8 AWG THWN-2,CU <br /> CIRCUIT 2(3 of 3) 4 1 5.OA - 5.00A x 1.25 = 6.25A 3 #e AWG THWN-2.CU #8 AWG THWN-2,CU <br /> 4 #8AWG THWN-2,CU #B AWG THWN-2,CU <br /> LOAD CALCS-TOTAL AMPS AVAILABLE BREAKER SIZE CALCS CABLE WILL BE RUN THROUGH ATTIC WHERE POSSIBLE *'TAG D ONLY IF APPLICABLE' <br /> BUS RATING 120% TOTAL MAIN BREAKER MAX BREAKER SIZE MAX AC OPERATING CURRENT 125% TOTAL BREAKER SIZE <br /> 200A X 1.2 - 240 - 200A - 40A 16.15A Xl 1.25 1 x I 20.19A I=I 25A <br /> 2 ZNSHINE ZXM6-NH120-360M MODULES 4 ZNSHINE ZXM6-NH120-360M MODULES <br /> WITH HOYMILES HM-600 MICRO INVERTERS WITH HOYMILES HM-1200 MICRO INVERTERS <br /> I <br /> (V X21 X11 X41 3 <br /> X1 X2 <br /> 1 X11 I N <br /> ,. ,. <br /> I <br /> I <br /> I <br /> MAIN PANEL UPGRADE REQUIRED. <br /> 200A MAIN BUS RATING/200A MAIN <br /> I <br /> ti ti I BREAKER <br /> I <br /> I <br /> 1 ZNSHINE ZXM6-NH120-360M MODULE 2 ZNSHINE ZXM6-NH120-360M MODULES 4 ZNSHINE ZXM6-NH120-360M MODULES <br /> WITH HOYMILES HM-300 MICRO INVERTER WITH HOYMILES HM-600 MICRO INVERTERS WITH HOYMILES HM-1200 MICRO INVERTERS I UTILITY <br /> (1 OF 3) (2 OF 3) (3 OF 3) j SERVICE <br /> -------------- ---- ------ <br /> II SINGLE PHASE <br /> co X11 X21 X11 (4) (3) (2) (11 II 1 w <br /> II <br /> II <br /> II <br /> II <br /> II (N)240V/60A PV <br /> 125A LOAD CENTER, O <br /> NEMA 3R RATED <br /> II q g (N)UTILITY 200A 200A RATED <br /> II AC DISCONNECT MAIN MAIN SERVICE <br /> II 240V/30A NEMA 3R DISCONNECTPANEL <br /> II NON-FUSIBLE, <br /> II VISIBLE-LOCKABLE (E)LOADS <br /> II LABELED <br /> II 20A <br /> II 20A <br /> II (N)PV OCPD <br /> II 2P-25A <br /> II <br /> --------- — --� I <br /> I I <br /> I <br /> NEMA3R RATED D 25A LOAD-SIDEJ FACILITY GROUND <br /> JUNCTION BOX:SHALL 2 SOLAR OCPD GROUND ROD <br /> COMPLY W/NEC 110.3 (Opposite end of the main disconnect <br /> NOTES: &314.6 on the busbar-NEC 705.12(B)(3) <br /> 1. 200A UTILITY METER&200A LOAD CENTER INSTALLED <br /> WITH SURGE PROTECTION.(NEW) 3 <br /> 2. 30A RATED NON-FUSED LOCKABLE AC DISCONNECT. <br /> (NEW) <br /> 3. 125A RATED COMBINER PANEL.(NEW) <br /> LO cn <br /> ALL CONDUIT SIZES ARE MINIMUM SIZES <br /> ALL WIRE SIZES ARE FOR COPPER WIRE <br /> DRAWN BY: DRAWING SCALE: <br /> CONFIDENTIAL-THE INFORMATION CONTAINED EAC NOT TO SCALE <br /> IN THIS PACKET AND SUBSEQUENT CUTSHEETS Robert DixonDESIGN <br /> SO <br /> SHALL NOT BE USED FOR THE BENEFIT OF SOLGEN POWER <br /> DATE:L G C N ANYONE OUTSIDE SOLGEN POWER. NEITHER 5715 BEDFORD ST, 23/08/2023 <br /> SHALL IT BE DISCLOSED TO OTHERS OUTSIDE PASCO, WA 99301 1 <br /> P O V V E R THE RECIPIENT'S ORGANIZATION, EXCEPT IN 7021 Lower Ridge Rd Everett WA 98203 PAGE# <br /> CONNECTION WITH THE SALE AND USE OF THE P: 509-931-1663 <br /> RESPECTIVE EQUIPMENT, WITHOUT WRITTEN PV <br /> CONSENT FROM SOLGEN POWER. <br />