A B I C D E F G H <br /> COMBINER BOX PANEL SIZE CALCSMAX AL;UPE <br /> NUMBER OF NUMBER OF NOMINAL OUTPUT COMBINED CURRENT FOR HM-1200.600.300 CONDUCTOR SCHEDULE <br /> TOTAL 125% TOTAL BREAKER SIZE INVERTER NUMBERR OF OMINAL OUTPUT COMBINED <br /> CIRCUIT# MODULES MICROINVERTERS CURRENT TOTAL TYPE INVERTERS CURRENT TOTAL TOTAL CONDUCTORS GROUND <br /> CIRCUIT 12 3 X 5.OA = 15.00A x 1.25 = 18.75A = N/A = 20A HM-1200 9 X 5.OA = 45.00A WIRES IN MINIMUM MINIMUM <br /> CIRCUIT 2(1 of 3) 1 1 X 1.23A - 1.23A = 1.54A HM-600 1 X 2.46A - 2.46A = 48.69A TAG ID CONDUIT WIRE SIZE TYPE,MATERIAL WIRE SIZE TYPE,MATERIAL <br /> CIRCUIT 2(2 of 3) 2 1 X 2.46A - 2.46A X 1.25 = 3.08A = 17.11A - 20A HM-300 1 X 1.23A - 1.23A <br /> CIRCUIT 2(3 of 3) 8 2 x5.OA - 10.00A x 1.25 = 12.50A A' 12 #12 AWG PV CABLE,CU #6 AWG BARE,CU <br /> CIRCUIT 3 8 2 X 5.OA - 10.00A x 1.25 = 12.50A = N/A - 20A LOAD CALCS-TOTAL AMPS AVAILABLE B 9 #12 AWG THWN-2,CU #8 AWG THWN-2,Cu <br /> CIRCUIT 4 1 8 1 2 X1 5.OA - 10.06A x 1.25 = 12.50A = N/A - 20A BUS RATING 120% 1 TOTAL IMAIN BREAKER MAX BREAKER SIZE C 3 #4 AWG THWN-2,CU #8 AWG THWN-2,Cu <br /> 225A X 1.2 1=1 270 200A = 70A <br /> D'" 4 #4 AWG THWN-2,CU #B AWG I THWN-2,CU <br /> BREAKER SIZE CALCS 'TAG A CABLE WILL BE RUN THROUGH ATTIC WHERE POSSIBLE "TAG D ONLY IF APPLICABLE' <br /> MAX AC OPERATING CURRENT 125% TOTAL BREAKER SIZE <br /> 48.69A x 1.25 x 60.86A = 70A <br /> 12 ZNSHINE ZXM6-NH120-360M MODULES <br /> WITH HOYMILES HM-1200 MICRO INVERTERS <br /> I <br /> N 1ql �3 X21 �1l N <br /> I <br /> I <br /> I <br /> I <br /> c = <br /> MAIN PANEL UPGRADE REQUIRED. <br /> 225A MAIN BUS RATING/200A MAIN <br /> BREAKER <br /> 1 ZNSHINE ZXM6-NH120-360M MODULE 2 ZNSHINE ZXM6-NH120-360M MODULES 8 ZNSHINE ZXM6-NH120-360M MODULES <br /> WITH HOYMILES HM-300 MICRO INVERTER WITH HOYMILES HM-600 MICRO INVERTERS WITH HOYMILES HM-1200 MICRO INVERTERS UTILITY <br /> (1 OF 3) ------------ (20F3) SERVICE <br /> —__--- (30F3) _-- <br /> li SINGLE PHASE <br /> M �'1 ��1 `g"1 Lql L31 L.2, <br /> II <br /> II <br /> . II <br /> _ _ 'I M <br /> II (N)240V/60A PV •1 <br /> II 125A LOAD CENTER, <br /> NEMA 3R RATED 225A RATED <br /> A B (N)UTILITY MAIN SERVICE <br /> II AC DISCONNECT MAIN <br /> II 240V/100A NEMA 3R DISCONNEC PANEL <br /> NON-FUSIBLE, <br /> 8 ZNSHINE ZXM6-NH120-360M MODULES I VISIBLE-LOCKABLE (E)LOADS <br /> WITH HOYMILES HM-1200 MICRO INVERTERS II LABELED <br /> ------- --- --- --- ---�I� 20A <br /> 20A <br /> • • • �� �� �'2 1 �� it 20A (N2PPV O APD <br /> III <br /> III <br /> I I I <br /> Ln <br /> = NEMA3R RATED 0 2 70A LOAD-SID2 FACILITY GROUND <br /> ^' JUNCTION BOX:SHALL SOLAR OCPD GROUND ROD <br /> COMPLY W/NEC 110.3 (Opposite end of the main disconnect <br /> &314.6 3 on the busbar-NEC 705.12(6)(3) <br /> I <br /> 8 ZNSHINE ZXM6-NH120-360M MODULES I <br /> WITH HOYMILES HM-1200 MICRO INVERTERS I <br /> �g1 L1 331 X21 <br /> NOTES: <br /> 1. 200A UTILITY METER&225A LOAD CENTER INSTALLED <br /> u') WITH SURGE PROTECTION.(NEW) <br /> 2. 100A RATED NON-FUSED LOCKABLE AC DISCONNECT. <br /> (NEW) ti -ti <br /> 3. 125A RATED COMBINER PANEL.(NEW) <br /> ALL CONDUIT SIZES ARE MINIMUM SIZES <br /> ALL WIRE SIZES ARE FOR COPPER WIRE <br /> DRAWN BY: DRAWING SCALE: <br /> CONFIDENT/AL-THE INFORMATION CONTAINED JB NOT TO SCALE <br /> IN THIS PACKET AND SUBSEQUENT CUTSHEETS Alie R. Byland DATE: DESIGN <br /> SO L G L N SHALL NOT BE USED FOR THE BENEFIT OF SOLGEN POWER <br /> ANYONE OUTSIDE SOLGEN POWER. NEITHER 5715 BEDFORD ST, 9/13/2023 <br /> SHALL IT BE DISCLOSED TO OTHERS OUTSIDE PASCO, WA 99301 I <br /> P 0 W E R THE RECIPIENT'S ORGANIZATION, EXCEPT IN PAGE# <br /> CONNECTION WITH THE SALE AND USE OF THE P: 509-931-1663 3605 Earl Ave, Everett, WA 98201 <br /> RESPECTIVE EQUIPMENT, WITHOUT WRITTEN PV 3 <br /> CONSENT FROM SOLGEN POWER. <br />