MODULE SPECIFICATIONS REC Solar REC420AA PURE-R DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS
<br /> RATED POWER(STC) 420W TEMPERATURE DATA SOURCE ASHRAE2%AVG.HIGH TEMP MICROINVERTERTO MAX.SHORT CIRCUIT CURRRENT(ISC)= 11.8AAC
<br /> MODULE VOC 59.4 V DC STATE Washington JUNCTION BOX(1) MAX.CURRENT(ISC X1.25)= 14.7 A AC
<br /> MODULE VMP 50 V DC CITY Everett CONDUCTOR(TC-ER,COPPER(90°C))= 12 AWG BLUE RAVEN
<br /> MODULE IMP 8.4 A DC WEATHER STATION SNOHOMISH CO CONDUCTOR RATING= 30 A
<br /> MODULE ISC 8.88 A DC ASHRAE EXTREME LOW TEMP("C) -5 AMB.TEMP.AMP.CORRECTION= 1
<br /> VOC CORRECTION -0.24 %/°C ASHRAE 2%AVG.HIGH TEMP(°C) 26 ADJUSTED AMP.= 30 ? 14.7 1403 N. Research Way
<br /> VMP CORRECTION -0.24 %/°C JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 11.8AAC Orem, UT 84097
<br /> SERIES FUSE RATING 25 A DC SYSTEM ELECTRICAL SPECIFICATIONS CIR 1 CIR 2 CIR 3 CIR 4 CIR S CIR 6 JUNCTION BOX(2) MAX.CURRENT(ISC X1.25)= 14.7 A AC 800.377.4480
<br /> W W W.BLUERAVENSOLAR.COM
<br /> ADJ.MODULE VOC @ ASHRAE LOW TEMP 63.7 V DC NUMBER OF MODULES PER MPPT 9 CONDUCTOR(UF-B,COPPER(60°C))= 10 AWG
<br /> CONFIDENTIAL-THE INFORMATION
<br /> ADJ.MODULE VMP @ ASHRAE 2%AVG.HIGH TEMP 46.0 V DC DC POWER RATING PER CIRCUIT(STC) 3780 I I CONDUCTOR RATING= 30 A HEREIN CONTAINED SHALL NOT BE
<br /> TOTAL MODULE NUMBER 9 CONDUIT FILL DERATE= 1 USED FOR THE BENEFIT OF ANYONE
<br /> EXCEPT BLUE RAVEN SOLAR NOR
<br /> MICROINVERTER SPECIFICATIONS Enphase IQ7X Microinverters STC RATING OF ARRAY 3780 AMB.TEMP.AMP.CORRECTION= 1 SHALL IT BE DISCLOSED IN WHOLE OR
<br /> IN PART TO OTHERS OUTSIDE
<br /> POWER POINTTRACKING(MPPT)MIN/MAX 53 - 64 V DC AC CURRENT @ MAX POWER POINT(IMP 11.8 ADJUSTED AMP.= 30 i 14.7 RECIPIENTS ORGANIZATION,EXCEPT
<br /> MAXIMUM INPUTVOLTAGE 79.5 V DC MAX.CURRENT(IMP X 1.25) 14.7375 JUNCTION BOX TO MAX.SHORT CIRCUITCURRRENT(ISC)= 11.8 A AC IN CONNECTION WITH THE SALE AND
<br /> USE OF THE RESPECTIVE EQUIPMENT,
<br /> MAXIMUM DC SHORT CIRCUIT CURRENT 10 A DC OCPD CURRENT RATING PER CIRCUIT 20 COMBINER BOX(3) MAX.CURRENT(ISC X1.25)= 14.7 A AC WITHOUT THE WRITTEN PERMISSION
<br /> MAXIMUM USABLE DC INPUT POWER 460 W MAX.COMB.ARRAY AC CURRENT(IMP) 11.8 CONDUCTOR(UF-B,COPPER(60°C))= 10 AWG OF BLUE RAVEN SOLAR LLC.
<br /> MAXIMUM OUTPUT CURRENT 1.31 A AC MAX.ARRAY AC POWER 2835W AC CONDUCTOR RATING= 30 A
<br /> AC OVERCURRENT PROTECTION 20 A CONDUIT FILL DERATE= 1NABCEP
<br /> MAXIMUM OUTPUT POWER 315 W AC VOLTAGE RISE CALCULATIONS DIST(FT) GOND. JRISE(V) VEND(V) %VRISE AMB.TEMP.AMP.CORRECTION= 1 CERTIFIED
<br /> CEC WEIGHTED EFFICIENCY 9750% VRISE SEC_1(MICRO TO JBOX) 32.4 12 Cu. 1.18 241.18 0.49% ADJUSTED AMP.= 30 ? 14.7
<br /> VRISE SEC_2(JBOX TO COMBINER BOX) 25 10 Cu. 0.75 240.75 0.31% COMBINER BOX TO INVERTER RATED AMPS= 11.8 A AC PV INSTALLATION
<br /> AC PHOTOVOLATIC MODULE MARKING(NEC 690.52) VRISE SEC.3(COMBINER BOX TO POI) 5 10 Cu. 0.15 240.15 0.06% MAIN PV OCPD(15) MAX.CURRENT(RATED AMPS X1.25)= 14.74 A AC PROFESSIONAL
<br /> NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 2.08 242.08 0.87% CONDUCTOR(THWN-2,COPPER(75`C TERM.))= 10 AWG Scott Gumey
<br /> #PV-011719-015866
<br /> NOMINAL OPERATING AC FREQUENCY 47.68 HZ AC CONDUCTOR RATING= 35 A
<br /> MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL(NEC 690-54) CONDUIT FILL DERATE= 1 CONTRACTOR:
<br /> MAXIMUM AC CURRENT 1.0 A AC ACO UTCURRENT 11.8 A AC AMB,TEMP.AMP.CORRECTION= 1 BRS FIELD OPS
<br /> MAXIMUMOCPD RATING FOR ACMODULE 20AAC NOMINAL AC VOLTAGE 240VAC ADJ USTE DAMP.= 35 > 14.7 800-377-4480
<br /> Q Q
<br /> GROUNDING NOTES WIRING & CONDUIT NOTES
<br /> 1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.471 AND[NEC 250.50-601 SHALL BE 1.ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE scf 3:
<br /> PROVIDED. PER [NEC 690.47],THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. O O Lr)
<br /> USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR(USEQ N
<br /> INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE POLARIS BLOCK OR NEUTRAL BAR). CC 00 00
<br /> USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE G O7 CV (7
<br /> 2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED
<br /> THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER)IF SMALLER THAN#6 AWG COPPER WIRE 4.UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF O O W W
<br /> PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)]. +-
<br /> SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)]. 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE Z 0) N N
<br /> 3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. z i
<br /> COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6.ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2, AND SINGLE-CONDUCTOR CABLE LISTED AND a/ > C
<br /> 4.PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.211,[NEC TABLE 250.1221,AND ALL METAL IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS �pI W', u i U G
<br /> PARTS OR MODULE FRAMES ACCORDING TO[NEC 690.461. REQUIRED. � LU I) In LU LU
<br /> 65..ITSOURCE
<br /> GROUNDED
<br /> ACCORDANCE
<br /> CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE 'fit'��c �WASI.JH+ F� 0
<br /> HE GROUNDING CONNECTION TO A MODULE SHALLBE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS. � y Cl)
<br /> MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8"ABOVE �� �G Q)
<br /> 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE 401N � 04 �
<br /> MANUFACTURER'S INSTALLATION INSTRUCTIONS. 310.15(B)(3)(A)],&[NEC 310.15(B)(3)(C)]. s (0 Q a)
<br /> 8.ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9.EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90°C RATED,WET AND UV RESISTANT,AND UL = Ln > U V
<br /> GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP U Q I` W Q
<br /> 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES.
<br /> EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 INSULATED, 90'C RATED, 'FO 54072 �k
<br /> 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V xt GJST�R �] DRAWING BY:
<br /> EXPOSED. 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND �SS7ONALENG�
<br /> 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. Brendan Fillmore
<br /> MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION
<br /> DAMAGE). 13.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS PLOT DATE:
<br /> 12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DCGREEN 2023 .09. 1
<br /> 13.ALL IF 4 AWG CONDUIT OR LARGER).BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE POSITIVE- OR MARKED GREY)
<br /> POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED September 14, 2023
<br /> GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK)
<br /> 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.471, [NEC TABLE 250.661, DC SYSTEM GEC SIZED 16.AC CONDUCTORS>4AWG COLOR CODED OR MARKED: PHASE A OR L1-BLACK,PHASE B OR L2-RED, PROJECT NUMBER:
<br /> ACCORDING TO[NEC 250.166],MINIMUM 8 AWG WHEN INSULATED,6 AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAY
<br /> 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE 860739
<br /> CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] **USE-2 IS AVAILABLE AS UV WHITE
<br /> REGARDLESS OF VOLTAGE. 17.RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES. 4 17 :29:42 SHEET NAME:
<br /> 18.IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT,
<br /> FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.311, [NEC 250.118(10)1. DISCONNECTING /�
<br /> MEANS SHALL COMPLY WITH[NEC 690.131 AND[NEC 690.151. E LEC CALLS
<br /> 19.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE COMPLYING WITH[NEC 0600
<br /> 230.6(4)]AND SECURED NO GREATER THAN 6'APART PER[NEC 330.30(B)]. REVISION: PAGE NUMBER:
<br /> 0 PV6