MODULE SPECIFICATIONS REC Solar REC420AA PURE-R DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS
<br /> RATED POWER(STC) 420 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMP MICROINVERTERTO MAX.SHORT CIRCUITCURRRENT(ISC)= 15.7 AAC
<br /> MODULE VOC 59.4 V DC STATE Washington JUNCTION BOX(1) MAX.CURRENT(ISC X1.25)= 19.7 A AC
<br /> MODULE VMP 50 V DC CITY EVERETT CONDUCTOR(TC-ER,COPPER(90°C))= 12 AWG BLUE RAVEN
<br /> MODULE IMP 8.4 A DC WEATHER STATION SNOHOMISH CO CONDUCTOR RATING= 30 A
<br /> MODULE ISC 8.88 A DC ASHRAE EXTREME LOW TEMP(°C) -5 AMB.TEMP.AMP.CORRECTION= 1
<br /> VOC CORRECTION -0.24%/°C ASHRAE 2%AVG.HIGH TEMP(°C) 26 ADJUSTED AMP.= 30 > 19.7 1403 N. Research Way
<br /> VMP CORRECTION -0.24%/°C JUNCTION BOX TO MAX.SHORT CIRCUITCURRRENT(ISC)= 15.7 AAC Orem, UT 84097
<br /> SERIES FUSE RATING 25 A DC SYSTEM ELECTRICAL SPECIFICATIONS CIR 1 CIR 2 CIR 3 CIR 4 CIR 5 CIR 6 JUNCTION BOX(2) MAX.CURRENT(ISC X1.25)= 19.7 A AC 800.377.4480
<br /> W W W.BLUERAVENSOLAR.COM
<br /> ADJ.MODULE VOC @ ASHRAE LOW TEMP 63.7 V DC NUMBER OF MODULES PER MPPT 12 CONDUCTOR(THWN-2,COPPER(75°C TERM.))= 10 AWG
<br /> CONFIDENTIAL-THE INFORMATION
<br /> ADJ.MODULE VMP @ ASHRAE 2%AVG.HIGH TEMP 46.0 V DC DC POWER RATING PER CIRCUIT(STC) 5040 CONDUCTOR RATING= 35 A HEREIN CONTAINED SHALL NOT BE
<br /> TOTAL MODULE NUMBER 12 CONDUIT FILL DERATE= 1 USED FOR THE BENEFIT OF ANYONE
<br /> EXCEPT BLUE RAVEN SOLAR NOR
<br /> MICROINVERTER SPECIFICATIONS Enphase IQ7X Microinverters STC RATING OF ARRAY 5040 AMB.TEMP.AMP.CORRECTION= 1 SHALL IT BE DISCLOSED IN WHOLE OR
<br /> IN PART TO OTHERS OUTSIDE
<br /> POWER POINTTRACKING(MPPT) MIN/MAX 53 - 64 V DC AC CURRENT @ MAX POWER POINT(IMP 15.7 ADJUSTED AMP.= 35 > 19.7 RECIPIENTS ORGANIZATION,EXCEPT
<br /> MAXIMUM INPUT VOLTAGE 79.5 V DC MAX.CURRENT(IMP X 1.25) 19.65 JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 15.7 A AC IN CONNECTION WITH THE SALE AND
<br /> USE OF THE RESPECTIVE EQUIPMENT,
<br /> MAXIMUM DC SHORT CIRCUIT CURRENT 10 A DC OCPD CURRENT RATING PER CIRCUIT 20 COMBINER BOX(3) MAX.CURRENT(ISC X1.25)= 19.7 A AC WITHOUT THE WRITTEN PERMISSION
<br /> MAXIMUM USABLE DC INPUT POWER 460 W MAX.COMB.ARRAY AC CURRENT(IMP) 15.7 CONDUCTOR(THWN-2,COPPER(75°C TERM.))= 10 AWG OF BLUE RAVEN SOLAR LLC.
<br /> MAXIMUM OUTPUT CURRENT 1.31 A AC MAX.ARRAY AC POWER 3780W AC CONDUCTOR RATING= 35 A
<br /> AC OVERCURRENT PROTECTION 20A CONDUIT FILL DERATE= 1 NABCEP
<br /> MAXIMUM OUTPUT POWER 315 W AC VOLTAGE RISE CALCULATIONS DIST(FT) COND. ✓RISE(V) VEND(V) %VRISE AMB.TEMP.AMP.CORRECTION= 1 CERTIFIED
<br /> CEC WEIGHTED EFFICIENCY 9750% VRISE SEC.1(MICRO TO JBOX) 43.2 12 Cu. 2.09 242.09 0.87% ADJUSTED AMP.= 35 > 19.7
<br /> VRISE SEC.2(JBOXT0COMBINER BOX) 75 10 Cu. 2.99 242.99 1.25% COMBI N ER BOX TO INVERTER RATED AMPS= 15.7 AAC PV INSTALLATION
<br /> AC PHOTOVOLATIC MODULE MARKING(NEC 690.52) VRISE SEC.3(COMBINER BOX TO POI) 25 10 Cu. 1.00 241.00 0.42% MAIN PV OCPD(15) MAX.CURRENT(RATED AMPS X1.25)= 19.65 A AC PROFESSIONAL
<br /> NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 6.09 246.09 2.54% CONDUCTOR(THWN-2,COPPER(75°C TERM.))= 10 AWG Scott Gurney
<br /> #PV-011719-015866
<br /> NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC CONDUCTOR RATING= 35 A
<br /> MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL(NEC 690.54) CONDUIT FILL DERATE= 1 CONTRACTOR:
<br /> MAXIMUM AC CURRENT 1.0 A AC AC OUTPUT CURRENT 15.7 A AC AMB.TEMP.AMP.CORRECTION= 1 BRS FIELD OPS
<br /> MAXIMUM OCPD RATING FOR AC MODULE 20 A AC NOMINAL AC VOLTAGE 240 V AC ADJUSTED AMP.= 35 > 19.7 800-377-4480
<br /> U U
<br /> GROUNDING NOTES WIRING &CONDUIT NOTES Z Q
<br /> 1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.471 AND[NEC 250.50-60]SHALL BE 1. ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE O N
<br /> PROVIDED. PER[NEC 690.471, THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. 00
<br /> USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR (USE Q M 0 O
<br /> INADEQUATE, OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE POLARIS BLOCK OR NEUTRAL BAR). CC LLI C
<br /> USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE G > O M Lf�
<br /> 2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED Q
<br /> THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER) IF SMALLER THAN#6 AWG COPPER WIRE 4.UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF O Q W LV
<br /> PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)].
<br /> SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)]. 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE Z Q U) N
<br /> 3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. m J C C
<br /> COPPER AND
<br /> NDED
<br /> THE
<br /> OR A
<br /> MPLETE SYSTEM. 6. ALL PV
<br /> MUN WIRES BE TYPE USE-2, AND SINGLE-CONDUCTR CABLE LISTED AND
<br /> 4.PV SYSTEM SOHALL BEOGROUNDED EXISTING
<br /> IN ACCORDANCE TO[NEC 250 2O PROVIDE TABLE 0 1202],AND ALL METAL IDENTIFIED A CABLES
<br /> WIRED,TYPE EETRC-ER,OR EQUIVALENT;ROUTED TO SOURCES CIIRC ITT COMBINER BOXES AS c c
<br /> PARTS OR MODULE FRAMES ACCORDING TO[NEC 690.46]. REQUIRED. LU LU
<br /> 5.MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC 690.42]. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE C G = C W W
<br /> 6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS. G U) U)
<br /> MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8"ABOVE O >- > w
<br /> 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (13)(2)(A)], [NEC TABLE _J > V) U)
<br /> MANUFACTURER'S INSTALLATION INSTRUCTIONS. 310.15(B)(3)(A)],&[NEC 310.15(B)(3)(C)]. Cn _J= CD .I
<br /> LLU V
<br /> 8.ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9. EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90°C RATED,WET AND UV RESISTANT,AND UL O
<br /> GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP V N W Q IO
<br /> 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES.
<br /> EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 INSULATED, 90°C RATED,
<br /> 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V DRAWING BY:
<br /> EXPOSED. 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND
<br /> 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.451 AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. Michael Horley
<br /> MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION
<br /> DAMAGE). 13.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS PLOT DATE:
<br /> 12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC
<br /> GREEN
<br /> 3.ALL CONDUIT BETWEEN IF 4 AWG OR RTHE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE POSITIVE-PIOSITIVE GROUN EC D SYYSTEMS CONDUCTORS COLOR CODED GREY) October 16, 2023
<br /> GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK)
<br /> 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.471, [NEC TABLE 250.66], DC SYSTEM GEC SIZED 16.AC CONDUCTORS>4AWG COLOR CODED OR MARKED: PHASE A OR L1-BLACK, PHASE B OR L2-RED, PROJECT NUMBER:
<br /> ACCORDING TO[NEC 250.166],MINIMUM 8 AWG WHEN INSULATED,6 AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAY
<br /> 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE 845881
<br /> CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] USE-2 IS AVAILABLE AS UV WHITE
<br /> REGARDLESS OF VOLTAGE. 17.RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES.
<br /> 18. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, SHEET NAME:
<br /> FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.311, [NEC 250.118(10)]. DISCONNECTING /� /�
<br /> MEANS SHALL COMPLY WITH[NEC 690.131 AND[NEC 690.15]. ELEC CALCS
<br /> 19.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE COMPLYING WITH [NEC
<br /> 230.6(4)]AND SECURED NO GREATER THAN 6'APART PER[NEC 330.30(B)]. REVISION: PAGE NUMBER.
<br /> A PV6