EVERETT <br />WASHINGTON <br />Commercial Kitchen Hood System <br />Acceptance Test Checklist <br />INFORMATION HANDOUT C-10 <br />4.29.2020 <br />General <br />This document's intent is to provide contractors with guidelines outlining the expectations and <br />procedures for how the Everett Fire Marshal's Office will conduct an acceptance test of a commercial <br />kitchen hood system. This document addresses the most common aspects of a commercial kitchen hood <br />system acceptance tests, in cases where this document does not address a device or operation used <br />with your system IFC, NFPA 17A & 96, and/or Manufacturer Specifications will be used to determine <br />testing criteria. <br />ICPrIP_ral <br />PASS FAIL N/A <br />1. Fire Alarm Tech? - In buildings that are equipped with a fire alarm system, the ❑ ❑ ❑ <br />system installer as well as the fire alarm tech shall be present during acceptance <br />testing. <br />2. Approved Plans - The installing contractor shall have the approved/stamped set of ❑ ❑ ❑ <br />plans and the specific system installation manual located at the job site. <br />3. Check Plans - Verify that the suppression system, piping, and cooking equipment ❑ ❑ ❑ <br />are the same type/style identified on the approved plans. <br />4. NFPA 17A Report - Prior to final approval the installing contractor shall complete, ❑ ❑ ❑ <br />sign, and provide a copy of the NFPA 17A acceptance test report. <br />5. Appliance Signage - Signage shall be provided on the exhaust hood or system ❑ ❑ ❑ <br />cabinet, indicating the type and arrangement of cooking appliances protected by <br />the automatic fire -extinguishing system. Signage shall indicate appliances from left <br />to right, be durable, and the size, color, and lettering that allows it to be legible <br />from where an inspector may be standing to view the sign. <br />Building Fire Alarm System <br />PASS FAIL N/A <br />1. Fire Alarm - In buildings that are equipped with a fire alarm system, the ❑ ❑ ❑ <br />suppression system shall be interconnected so that the actuation of the <br />extinguishing system will sound the fire alarm and all notification devices. <br />Fire Marshal's Office 1 425.257.8100 1 everettwa.gov/fire <br />