My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
1021 NORTH PARK DR 2023-11-28
>
Address Records
>
NORTH PARK DR
>
1021
>
1021 NORTH PARK DR 2023-11-28
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
11/14/2023 1:47:09 PM
Creation date
11/9/2023 7:48:39 AM
Metadata
Fields
Template:
Address Document
Street Name
NORTH PARK DR
Street Number
1021
Imported From Microfiche
No
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
25
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
SYSTEM DESIGN SUMMARY <br /> 1. Intended for outdoor installation with free air inlet and outlet.Outdoor fan external static pressure available is less than 0.01—in,wc. <br /> 2. Minimum outdoor operating air temperature for cooling mode without low—ambient operation accessory is 55°F(12.8°C). <br /> 3. Maximum outdoor operating air temperature is 125°F(51.7°C). <br /> 4. For reliable operation,unit should be level in all horizontal planes. <br /> 5. For interconnecting refrigerant tube lengths greater than 80 ft(23.4 m)and/or 35 ft(10.7 m)vertical differential,consult Residential <br /> Piping and Longline Guideline and Service Manual available from equipment distributor. <br /> 6. If any refrigerant tubing is buried,provide a 6 in. (152.4 mm)vertical rise to the valve connections at the unit. Refrigerant tubing <br /> lengths up to 36 in.(914.4 mm)may be buried without further consideration.Do not bury refrigerant lines longer than 36 in.(914.4 <br /> mm). <br /> 7. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector <br /> provided. <br /> 8. Do not apply capillary tube indoor coils to these units. <br /> 9. Factory—supplied filter drier must be installed. <br /> ©2015 Bryant Heating&Cooling Systems 7310 W.Morris St. Indianapolis,IN 46231 Edition Date: 08/15 Catalog No.PDS126B-05 <br /> Manufacturer reserves the right to discontinue,or change at any time,specifications or designs without notice and without Incurring obligations. Replaces:PDS126B-04 <br /> 20 <br />
The URL can be used to link to this page
Your browser does not support the video tag.