Conductor, Conduit, and OCPD Sizing Validation 2.Wire, Conduit, and OCPD Code Compliance Validation <br /> 1. Maximum System DC Voltage Test 2.1.#1: Branch cables: Microinverter to Transition Box <br /> 1.1. Enphase microinverter system w112 Hyundai HIS-S400YH(BK)(40OW)s Circuit Section Properties G. Minimum Required EGC Size 14 AWG <br /> see NEC Table 250.122 <br /> Conductor 12 AWG THHN/THWN-2 in Enphase <br /> Array Properties NEC Code Validation Tests Q Cable,Copper The smallest EGC size allowed is 14 AWG for OCPD rating 15A <br /> Arra Type Microinverter Arra Equipment Ground Conductor EGC 6 AWG Bare,Copper according to Table 250.122. <br /> PV Source Circuit maximum Voc must not exceed PASS OCPD(s) 15A <br /> System Description Enphase microinverter system w112 600V NEC Code Validation Tests <br /> Hyundai H HiS-S400YH BK 400W s Raceway/Cable/Cable Cable <br /> Hyundai0YH BK 400W 49.07V<600V=true Lowest Terminal Temperature 90°C <br /> Module Ratingo <br /> Highest number of modules in series 1 OCPD <br /> ( e at least 125/o of Continuous PASS <br /> Current <br /> in a PV Source Circuit Maximum Wire Temperature 49°C (NEC 240,4) <br /> Design Low Temp. -6.2°C Power Source Description Branch of 6 IQ8A-72-2-US 15A-8.7A X 1.25=true <br /> Module voc 45.3V microinverters <br /> Power Source Current 8.7A Derated ampacity must exceed OCPD rating,or PASS <br /> Temp.Coefficient voc -0.121V/C Voltage 240V rating of next smaller OCPD(NEC 240.4) <br /> 25A-15A(OCPD Rating)=true <br /> NEC Code Calculations <br /> NEC Code Calculations OCPD rating must not exceed max OCPD rating PASS <br /> A. Maximum Voltage of PV Source Circuit 49.07V for conductor(NEC 240.4) <br /> see NEC 690.7(A) A. Continuous Current 8.7A 15(OCPD Rating)<-20A =true <br /> see NECAdic%100 <br /> NEC 690.7(A)requires that if the PV module manufacturer provides a Equipment maximum rated output current is 6 X 145A=8.7A Derated Ampacity must be greater than or equal to PASS <br /> qpp . <br /> temperature coefficient of open-circuit voltage,it must be used to the Continuous Current(NEC Article 100) <br /> calculate the PV array's maximum system voltage.It includes an 25A-8.7A=true <br /> information note recommending the use of the ASHRAE'Extreme Annual B.Ampacity of Conductor 30A <br /> Mean Minimum Design Dry Bulb Temperature'as the design low see NEC Table 310.16 Conductor Ampacity must be at least 125%of PASS <br /> temperature.Using these values,the module Voc(45.3V)will increase to Ampacity(30°C)for a copper conductor with 90°C insulation in Continuous Current(NEC 215.2(A)(1)) <br /> 49.07V at the design low temperature(-6.2°C). conduit/cable is 30A. 30A-8.7A x 1.25=true <br /> (-6.2°C-25°C)X-0.121V/C+45.3V=49.07V <br /> The module Voc at the design low temperature is 49.07V. C. Derated Ampacity Of Conductor 25A • Max current for terminal must beat least 125%of PASS <br /> 49.07V X 1=49.07V see NEC 310.15(g)(2),NEC Table 310.15(CJ(1J,andNECAdic%100 the Continuous Current.(NEC 110.14(C)) <br /> 30A>=8.7A X 1.25 =true <br /> The temperature factor for 90°C insulation at 49°C is 0.82. <br /> The fill factor for a conduit/cable that has 2 wires is 1. EGC must meet code requirements for minimum PASS <br /> The ampacity derated for Conditions of Use is the product of the size(NEC Table 250.122) <br /> conductor ampacity(30A)multiplied by the temperature factor(0.82)and 6 AWG>=14 AWG=true <br /> by the fill factor(1). <br /> 30A X 0.82 X 1=24.6A rounded to 25A <br /> D. Max Current for Terminal Temp. Rating 30A <br /> see NEC 110.14(C) <br /> The lowest temperature rating for this conductor at any termination is <br /> 90°C. <br /> Using the method specified in NEC 110.14(C),the maximum current <br /> permitted to ensure that the device terminal temperature does not exceed <br /> its 90°C rating would be the amount referenced in the 90°C column in <br /> NEC Table 310.16,which is 30A. <br /> E. Minimum Allowed OCPD Rating 11A <br /> see NEC 240.4 <br /> NEC 690.9(8)(1)requires OCPD be rated for no less than 1.25 times <br /> Continuous Current of the circuit. <br /> 8.7A X 1.25=10.88A <br /> F. Maximum Allowed OCPD Rating 20A <br /> see NEC 240.4(D) <br /> NEC 240.4(D)requires that OCPD rating not exceed 20A when <br /> protecting a Copper 12 AWG conductor. <br />