PPurelight <br /> RT Mini Connection Calculation <br /> This calculation justifies the connection of the solar panels to existing roof members, by showing the connection <br /> capacity is equal to or greater than the uplift force demands. Minimum embedment is 1.5 inches, <br /> Connection Demand <br /> SOLAR PANEL <br /> Spacing perpendicular to rail 32.5 in (1/2 panel length) ROOFING <br /> Roof Angle 23 degrees AFOOT <br /> Roof Type Hip <br /> Wind Speed 110 mph ROOINI <br /> MINI <br /> CHIKO <br /> Topographic Factor, K,t 1 <br /> Directionality Factor, Kd 0.85 <br /> Elevation Factor, Ke 0.99 Mount through roof sheathing <br /> into existing ratters <br /> Velocity Pressure, q, 16.1 psf <br /> Zone 1 Zone 2r Zone 3 <br /> Spacing parallel to rail 48 48 48 in (max) <br /> Effective Wind Area on each connection 10.8 10.8 10.8 ft` <br /> GCp (max) 1.90 1.97 1.97 <br /> Exposed Panels? (YE = 1.5) No No No <br /> Pressure Equalization Factor, ya 0.79 0.79 0.79 <br /> Uplift Force 24.1 25.0 25.0 psf <br /> Max. Uplift Force/ Connection (1.0 WL) 260.6 271.2 271.2 lbs <br /> ASD Factored (0.6 WL) 156.4 162.7 162.7 lbs <br /> Solar Dead Load (0.6 DL) 17.2 17.2 17.2 lbs <br /> Max. Uplift Force (0.6 WL- 0.6 DL) 139.1 145.5 145.5 lbs <br /> Connection Capacity <br /> Connection Type RT Mini (Deck or Rafter Mount) <br /> Total Allowable Capacity 180.0 lbs (per manufacturer) <br /> Compare ASD Factored Demand to Capacity <br /> Demand 145.5 lbs <br /> Capacity 180.0 lbs <br /> Result Capacity exceeds demands. Therefore, connection passes. <br />