Laserfiche WebLink
➢ The fire alarm system will be monitored by a U.L. Listed Monitoring Center for Remote <br /> System Type monitoring. U.L. Certificate enclosed. <br /> ➢ Off Premise notification shall be accomplished by cellular sole path communication <br /> method. <br /> ➢ Manual Pull Station,Heat Detector, smoke detection and water flow activation will <br /> generate an alarm condition. <br /> ➢ The Fire Alarm Control Panel has a backup power source of two 12vdc, 18amp battery <br /> for 12vdc operation,capable of meeting/exceeding the 24hr standby period followed by 5 <br /> minutes of alarm at maximum system load. <br /> ➢ Copies of Fire Marshal approved, stamped, signed drawings along with a complete user's <br /> manual will be left with the Site Manager for their reference and all future annual <br /> inspections. Site personnel will be provided training on proper use of the Fire Alarm <br /> System by the installation contractor. <br /> ➢ An NFPA Record of Completion will be submitted. As-Built(Record) drawings will be <br /> generated upon completion of a successful final inspection and copies will be provided to <br /> the customer and kept on file with ADT Security Services. <br />