Laserfiche WebLink
PEM POWER CABLE (SUPPLIED LEGEND <br /> WITH PEM) FACP BATTERY CALCULATIONS <br /> COMPONENTS QTY, STANDBY ALARM <br /> CURRENT CURRENT <br /> AFC-100(FACE) 1 0.13000A 022000A GENERAL_ NOTES <br /> UD-2000(DACT) 1 0.01600A 0.02300A <br /> SLC DEVICES SUPERVISORY ALARM <br /> CURRENT CURRENT <br /> PAD-PD 1 0.00030A 0.00030A 0.00030A 0.00030A <br /> PAD-HD 0 1 0.00030A 0.00030A O.000OOA O.000OOA99 F B REFERENCE DRAWINGS <br /> PAD-DUCT 0 0.00030A 0.00030A O.000OOA O.000OOA <br /> 3/4"C - 2#14THHN,1#14G 'Z 0 PAD1Oo-PSSA/PSDA 1 0.00020A 0.00020A 0.00020A 0.00020A <br /> TG-PEM RED PAD100-RM 0 0.00024A 0.00024A 0.000OOA 0.000OOA <br /> Duc PAD-MIM 2 0.00020A 0.00040A 0.00020A 0.00040A <br /> FACP EVT-FA-45-06 TG-7FS PAD100-DIM 0 0.00024A 0.00024A 0 OOOOOA o.000OOA <br /> (BY FIRE ALARM VENDOR) DNN 1 1 4 7 STANDBY ALARM CONSTRUCTION NOTES <br /> CURRENT CURRENT <br /> R NAC CRT 1(AUX PWR) 0.018A 0.11000A 0.01800A 0.11000A <br /> TO <br /> NAG CRT 2 o.00A o.00000A o.0o000A o.00000A PROVIDE CELLULAR DIALER, AND MOUNT ADJACENT E <br /> 3 THE BUILDING FACP. CONFIGURE DIALER TO PROVIDE <br /> ❑ T - o.00A o.0oo00A o.000OOA 0.00000A SOLE PATH COMMUNICATION. DIALER SHALL BE <br /> SLC ALARM LED o.00A o.o3sooA o.00000A 0.03600A COMPATIBLE WITH AT&T CELL SERVICE. <br /> TOTAL 0.16490A 0.38990A <br /> DC STC2 STCiTRIP BATT AC <br /> TOTAL STANDBY CURRENT DRAW= 0.1649 AMPS 2 PROVIDE 1 CONDUIT PENETRATION FOR PHONE AND <br /> 1 2 1 23456 1 23 1 2 G ( ) <br /> 0 � 0� 00 x STANDBY TIME 48 HOURS FIRE ALARM CONNECTIONS. WIRE AS SHOWN. PROVIDE <br /> STANDBY AMP HOUR TOTAL= 7.9152 AH ADDRESSABLE MODULE AS NECESSARY TO PROVIDE <br /> TOTAL ALARM CURRENT DRAW= 0.3899 AMPS GENERAL TROUBLE ALARM FROM CELLULAR DIALER TO <br /> RED <br /> EOL(k NEEDED) X ALARM TIME 0.167 HOURS BUILDING FACP. <br /> ALARM AMP HOUR TOTAL- 0.065 AH <br /> STANDBY AN+ ALARM AN - 7.98 AN PROVIDE (1) CONDUIT PENETRATION FOR 24/12VDC <br /> X DE-RATING FACTOR zo(zo%) POWER AND EARTH GROUND FROM THE BUILDING FACP <br /> 3/4"C - (1) PHONE CABLE, TOTAL AN REQUIRED- 9.576 AH POWER SUPPLY. PROVIDE POWER AND EXPANSION <br /> MINIMUM BATTERY SIZE NEEDED: 10 AN MODULE AND WIRE AS SHOWN. MAINTAIN <br /> (1) 2 CONDUCTOR FPL OR BATTERY SIZE PROVIDED: 12 AN MANUFACTURER'S REQUIRED 1/4" SEPARATION <br /> APPROVED EQUAL NOTE: 0.117 EQUALS 10 MINUTES of ALARM TIME BETWEEN POWER AND COMMUNICATION WIRING. <br /> ® PROVIDE PHENOLIC LABEL, WHITE LETTERING, RED <br /> FACP VOLTAGE DROP CALCULATION BACKGROUND, THAT READS: <br /> FIRE ALARM SYSTEM COMMUNICATIONS DETAIL CIRCUIT SUPPLY ALARM OHMS NGT TOTAL LAST DEVICE VOL <br /> NAME VOLTAGE CURRENT WIRE TYPE 1000 FEET RESISTANCE VOLTAGE DROP % FIRE ALARM CELLULAR DIALER <br /> NAC1(AUX) 24 VDC 0.110 A #14AWG SOLID 2.52 10 0.0504 20.395 VDC 0.03% <br /> SCALE: NONE E26 0 E506 NAC2 24 voc 0.000 A g14Awc soup 2.52 0 0 00.00 voc o% PROVIDE CELL ANTENNA AND EVALUATE FIELD SIGNAL <br /> STRENGTH IN ACCORDANCE WITH DETAIL 2. INSTALL <br /> N/A 24 VDC 0.000 A #14AwG SOLD 2.52 0 0 00.00 VDC 0% CONDUIT AND EXTENDED ANTENNA CABLE AS <br /> N/A 24 voc 0.000 A g14AwG SOLID 2.52 0 0 00.00 VDC 0% NECESSARY TO REMOTE MOUNT ANTENNA IF COVERAGE <br /> STEP 1: VERIFY SIGNAL STRENGTH AT PROPOSED LOCATION FOR CELLULAR COMMUNICATOR PANEL INDICATED ON IS NOT SUITABLE AT FACP LOCATION, UPDATE BOM <br /> DRAWINGS. IF ACCEPTABLE *SIGNAL STRENGTH IS ACQUIRED, SKIP TO STEP 5. WITH SELECTED CABLE LENGTH AND PROVIDE REDLINES <br /> STEP 2: IF ORIGINALLY PROPOSED LOCATION IS INADEQUATE, FIELD TEST *SIGNAL STRENGTH WITHIN A 20FT RADIUS TO BOEING ENGINEER. <br /> TO IDENTIFY LOCATIONS) SUITABLE FOR INSTALLATION OF REMOTE/EXTERNAL CELLULAR ANTENNA. © FOR REMOTE INSTALLATIONS PROVIDE PHENOLIC LABEL, <br /> COORDINATE THE FINAL ANTENNA LOCATION WITH BOEING AND SPACE USERS (IF IMPACTED) FOR WHITE LETTERING, RED BACKGROUND, THAT READS: <br /> APPROVAL PRIOR TO ROUGH-IN AND SKIP TO STEP 4. <br /> STEP 3: IF ACCEPTABLE *SIGNAL STRENGTH IS NOT ACHIEVED WITHIN 20FT OF ORIGINAL PROPOSED LOCATION FOR 'TIRE ALARM CELLULAR ANTENNA" <br /> CELLULAR COMMUNICATOR PANEL, PROPOSE ALTERNATE LOCATION FOR CELLULAR PANEL. COORDINATE <br /> WITH BOEING AND SPACE USERS FOR POTENTIAL LOCATIONS, PREFERABLY NEAR ORIGINAL LOCATION. INSIDE CELL ENCLOSURE POST COMMUNICATOR <br /> SETTINGS AND CELLUAR PHONE NUMBER. PROVIDE <br /> STEP 4: LOCATE AND PROVIDE EXTERNAL CELLULAR ANTENNA, EXTERIOR MOUNTING BRACKET AND COAXIAL CABLE PRINTED LABEL, HANDWRITTEN INFORMATION IS NOT <br /> FROM CELLULAR COMMUNICATOR TO THE ANTENNA. THE ANTENNA AND PANEL SHOULD BE LOCATED ACCEPTABLE. PROVIDE SETTINGS AND CELLULAR <br /> WITHIN 20FT OF EACH OTHER. INFORMATION TO BOEING ENGINEER. <br /> STEP 5: PROVIDE 24VDC POWER, MONITORING CIRCUIT, AND TELEPHONE LINE TO CELLULAR COMMUNICATOR FROM <br /> BUILDING FACP. <br /> STEP 6: PROVIDE REQUIRED SET-UP, PROGRAMMING AND TESTING OF CELLULAR COMMUNICATOR EQUIPMENT PER <br /> THE MANUFACTURER'S INSTRUCTIONS. CELLULAR DIALER SHALL BE CONFIGURED AND INSTALLED AS A <br /> SOLE PATH FOR FIRE COMMUNICATIONS. <br /> *ACCEPTABLE SIGNAL STRENGTH SHALL BE DETERMINED BY MANUFACTURERS SPECIFICATIONS AND LOCAL AHJ <br /> ORDINANCES. <br /> SMK @FACP <br /> CELLULAR E NNECOMMUNICATOR INSTALLATION SEQUENCE E2soESos sLACP ANA G PHON LINE#*TWO <br /> CELLDIAULAR MOSIGNIITOSENTTOCENTRAD <br /> (PRIMARY BOEING FIRE DEPARTMENT <br /> 45-06 FACP SEPARATE PATHWAYSFOR SIGNAL REQUIRED BY CODE, AS SHOWN. <br /> SV45-06 TAMPER <br /> SV45-06 WF <br /> ANA�O PHON Y)INE <br /> 4501 BUILDING SYSTEM FACP POINTS EVT-FA-45-06 <br /> POINT NUMBER/ZONE BOEING DESCRIPTION FACP POINT - COMMENTS - GRID/SHEET LOC. U:02 BILL OF MATERIALS <br /> _1:001 1 SV45-06 SMK @ FACP FACP SMOKE DETECTOR - F1/E260 WF VS L XE2VO3-2R2/13Q ITEM QTY. PART NO. MANUFACTURER DESCRIPTION <br /> L1:002 2 SV45-06 MAN PULL @ FACP FACP MANUAL PULL STATION - F1/E260 11". 1//. <br /> 1 1 3992753 POTTER FIRE ALARM CONTROL PANEL <br /> L1:003 3 SV45-06 TAMPER SPRINKLER TAMPER SWITCH - C1/E260 <br /> 2 1 3992769 POTTER UD-2000 DACT CARD <br /> _1:004 4 SV45-06 WF WATERFLOW PRESSURE SWITCH - C1/E260 <br /> 3 1 3992732 POTTER PAD100 6" BASE <br /> MAN PULL @ FACP 4 1 3992770 POTTER PAD200 PHOTO DETECTOR <br /> Or BUILDING FACP POINTS LIST BUILDING FIRE ALARM SYSTEM RISER 5 1 3992720 POTTER PAD100 PULL STATION6 2 3992700 POTTER PAD100-MIM <br /> SCALE: NONE E506 SCALE: NONE E506 <br /> 7 2 1 SLA1104 POWERPATROL 12VDC 12 AH BATTERIES <br /> 8 1 1 TG-7FS-A ITELGUARD ATT CELLULAR DIALER <br /> ir be 1 9 1 1 ISSU00689 ISPACEAGE IFIRE ALARM STORAGE CABINET <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE ACCEPTABILITY DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE <br /> THIS DESIGN AND/OR H K FIRE ALARM SYSTEM DETAILS A 04.28.23 0 <br /> NEW FIRE MONITORING PANEL REPLACEMENT 27851053 MDK Ti 09.12.22 SPECIFICATION IS APPROVED SHEET <br /> A SHOP DRAWING AGOW/JS 04.28.23BOE/A/G® m APPROVED BY DEPT. DATE TTLE E506 m <br /> CHECKED <br /> H <br /> Li <br /> .n.O..D',.ei. APPROVED BUILDING 45-006 JOB N0, COMP N0. <br /> -�„p„ APPROVED ELECTRICAL MASTER EVERETT, WA DWG NO, 45-006-E506 <br />