Laserfiche WebLink
Specifications Approved Releasing Solenoids <br /> Physical Manufacturer Part number Rating Current Freq <br /> Flush Mount Dim: 14.75"W x 25"H x 4"D Asco T8210A107 24 VDC 3 A max 0 Hz <br /> (37.5 W x 63.5 H x 10.16 D cm) Asco 8210G207 24 VDC 3 A max 0 Hz <br /> Overall Dimensions:1 6"W x 26.4"H x 4.65"D Ordering Information <br /> (40.6 W x 67 H x 11.8 D cm) <br /> IFP-2000 Intelligent Fire Alarm Control Panel <br /> Weight: 28 lbs. (12.8 kg) IFP-2000HV High Voltage (240VAC) Intelligent Fire <br /> Color: Red Alarm Control Panel <br /> RPS-2000 Intelligent Fire Alarm Control Panel <br /> Environmental without built in display <br /> Operating Temperature: 32°F— 120°F (0°C—49°C) RPS-2000HV High Voltage (240VAC) Intelligent Fire <br /> Humidity: 10%—93% non-condensing d Is rP a display Panel without built-in <br /> Electrical SBUS Accessories <br /> IFP-2000 AC: 120 VAC, 50/60 Hz, S.OA RA-2000 Red Remote Annunciator. Four line LCD <br /> annunciator with 40 characters per line <br /> IFP-2000HV AC: 240 VAC, 50/60 Hz, 2.5A RA-2000GRAY Gray Remote Annunciator Four line LCD <br /> Total Accessory Load: 9A @ 24 VDC power-limited annunciator with 40 characters per line <br /> Standby Current: 290 mA 5815XL Signal Line Circuit (SLC) Expander <br /> Alarm Current: 530 mA RPS-1000 6 amp Intelligent Power Module with 6 <br /> flexputs <br /> Battery Charging Capacity: 17 to 55 AH 5496 6 amp intelligent Power Module <br /> Battery Size: 18 AH max. allowed in control panel cabinet. 5824 Serial/Parallel Printer Interface Module <br /> Larger capacity batteries can be housed in RBB or AB-55 5880 LED 1/0 Module <br /> accessory cabinet. 5865-3 &5865-4 LED Fire Annunciators <br /> 5883 Relay Interface Board <br /> Flexput Circuits IDP Devices <br /> Eight circuits that can be programmed individually as: <br /> Notification Circuits: 3A per circuit @ 24 VDC, power-limited See the spe IDP devices <br /> ecification sheets listed below for a complete <br /> Auxiliary Power Circuits: 3A per circuit @ 24 VDC, power- <br /> listing of th <br /> limited 350361 Intelligent Device Protocol devices <br /> specification sheet <br /> Initiation Circuit: 100 mA per circuit @ 24 VDC, power-limited Hochiki Devices <br /> See the specification sheets listed below for a complete <br /> Indicator Lights listing of the Hochiki devices <br /> General Alarm (Red): On when in alarm 350360 Hochiki (SD) Device Protocol devices <br /> Supervisory(Yellow): On when a supervisory condition exists specification sheet <br /> System Troubles (Yellow): On when a trouble condition exists Networking Accessories <br /> IFP-RPT-FO Network repeater board for fiber optic <br /> System Silenced (Yellow): On when an alarm, trouble or IFP-RPT-UTP Network repeater board for twisted pair <br /> supervisory condition has been silenced but not yet cleared wire <br /> System Power(Green): Off for AC failure; On when power IFP-RPT-UTP-KIT Wired twisted pair network repeater card <br /> systems are normal and cabinet kit. <br /> IFP-RPT-FO-KIT Fiber optic network repeater card and <br /> Telephone cabinet kit. <br /> Requirements: FCC Part 15 & Part 68 approved Miscellaneous Accessories <br /> Jack: RJ31X(two required) 5655 Silent Knight Software Suite -2. <br /> Provides programming, upload <br /> Approvals /download, and event reporting <br /> NFPA 13, NFPA 15, NFPA 16, NFPA 70, & NFPA 72: Central RBB Remote Battery Box Accessory Cabinet. <br /> Station; Remote Signalling; Local Protective Signalling Use for backup batteries up to 35 AH. <br /> Dimensions: 16"W x 10" H x 6" D <br /> Systems;Auxiliary Protected Premises Unit; &Water Deluge (40.64 W x 25.4 H x 15.24 D cm) <br /> Releasing Service. Suitable for automatic, manual, waterflow, AB-55 Remote Battery Box Accessory Cabinet. <br /> sprinkler supervisory(DACT non-coded)signalling services Use for backup batteries that are <br /> Other Approvals: UL Listed, FM Approved, City of New York, 35 AH -55AH. <br /> and CSFM Dimensions: 20"W x 12" H x 7.5" D <br /> (50.8 W x 30.48 H x 19.05 D cm) <br /> SILENT This document is not intended to be used for installation purposes.We try to keep <br /> our product information up-to-date and accurate.We cannot cover all specific <br /> KNIGHT applications or anticipate all requirements.All specifications are subject to change <br /> without notice. For more information, contact Silent Knight 12 Clintonville Road, <br /> Northford, CT 06472-1610 Phone: (800)328-0103, Fax: (203)484-7118. <br /> by Honeywell www.farenhyt.com Made in the U.S.A. <br />