GENERAL NOTES <br /> D JUNCTION BOX 4S UNLESS NOTED OTHERWISE <br /> OS IONIZATION SMOKE DETECTOR <br /> 4) HEAT DETECTOR FIXED 135° <br /> ❑F MANUAL STATION, DOUBLE ACTING <br /> ® STROBE ALARM <br /> ®Q AUDIBLE/VISUAL ALARM <br /> B FIRE ALARM PANEL <br /> O ADT PANEL <br /> FAC CELLULAR COMMUNICATOR <br /> GENERAL NOTES <br /> 4 3 2 1. RACEWAY: 1/2" RGS, UNLESS OTHERWISE NOTED. <br /> 2. CONDUCTORS SHOWN: #10 AWG, STRANDED COPPER, <br /> INSULATION TYPE XHHW-2, UNLESS OTHERWISE NOTED. <br /> 3. COLOR CODE CONDUCTORS: INDENTIFY CONDUCTORS <br /> WHICH DO NOT HAVE APPROPRIATELY COLORED INSULATION <br /> WITH COLOR TAPE WHEREVER CONDUCTORS ARE <br /> ACCESSIBLE. IDENTIFY INSULATED GROUND CONDUCTORS <br /> PER NEC (USING TAPE). COLOR CODE AS FOLLOWS: <br /> 208Y 120V 480Y 277V <br /> A4 (LEFT BUS IN PNL) BLACKBROWN <br /> zW 1w ------ BC (CENTER BUS IN PNL) RED ORANGE <br /> CO (RIGHT BUS IN PNL) BLUE YELLOW <br /> NEUTRAL WHITE GRAY <br /> EQUIPMENT GROUND GREENGREEN <br /> ISOLATED GROUND GRN/YEL* GRN/YEL* <br /> *GREEN WITH YELLOW TRACER <br /> 4. DYMO LABEL EACH RECEPTACLE, JUNCTION/OUTLET <br /> BOX AND SWITCH WITH CIRCUIT IDENTIFICATION. <br /> A <br /> �45-27,6.SMK W 45- 76 SMK E 5. ALL RECEPTACLES SHALL BE NEMA 5-20R RATED <br /> 11, 1_1:11 0 ZON #: 10, _1:10 2 AND INSTALLED AT A HEIGHT OF 48" ABOVE FINISHED <br /> FLOOR. <br /> 6.TO FIRE ALARM PANEL LOCATED Q,=N COMPLETTIION OF PRR CORD <br /> OJST RECORD (ECT_BUILT) PANEL SCHEDULES UPON <br /> IN BLDG 45-201, 3/4"C - 4#12 <br /> CTION NOTES SMOKE DETECTORS (QTY. 2) WITHKE DETECTORS COMPATIBLE WITH THEFACE. REUSE CONDUIT AND WIRE ASE <br /> B <br /> NOTE: ALL AREAS (INSIDE AND OUTSIDE OF BUILDING) <br /> SHALL BE CLASSIFIED CLASS I, DIVISION 2 UP TO <br /> 18" ABOVE FINISHED GRADE IN ACCORDANCE WITH <br /> THE NEC. <br /> POWER AND FIRE ALARM PLAN N <br /> SCALE: 1/4"=1'-0" <br /> G <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE <br /> HSC ESTN BILI R CHECKED POWER AND FIRE ALARM PLAN 27851053 A 04.28.23 <br /> NEW FIRE PANEL INSTALLATION 27851053 CLS MDK 08.05.22 SPECIFICATION IS APPROVED SHEET <br /> A SHOP DRAWINGS AGOW/JS 04.28.23BOE/NG® m APPROVED BY DEPT. DATE TITLE 1 E60 m <br /> CHECKED <br /> ete <br /> Lin BUILDING 45-276 DB ND DMP Na. <br /> APPROVED <br /> wcE.amcmxwmm.„v, 3 <br /> APPROVED ELECTRICAL MASTER EVERETT, WA ID11 No. 45-276-1E60 <br />