MODULE SPECIFICATIONS REC Solar REC420AA PURE-R DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS <br /> RATED POWER(STC) 420 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMP MICROINVERTER TO MAX.SHORT CIRCUIT CURRRENT(ISC) = 10.5 A AC <br /> MODULE VOC 59.4 V DC STATE Washington JUNCTION BOX(1) MAX.CURRENT(ISC X1.25)= 13.1 A AC <br /> MODULE VMP 50 V DC CITY Everett CONDUCTOR(TC-ER,COPPER(90'C))= 12 AWG BLUE RAVEN <br /> MODULE IMP 8.4 A DC WEATHER STATION SNOHOMISH CO CONDUCTOR RATING= 30 A <br /> MODULE ISC 8.88 A DC ASHRAE EXTREME LOW TEMP('C) -5 AMB.TEMP.AMP.CORRECTION= 1 <br /> VOC CORRECTION -0.24 %/'C ASHRAE 2%AVG.HIGH TEMP('C) 26 ADJUSTED AMP.= 30 > 13.1 1403 N. Research Way <br /> VMP CORRECTION -0.24%/'C JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 10.5 A AC Orem, UT 84097 <br /> SERIES FUSE RATING 25 A DC SYSTEM ELECTRICAL SPECIFICATIONS CIR I CIR 2 UR 3 CIR 4 CIR 5 CIR 6 JUNCTION BOX(2) MAX,CURRENT(ISC X1.25)= 13.1 A AC 8ERAV.4480 <br /> W W W.BLU RAVENSOLAR.COM <br /> ADJ, MODULE VOC @ ASHRAE LOW TEMP 63.7 V DC NUMBER OF MODULES PER MPPT 8 CONDUCTOR(UF-B,COPPER(60'C))= 10 AWG <br /> CONFIDENTIAL-THE INFORMATION <br /> ADJ.MODULE VMP @ ASHRAE_ EM <br /> 2%AVG.HIGH TP 46.0 V DC DC POWER RATING PER CIRCUIT(STC) 33_6_0_ CONDUCTOR RATING= 30 A HEREIN CONTAINED SHALL NOT BE <br /> T TOTAL MODULE NUMBER 8 CONDUIT FILL DERATE= 1 USED FOR THE BENEFIT OF ANYONE <br /> EXCEPT BLUE RAVEN SOLAR NOR <br /> MICROINVERTER SPECIFICATIONS Enphase IQ7X Mlcrolnverters STC RATING OF ARRAY 3360 AMB.TEMP.AMP.CORRECTION= 1 SHALL IT BE DISCLOSED IN WHOLE OR <br /> IN PART TO OTHERS OUTSIDE <br /> POWER POINT TRACKING(MPPT)MIN/MAX 53 - 64 V DC AC CURRENT @ MAX POWER POINT(IMP 10.5 ADJUSTED AMP. = 30 > 13.1 RECIPIENTS ORGANIZATION,EXCEPT <br /> MAXIMUM INPUT VOLTAGE 79.5VDC MAX.CURRENT(IMP X 1.25) 13.1 JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC) = 10.5AAC IN CONNECTION WITH THE SALE AND <br /> USE OF THE RESPECTIVE EQUIPMENT, <br /> MAXIMUM DC SHORT CIRCUIT CURRENT 10 A DC OCPD CURRENT RATING PER CIRCUIT 20 COMBINER BOX(3) MAX.CURRENT(ISC X1.25)= 13.1 A AC WITHOUT THE WRITTEN PERMISSION <br /> MAXIMUM USABLE DC INPUT POWER 460 W MAX.COMB.ARRAY AC CURRENT(IMP) 10.5 CONDUCTOR(UF-B,COPPER(60'C))= 10 AWG OF BLUE RAVEN SOLAR LLC. <br /> MAXIMUM OUTPUT CURRENT 1.31 A AC MAX.ARRAY AC POWER 2520W AC CONDUCTOR RATING= 30 A <br /> AC OVERCURRENT PROTECTION 20 A CONDUIT FILL DERATE= 1 NABCEP <br /> MAXIMUM OUTPUT POWER 315 W AC VOLTAGE RISE CALCULATIONS DIST(FT) COND, VRISE(V) VEND(V) %VRISE AMB.TEMP.AMP.CORRECTION= 1 CERTIFIED <br /> CEC WEIGHTED EFFICIENCY 9750% VRISE SEC. 1(MICRO TO JBOX) 28.8 12 Cu. 0.93 240.93 0.39% ADJUSTED AMP.= 30 > 13,1 <br /> VRISE SEC.2(JBOX TO COMBINER BOX) 50 10 Cu. 1.33 241.33 0.55% COMBINER BOX TO INVERTER RATED AMPS= 10.5 A AC PV INSTALLATION <br /> AC PHOTOVOLATIC MODULE MARKING(NEC 690.52) VRISE SEC_3(COMBINER BOX TO POI) 5 10 Cu. 0.13 240.13 0.06% MAIN PV OCPD(15) MAX.CURRENT(RATED AMPS X1.25)= 13.1 A AC PROFESSIONAL <br /> NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 2.39 242.39 1.00% CONDUCTOR(THWN-2,COPPER(75'C TERM.))= 10 AWG Scott Gurney <br /> #PV-011719-015866 <br /> NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC CONDUCTOR RATING= 35 A <br /> MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL(NEC 690.54) CONDUIT FILL DERATE= 1 CONTRACTOR: <br /> MAXIMUM AC CURRENT 1.0 A AC AC OUTPUT CURRENT 10.S A AC AMB.TEMP.AMP.CORRECTION= 1 BRS FIELD OPS <br /> MAXIMUM OCPD RATING FOR AC MODULE 20 A AC NOMINAL AC VOLTAGE 240 V AC ADJUSTED AMP.= 35 > 13.1 800-377-4480 <br /> U U <br /> GROUNDING NOTES WIRING &CONDUIT NOTES Z Q 0 <br /> 1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.47]AND[NEC 250.50-60]SHALL BE 1.ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE O M <br /> PROVIDED. PER[NEC 690.47],THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. Q C) <br /> (USE AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR USELf) M <br /> INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE POLARIS BLOCK OR NEUTRAL BAR). CC 00 <br /> USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE G Cf) CV M <br /> 2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED ; <br /> THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER) IF SMALLER THAN#6 AWG COPPER WIRE 4.UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF Q LLI W <br /> PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)]. LL O N N <br /> SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)]. 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE - <br /> 3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. Z y <br /> COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6. ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2,AND SINGLE-CONDUCTOR CABLE LISTED AND O 0) <br /> IDENTIFIED PARTS SYSTEM MODULE FRAMES ACCORD NG TO[N ONCE TO[NEC 250.21],[NEC TABLE 250.122],AND ALL METAL REQUIRED.AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS ��N�µ1 W �q't W 0 � U) LU Lu <br /> 6.5.TIHHE GRO NDIING CODULE SOURCE IONN RCUITS CTION TO A MO ULESHALL BE ESHALLIN CBE ARRANGED SUCH CORDANCE TO[NEC T HAT THE REMOVAL OF A COND C 7.ALL OTORSCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE �Q'��pF W�SH2,1^ E� O 0 CU �j <br /> MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8"ABOVE Y C N <br /> 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE x i <br /> MANUFACTURER'S INSTALLATION INSTRUCTIONS. 310.15(B)(3)(A)],&[NEC 310.15(13)(3)(C)]. r = <br /> 8.ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9.EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90-C RATED,WET AND UV RESISTANT,AND UL > <br /> GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP V ti W Q in <br /> 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES. .4 <br /> EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHNrrHWN-2 INSULATED, 90°C RATED, 'P ,P 54072 <br /> 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V Gi< �Glsi-e � t1� DRAWING BY: <br /> EXPOSED. 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND F`rS7UNALti�G` <br /> 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. Brendan Fillmore <br /> MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION <br /> DAMAGE). 13.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS PLOT DATE: <br /> 12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC 2023 .09.2 <br /> GREEN IF 4 AWG OR LARGER). POSITIVE-RED(OR MARKED RED),DC NEGATIVE-GREY(OR MARKED GREY) September 20, 2023 <br /> 13.ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE 15.POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: <br /> GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK) <br /> 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.661, DC SYSTEM GEC SIZED 16.AC CONDUCTORS>4AWG COLOR CODED OR MARKED: PHASE A OR L1-BLACK,PHASE B OR L2-RED, PROJECT NUMBER: <br /> ACCORDING TO[NEC 250.166],MINIMUM 8 AWG WHEN INSULATED,6 AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAY <br /> 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND 'USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE I� 09:40:55 <br /> 8640 80 <br /> CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] "USE-2 S AVAILABLE AS UV WHITE <br /> REGARDLESS OF VOLTAGE. 17.RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES. I <br /> 18. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, SHEET NAME: <br /> FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.31], [NEC 250.118(10)]. DISCONNECTING <br /> MEANS SHALL COMPLY WITH[NEC 690.13]AND[NEC 690.151. E L EC CALCS <br /> 19.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE COMPLYING WITH[NEC 0�'O O' <br /> 230.6(4)]AND SECURED NO GREATER THAN 6'APART PER[NEC 330.30(B)]. -06'00' <br /> REVISION: PAGE NUMBER: <br /> 0 PV6 <br />