Laserfiche WebLink
JOB: HAACK BROTHERS CONSTRUCTION <br /> ADDRESS: 5611 COLBY AVE, EVERETT <br /> DESIGNER: KENNETH H.ROBINSON-ELMSLIE <br /> CALCULATIONS FOR 26 GPM FLOW(2 HEADS) IND. LOSS NET TOTAL <br /> A.WATER PRESSURE IN STREET 80.00 <br /> B:SELECT PIPE SIZE: 1" <br /> C: DEDUCT METER&SETTER LOSS(1") 12.00 68.00 <br /> DEDUCT BACKFLOW DEVICE LOSS(NONE) 0.00 68.00 <br /> D: DEDUCT HEAD LOSS FOR ELEVATION <br /> HEIGHT 10 X.434 LBS/FT 4.34 63.66 <br /> E. DEDUCT PRESSURE LOSS FROM MAIN TO SRINKLER <br /> 1" WATER SERVICE <br /> ITEM QUANTITY EQUIV FT. TOTAL FT. <br /> PIPE: 50 1 50 <br /> ELLS: 4 2 8 <br /> R-TEES 2 3 6 <br /> B-TEES 1 2 2 <br /> TOTAL: 66 <br /> TOTAL EQUIVALENT FT.X .18 PSI/FT= 11.88 51.78 <br /> F: DEDUCT PRESSURE LOSSES FOR 1-1/2"PIPING <br /> FROM CONTROL VALVE TO MOST REMOTE SPRINKLER <br /> ITEM QUANTITY EQUIV FT. TOTAL FT. <br /> PIPE: 0 1 0 <br /> ELLS: 0 9 0 <br /> R-TEES 0 1 0 <br /> B-TEES 0 8 0 <br /> TOTAL: 0 <br /> TOTAL EQUIVALENT FT.X.0178 PSI/FT= 0 51.78 <br /> F: DEDUCT PRESSURE LOSSES FOR 1-1/4"PIPING <br /> FROM CONTROL VALVE TO MOST REMOTE SPRINKLER <br /> ITEM QUANTITY EQUIV FT, TOTAL FT. <br /> PIPE: 90 1 90 <br /> ELLS: 7 8 56 <br /> R-TEES 13 1 13 <br /> B-TEES 5 6 30 <br /> TOTAL: 189 <br /> TOTAL EQUIVALENT FT.X.0343 PSI/FT= 6.4827 45.30 <br /> F. DEDUCT PRESSURE LOSSES FOR 1"PIPING <br /> FROM CONTROL VALVE TO MOST REMOTE SPRINKLER <br /> ITEM QUANTITY EQUIV FT, TOTAL FT. <br /> PIPE: 55 1 55 <br /> ELLS: 3 7 21 <br /> R-TEES 3 1 3 <br /> B-TEES 4 5 20 <br /> TOTAL: 99 j■•■■..■.■...... .... .. <br /> TOTAL EQUIVALENT FT.X.1067 PSI/FT= 10.56 34.73 , 1NASNINOTON STATE <br /> CERTIFICATE OF COMPETENCY <br /> F: DEDUCT PRESSURE LOSSES FOR 3/4"PIPING <br /> plat PROTECTION SPRINKLER SYSTEMS <br /> FROM CONTROL VALVE TO MOST REMOTE SPRINKLER Kenneth H. Robinson-Elmsiie <br /> ITEM QUANTITY EQUIV FT. TOTAL FT. 7659-0106-CE Level 3 <br /> PIPE: 4 1 4 v Robinson Plumbing,Inc. <br /> ELLS: 1 7 7 8 ROBINP•272C2 S'/1143 • <br /> R-TEES 0 1 0 s /� <br /> L\ "Expires <br /> B-TEES 0 3 0 � pSwolw■ oec :3 � <br /> TOTAL: 11 amen...■• ...� <br /> TOTAL EQUIVALENT FT.X.0296 PSI/FT= 0.33 34.41 <br /> REMAINING PRESSURE FOR SPRINKLER OPERATION 34.41 <br /> CALCULATIONS PER NFPA 13D A.10.4.4(A)(2016 ED.) <br />