Laserfiche WebLink
victaulic.com <br /> 2.0 CERTIFICATION/LISTINGS <br /> Ce. <br /> LISTED <br /> Listing Agency/ <br /> Approved Temperature Max.Coverage Area Minimum <br /> Nominal K Factor Ratings Width x Length Flow Pressure Adjustment Spacing <br /> Sprinkler <br /> 155°F/68°C Deflector to Ceiling/ <br /> Cover Ft.x Ft. GPM PSI in Mounting Surface Ft. <br /> SIN Imperial S.I? 135°F/57°C m x m L/min kPa mm Distance m <br /> 12x12 13 7.0 <br /> 3.7x3.7 49.2 1 48 <br /> 14x14 13 7.0 <br /> 4.3 x 4.3 49.2 48 <br /> V4906 4.9 7.1 cULus 16 x 16 13 7.0 7/S Smooth Ceilings 9 <br /> 4.9 x 4.9 49.2 48 22 (See appropriate 2,7 <br /> 18 x 18 17 12.0 installation detail <br /> 5.5 x 5.5 64.3 83 below) <br /> 20 x 20 20 16.7 OR <br /> 6.1 x 6.1 75.7 115 Beamed Ceilings: <br /> 12 x 12 16 8.2 Installed within the <br /> 3Beam In accordance <br /> .7 x 3.7 60.6 57 <br /> with NFPA 13,13D, <br /> 14x14 16 8.2 or 13R <br /> 4.3 x 4.3 60.6 57 (Max Beam Depth <br /> V3806 5.6 8.1 cULus 16 x 16 16 8.2 1/4 Depends on Edition 8 <br /> 4.9 x 4.9 60.6 57 6 of Standard) 2.4 <br /> 18 x 18 21 14.1 <br /> 5.5 x 5.5 79.5 97 <br /> 20 x 20 25 20.0 <br /> 6.1 x 6.1 1 94.6 138 <br /> 2 For K-Factor when pressure is measured in bar,multiply S.I.units by 10.0. <br /> NOTE <br /> • Listings and approval as of printing. <br /> 3.0 SPECIFICATIONS - MATERIAL <br /> Deflector: Bronze <br /> Bulb Nominal Diameter: 3.0 mm <br /> Load Screw: Brass <br /> Pip Cap: Brass <br /> Spring Seal: PTFE coated Beryllium nickel alloy <br /> Frame: Brass <br /> Lodgement Spring: Stainless Steel <br /> Pin: Stainless Steel <br /> Concealed Cup: Steel <br /> Cover Plate: Steel <br /> Installation Wrench: Ductile Iron <br /> Cover Plate Finishes: <br /> • Chrome plated <br /> • White painted <br /> • Flat black painted <br /> • Custom painted <br /> NOTES <br /> • For cabinets and other accessories refer to separate sheet. <br /> 43.03 16384 Rev B Updated 07/2021 ©2021 Victaulic Company.All rights reserved. <br /> victaulic.com 2 ✓ctsulic° <br />