Laserfiche WebLink
FireLockT" Series FL-QR/DRY/SW <br /> Standard Coverage Quick Response Dry Horizontal Sidewall <br /> and Recessed Horizontal Sidewall Sprinklers ✓ctauliic" <br /> K5.6 (8.1 SI), K8.0 (11.5 SI) 45.02 <br /> nEE7 <br /> 1.0 PRODUCT DESCRIPTION <br /> HORIZONTAL SIDEWALL QUICK RESPONSE DRY SPRINKLERS <br /> SIN V3610 V3612 <br /> Orientation HORIZONTAL HORIZONTAL <br /> K-FACTOR' 5.6 Imp./8.1 S.I. 8.0 Imp./1 1.5 S.I. <br /> CONNECTION 1"NPT/25mm BSPT/1"IGS 1"NPT/25mm BSPT/1"IGS <br /> MAX.WORKING PRESSURE 175 psi(1200 kPa) 175 psi(1200 kPa) <br /> ESCUTCHEONS Plain/Flush/Recessed Plain/Flush/Recessed <br /> Sleeve and Skirt/Extended Sleeve and Skirt/Extended <br /> GLOBE EQUIVALENT GL5641 GL8141 <br /> RECESSED HORIZONTAL SIDEWALL QUICK RESPONSE DRY SPRINKLERS <br /> SIN V3610 V3612 <br /> ORIENTATION HORIZONTAL HORIZONTAL <br /> K-FACTOR' 5.6 Imp./8.1 S.I. 8.0 Imp./1 1.5 S.I. <br /> CONNECTION 1"NPT/25mm BSPT/1"IGS 1"NPT/25mm BSPT/1"IGS <br /> MAX.WORKING PRESSURE 175 psi(1200 kPa) 175 si 11200 kPa) <br /> ESCUTCHEONS Recessed Recessed <br /> GLOBE EQUIVALENT GL5641 GL8141 <br /> AVAILABLE WRENCHES <br /> SPRINKLER V36 Recessed V36 Open End 3/16 Hex-Bit(V9) <br /> Sidewall 1 ■ ■ ■ <br /> Factory Hydrostatic Test: 100% @ 500 psi/3447 kPa/34 bar <br /> Min. Operating Pressure: UL/FM: 7 psi/48 kPa/.5 bar <br /> Temperature Rating: See tables in section 2.0 <br /> For K-Factor when pressure is measured in bar,multiply S.I.units by 10.0. <br /> ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT. <br /> victaulic.com <br /> 45.02 15954 Rev C Updated 11/2021 ©2021 Victaulic Company.All rights reserved. <br /> 1 �ctauIic° <br />