Laserfiche WebLink
Flow Summary - NFPA 2007 <br />A-PEX Design Services Inc. Page 4 <br />GRAYSON TH BLDG J UNIT 60 - One Head Calculation (H.1) Date 4l5/2023 <br />SUPPLYANALYSIS <br />Node at <br />Static <br />Residual <br />Available <br />Source <br />Pressure <br />Pressure <br />Flow Pressure Total Demand Required Pressure <br />STR <br />Norte Tag <br />41.0 <br />Elevation <br />20 <br />Node Type <br />500.0 40.96 <br />NODEANALYSIS <br />Pressure Discharge <br />at Norte at Norte <br />17.0 32.634 <br />Notes <br />H.1 <br />116.0 <br />49 <br />12.03 170 <br />0.05 324 <br />T.18 <br />116.0 <br />13.53 <br />T.20 <br />108.0 <br />17.44 <br />T.21 <br />116.0 <br />14.01 <br />T.23 <br />108.0 <br />17.9 <br />SA <br />104.0 <br />20.76 <br />SCV <br />100.0 <br />27.72 <br />MTR <br />100.0 <br />30.22 <br />STR <br />100.0 <br />32.63 <br />H.7 <br />116.0 <br />12.56 <br />H.10 <br />116.0 <br />12.86 <br />11.13 <br />116.0 <br />13.2 <br />T.29 <br />124.0 <br />9.9 <br />T.30 <br />116.0 <br />13.95 <br />H.14 <br />116.0 <br />13.97 <br />T.25 <br />116.0 <br />13.98 <br />H.17 <br />108.0 <br />17.6 <br />T.28 <br />108.0 <br />17.66 <br />HAS <br />116.0 <br />13.37 <br />T.27 <br />116.0 <br />13.39 <br />H.12 <br />116.0 <br />13.41 <br />HS <br />116.0 <br />13.44 <br />HA <br />116.0 <br />13.47 <br />T.19 <br />116.0 <br />13.48 <br />T.31 <br />116.0 <br />13.96 <br />H.16 <br />116.0 <br />13.96 <br />T.26 <br />116.0 <br />14.01 <br />H.6 <br />108.0 <br />17.44 <br />H.3 <br />108.0 <br />17.44 <br />H.2 <br />108.0 <br />17.45 <br />H.5 <br />108.0 <br />17.45 <br />T.22 <br />116.0 <br />13.98 <br />H.9 <br />116.0 <br />13.98 <br />T.24 <br />116.0 <br />13.98 <br />H.11 <br />116.0 <br />14.01 <br />Computer Programs 5y Hydatec Inc. Route 111 Windham N.H. USA 03087 <br />