Laserfiche WebLink
Flow Summary - NFPA 2007 <br />A-PEX Design Services Inc. <br />Page 4 <br />GRAYSON TH BLDG K UNIT 64 - One Head Calculation (H.1) <br />Date 3/15/2023 <br />SUPPLYANALYSIS <br />Node at Static Residual <br />Available <br />Source Pressure Pressure <br />now <br />Pressure <br />Totdl Demand Required Pressure <br />STR 41.0 20 <br />500.0 <br />40.96 <br />17.0 32.634 <br />NODEANALYSIS <br />Pressure <br />Discharge <br />Node Tag Elevation Node Type <br />at Node <br />at Norte <br />Notes <br />H.1 116.0 49 <br />12.03 <br />170 <br />0.05 324 <br />TAB 116.0 <br />13.53 <br />T.20 108.0 <br />17.44 <br />T.21 116.0 <br />14.01 <br />T.23 108.0 <br />17.9 <br />SA 104.0 <br />20.76 <br />SCV 100.0 <br />27.72 <br />MTR 100.0 <br />30.22 <br />STR 100.0 <br />32.63 <br />H.7 116.0 <br />12.56 <br />H.10 116.0 <br />12.86 <br />11.13 116.0 <br />13.2 <br />T.29 124.0 <br />9.9 <br />T.30 116.0 <br />13.95 <br />H.14 116.0 <br />13.97 <br />T.25 116.0 <br />13.98 <br />H.17 108.0 <br />17.6 <br />T.28 108.0 <br />17.66 <br />HAS 116.0 <br />13.37 <br />T.27 116.0 <br />13.39 <br />H.12 116.0 <br />13.41 <br />HA 116.0 <br />13.44 <br />HA 116.0 <br />13.47 <br />T.19 116.0 <br />13.48 <br />T.31 116.0 <br />13.% <br />H.16 116.0 <br />13.% <br />T.26 116.0 <br />14.01 <br />H.5 108.0 <br />17.44 <br />H.2 108.0 <br />17.44 <br />H.3 108.0 <br />17.45 <br />H.6 load <br />17.45 <br />T.22 116.0 <br />13.98 <br />H.9 116.0 <br />13.98 <br />T.24 116.0 <br />13.% <br />H.11 116.0 <br />14.01 <br />Computer Programs 5y Hydatec Inc. Route 111 Windham N.H. USA 03087 <br />