• EXOTHERMIC CONNECTION • INESTECT R GLRIONOUNOSLE o0EVE MID _
<br /> SP
<br /> VECTOR . GROUNNIGAL CONNECTION d ...• s h
<br /> /6 AWG STRANDED&INSUUTED
<br /> ' caourvD Bus BAR
<br /> e n a l n e ! n a A2 aMG SOL10 COPPER TINNED
<br /> Sr,rot rrr O GROUND ROD Vaie
<br /> DRAPER,Llrnrr 84030 www.vrcrow65.com A BUSS BAR INSULATOR wireless_
<br /> Firm License Number:2202
<br /> VSE Project Number:U3614-107-221 GROUNDING LEGEND 5701 SOUTH FE DRIVE
<br /> LITTT .CON BFT 2O
<br /> 1. GROUNDING IS SHOWN DIAGRAMMATICALLY ONLY.
<br /> 2. CONTRACTORUANCESHALL NECSECTION
<br /> ALL S0 N DI AS iA COMPLETE SYSTEM.GROUNDING DINGL BE IN /�
<br /> CON WOO C SENT A 2EEQUIPMENT
<br /> AND DISH Wireless L E.GROUNDINGYS . AND BONDING 1
<br /> REQUIREMENTS AND MANUFACTURER'S SPECIRCATONS.
<br /> } 3. ALL GROUND CONDUCTORS SHALL BE COPPER;NO ALUMINUM CONDUCTORS SHALL BE USED.
<br /> LI
<br /> I I. NO EXOTHERMIC WELDING ON ROOFTOP CAMP-F
<br /> I
<br /> ASSOCIATE,9
<br /> GROUNDING ROOFTOP KEY NOTES
<br /> 195 5 CREEK P ITE 220
<br /> PROPOSED DISH Wireless LLC. E
<br /> GROUNDING MOUNTED DOWN THE GRADE.OR GROUND RING;.2 AWG SOLID COPPER,BURIED AT A DEPTH OF AT LEAST 30 INCHES 6ELOw )b
<br /> EXISTING BUILDING TO PROPOSED \ O OR 6 INCHES BELOW THE FROST LINE AND APPROXIMATELY 2a INCHES FROM ME EXTERIOR WALL '"W�w
<br /> GROUND ROD WITH INSPECTION 1 OR FOOTING, t
<br /> SLEEVE(SCENARIO 2) \ �, i'O`.
<br /> OR ROOFTOP GROUND SYSTEM;THE GROUND SYSTEM USING MINIMUM/2 AWG SOLID COPPER CONDUCTORS. N,Nv •Tt A VA/ i,
<br /> \ O INTERIOR GROUND RING i2 AEG STRANDED GREEN INSULATED COPPER CONDUCTOR EXTENDED AROUND THE RAp \t �. /lr �'t'
<br /> PROPOSED DISH Wireless LLC PERIMETER OF THE EQUIPMENT AREA.ALL NON-TELECOMMUNICATIONS RELATED METALLIC OBJECTS FOUND A\ '�
<br /> GROUNDING i0 E%ISTNC�\ " 2
<br /> BOLDING STEEL BEAM \ I WITHIN A SRE SHALL BE GROUNDED TO THE INTERIOR GROUND RING W./6 AWG STRANDED GREEN $( L
<br /> (SCENARIO 1) INSUUTED CONDUCTOR. lc- 51
<br /> ,.5�-:,
<br /> OBOND TO INTERIOR GROUND RING#2 AWG SOLID TINNED COPPER WIRE PRIMARY BONDS SMALL BE '4+:: '�,%
<br /> \ PROVIDED AT LEAST AT FOUR POINTS ON THE INTERIOR GROUND RING,LOCATED AT THE CORNERS OF THEIM Nti3r)�y7
<br /> \ BUILDING OR ROOM. .PJ k.,. O
<br /> PAV ArA O GROUND ROD'UL LISTED COPPER CLAD STEEL MINIMUM 1/2'DIAMETER BY EIGHT FEET LONG.GROUND f,S S/E/``L��GC/2
<br /> _ RODS SHALL BE INSTALLED W.INSPECTION SLEEVES.GROUND RODS SHALL BE DRIVEN TO THE DEPTH OF
<br /> L C�-T.-J GROUND RING CONDUCTOR.
<br /> 9/26/2023
<br /> Q __ __ "' O EQUI EQUIPMENT FNTF F.A.S.ALMD ND(CRCB}PONY OF GROUND REFERENCE FOR ALL COMMUNICATIONS
<br /> EpUIPMEM S ALL BONDS ME MADE WITH�2 AWG UNLESS NOTED OTHERWISE STRANDED GREEN (EXPIRES: 06/05/2025I
<br /> i INSULATED COPPER CONDUCTORS.BONG TO COMMON BUILDING GROUND SYSTEM W.(2)I2 SOLID TINNED ON�s TM'M.D.R F�FOR DOCUMENT.r PERSON.
<br /> COPPER CONDUCTORS.
<br /> TO
<br /> THIS
<br /> r,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,i,� T r- -1 OG BATCH PLATE GROUND BNB:BOND TO THE COMMON BUILDING GROUND SYSTEM WITH TWO/2 AWG STRANDED
<br /> I I I I L gill-J GREEN INSULATED COPPER CONDUCTORS.WHEN A HATCH-PLATE AND A CELL REFERENCE GROUND BAR ARE
<br /> BOTH PRESENT,THE CROW MUST BE CONNECTED TO THE HATCH-PLATE AND TO THE INTERIOR GROUND RING DRAWN BY: CHECKED BY:APPROVED BY:
<br /> S I . I S USING (2)TWO/2 AWG STRANDED GREEN INSULATED COPPER CONDUCTORS EACH. - -
<br /> �{ SAC JAC JAC--
<br /> -
<br /> NI O EXTERIOR fARI F FMRY PORT f.RDUNO BARS:LOCATED AT THE ENTRANCE i0 THE CELL SITE ROOM.BOND REDS REV I:
<br /> ,III TO GROUND RING WITH A/2 AWG SOLID TINNED COPPER CONDUCTORS WRH MECHANICAL CONNECTIONS.
<br /> I I COTE GR_OTfN�BOND TO BOTH CELL REFERENCE GROUND BAR OR EXTERIOR GROUND RING.
<br /> (III '1 1 CONSTRUCTION
<br /> p^—CAM'EA FRAME BONDING:THE BONDING POINT FOR TELECOM EQUIPMENT FRAMES SHALL BE THE GROUND BUS THAT DOCUMENTS
<br /> (III O IS NOT ISOLATED FROM THE EQUIPMENTS METAL FRAMEWORK.
<br /> C
<br /> O INTERIOR UNIT BONDS'METAL FRAMES,CABINETS AND INDIVIDUAL METALLIC UNITS LOCATED WITH THE AREA SUBMITTALS
<br /> I I W pl OF THE INTERIOR GROUND RING REQUIRE A�6 AWG STRANDED GREEN INSULATED COPPER BOND TO THE REV DATE DESCRIPTION
<br /> ICJ INTERIOR GROUND RING.—
<br /> ^ 9/1¢/A22 SA INCORPORATED
<br /> O FENCE AND GATE GROUNDING-METAL FENCES SHALL BE BONED TO THE COMMON BUILDING GROUND 10/Ie/2022 EGA
<br /> SICM WITHA s FOR E.
<br /> A#2 AWG SOLID TINNED COPPER CONDUCTOR AT AN INTERVAL NOT EXCEEDING 25 FEET. Io/2e/2e22 ISSUED
<br /> BONDS SHALL BE MADE AT EACH GATE POST AND ACROSS GATE OPENINGS. A 11/0T/2022 ISSUED FOR KART
<br /> OM METALLIC OBJECTS.EXTERNAL TO OR MOUNTED TO THE BUILDING,SHALL BE BONDED 0 2/I4/2023 coomstas MOM THE an
<br /> TO THE COMMON BUILDING GROUND SYSTEM.USING#2 TINNED SOLID COPPER WIRE A 51/15/2o2S NGram 240INA[IW wuTwN
<br /> A 9/22/2023 ISSUED FOR FIXAL
<br /> O BSF RO'.F SiI_ P EACH ICE BRIDGE LEG SHALL BE BONED TO THE GROUND RING WITH#2 AWG BARE AWE PROJECT NUMBER
<br /> I I TINNED COPPER CONDUCTOR.PROVIDE EXOTHERMIC WELDS AT BOTH THE ICE BRIDGE LEG AND BURIED
<br /> GROUND RING. SESEA00377C
<br /> 1 SYSTEM CH
<br /> GE OUTS,RECTIFIER E
<br /> O ORRADDITIONS CBREKER DISTRBUTIONGCHANGES.IBATTERY ADDITIONS,BATTERY REPLACEMENTS AND
<br /> DISH Wireless L.L.C.
<br /> I INSTALLATIONS OR CHANCES TO DC CONVERTER SYSTEMS IT SHALL BE REQUIRED THAT SERVICE PROJECT INFORMATION
<br /> CONTRACTORS VERIFY ALL DC POWER ST,61AS ARE EQUIPPED WITH A MASTER DC`YT,ILM RETURN GROUND
<br /> I I
<br /> F{ CONDUCTOR FROM THE DC POWER SYSTEM COMMON RETURN BUS DIRECTLY CONNECTED TO THE CELL SOE SESEA00377C
<br /> G-- REFERENCE GROUND BAR
<br /> 2930 WETMORE AVENUE
<br /> J J O ROOFTOP COLLECTOR BUSS BAR IS TO BE MECHANICALLY BONDED TO COMMON BUILDING GROUND SYSTEM. EVER ET, 9 VENUE
<br /> O 1
<br /> �^ 201
<br /> I I r , I� REFER TO DISH Wireleca L.LC.GROUNDING NOTES.
<br /> SHEET TITLE
<br /> GROUNDING PLANS
<br /> T AND NOTES
<br /> SHEET NUMBER
<br /> G-1
<br /> GROUNDING PLAN a 1 GROUNDING KEY NOTES 2
<br /> No SCALE
<br /> DISH Wireless L.L.C.TEMPLATE VERSION 45-10/29/2021