Laserfiche WebLink
N <br />L <br />ML -1 <br />120V, 10 <br />S.W. ELECTRICAL VAULT #1 <br />(TYPICAL OF EF -6 & EF -8) <br />EF -4 <br />1/2 HP, 120V, 10 <br />SCHEMATIC, EXHAUST FAN CONTROL <br />SCALE: NONE E64 1E500 <br />�-- MAG MOTOR DISC. SW. <br />STARTER 30A, 3D <br />I4A,3A 3M 10L 1T1 <br />2a,4b,6c L10 -I i� r -—b SEF -1 <br />L2.-{ 1 3 �, 5HP 460V, 30 <br />t— SMOKE EXH FAN <br />L----- <br />3M 3T1 <br />4A,3A}-o-�j- <br />7a,9b,11c3T2 IHP 46OV, 30 <br />�O- -o-DOOR OPENER <br />3To--o ABOVE DOOR 100C <br />VERIFY FINAL CONNECTIONS PER EQUIPMENT <br />MANUFACTURER REQUIREMENTS <br />TO FAN CONTROL STATUS PANEL <br />I�1 11 <br />0 <br />ONE HOLE STEEL PIPE <br />STRAP ANCHORED TO <br />METAL ROOF DECK <br />(TYPICAL) BUILT-UP ROOFING <br />OVER METAL DECKING <br />3" METAL DECKING <br />w <br />CROUSE HINDS ALC 7575-40 <br />FLEXIBLE FIXTURE HANGER, W/ <br />0 3/4" RGC STEM & THREADED <br />d ENDS, TYPICAL FOR HANGING <br />Xo LIGHT FIXTURE <br />CL <br />SAFETY CABLE #10 GA <br />TSTAINLESS STEEL WITH <br />6" SLACK FOR MOVEMENT <br />(TYPICAL) <br />SECTION A -A OTTOM OF FIXTURES AT <br />T_____!40'-O"AFF (TYPICAL) <br />TYPE "A" &"A1 " FIXTURES <br />SCALE: NONE HBE10 1E500 <br />SEE DETAIL\ 1E10 E15 BUILT-UP ROOFING <br />1 OVER METAL DECKING <br />3/4" RGS NIPPLE <br />(12" TO 15") <br />3/4" EMT TO RIGID <br />FITTING <br />3" DEEP METAL <br />ROOF CHANNEL <br />SPACE <br />EMT CONDUIT <br />SAFETY CABLE #10 GA <br />STAINLESS STEEL <br />SECURED TO METAL <br />ROOF DECK AND LT. <br />FIXTURE. LEAVE 6" <br />SLACK FOR MOVEMENT <br />(TYPICAL)--� <br />NUT & BOLT TYPE/ I <br />CABLE CLAMPS AT ALL 12" <br />CABLE ENDS (TYPICAL) EPARATIO <br />�m <br />STEEL BEAM 25'-0" <br />� O.C. (TYPICAL) <br />N <br />�— 3/4" GRC <br />1 HOLE CLAMP ---METAL ROOF <br />RIGID STEEL DECK CHANNEL <br />#12 SCREWS STAINLESS <br />STEEL ANCHORED TO <br />METAL ROOF DECKING <br />CONDUIT SUPPORT DETAIL <br />SCALE: NONE 1E101 E600 <br />BOX, ANCHORED TO METAL <br />DECK WITH STAINLESS <br />STEEL #12 SCREWS <br />2 SEF -1 <br />MOTOR STARTER <br />L - <br />DOOR OPENER <br />MOTOR STARTER & <br />2 CONTROL STATION <br />FOR DOOR 100C <br />1/DOOR 100C <br />SHOWN, OTHERS SIMILAR <br />SCHEMATIC, FIRE PROTECTION INTERFACE <br />SCALE: NONE 1E1101E500 <br />w <br />0 <br />g <br />w <br />m <br />BOTTOM OF FIXTURE <br />FLUSH WITH BOTTOM <br />OV BEAMS (TYPICAL) <br />to• <br />DECK <br />-CROUSE-HINDS ARB12 <br />*FLEXIBLE FIXTURE HANGER <br />1/2" RSC. STEM WITH <br />THREADED ENDS <br />SAFETY CABLE #10 GA <br />STAINLESS STEEL. LEAVE 6" <br />SLACK FOR MOVEMENT <br />(TYPICAL) SECURE TO LT. <br />FIXTURE AND METAL ROOF <br />DECK <br />TYPE "M" FIXTURE MOUNTING DETAIL* (Z) <br />SCALE: NONE M1E15,M�1E18�1E600 <br />* LIGHTS RUNNING PERPENDICULAR TO BEAMS TO BE MOUNTED AT THE <br />BOTTOM OF THE BEAMS <br />REVISION <br />BY I APPROVED <br />DATE I SYM REVISION <br />BY I APPROVED DATE <br />A <br />DRAWING DEVELOPMENT J#567957 HGI 05.16.08 <br />ELIMINATE WATER LEAKS J#58633000 H. WEST KER/WRL 08.07.08 <br />EVERETT FIRE PANEL REPLACEMENT W2640474 SAZAN/Z0 05.29.19 <br />SHOP DRAWINGSAGOW/HG 10.04.19 <br />ONE HOLE STEEL PIPE <br />STRAP ANCHORED TO <br />METAL ROOF DECK <br />CROUSE HINDS ALC 7575-40 <br />FLEXIBLE FIXTURE HANGER, (TYPICAL) <br />3/4" RGC WITH <br />THREADED ENDS <br />(TYPICAL) <br />SWIVEL TYPE PIPE <br />CLAMPS WITH <br />1/2" DIA STEEL <br />ROD BRACING <br />BETWEEN CLAMPS <br />BOTTOM OF <br />FIXTURES AT <br />+40'-0"AFF <br />(TYPICAL) <br />TYPE "B" FIXTURE MOUNTING DETAIL M <br />SCALE: NONE HBE10 1E500 <br />EXPOSED CONDUIT ROUTED <br />UP AND SECURED TO PANEL <br />WITH 2 HOLE STI <br />FACE OF EXIT SI( <br />CENTERED OVER <br />TRANSOM PANEL ABOVE <br />DOOR WITH TWO LAYERS <br />OF 5/8" GYP. BOARD ON <br />INTERIOR SIDE <br />4"'X 2 1/8" STEEL <br />OUTLET BOX SECURED TO <br />PANEL FOR MOUNTING <br />EXIT LIGHT FIXTURE <br />TUBULAR STEEL DOOR <br />FRAME <br />STEEL DOOR <br />EXIT LIGHT MOUNTING DETAIL rg-'� <br />SCALE: NONE 1E10 1E500 <br />FOR REF�l <br />ACCEPTABILITY o AWN DATE SUBTITLE <br />THIS DESIGN ANo/.R MOTOR CONTROL SCHEMATICS <br />SPECIFICATION IS APPROVED <br />TITLE <br />avPRovEo BY DEP. DATE " """" I I EVERETT FIRE PANEL REPLACEMENT <br />ELECTRICAL MASTER <br />I 10 ON •7 1 <br />LEGEND <br />SEE SHEET E1A FOR SYMBOLS AND ABBREVIATIONS <br />GENERAL NOTES <br />FIELD CONTROL SWITCHES FOR (7) DOORS AND (21) <br />SMOKE EXHAUST FANS SHALL BE NORMALLY SWITCHED <br />TO THE AUTOMATIC POSITION. OPERATION OF THIS <br />EQUIPMENT SHALL BE AT THE FAN CONTROL PANEL. <br />HAND AND OFF FIELD SWITCH POSITIONS ARE FOR <br />TESTING AND MAINTENANCE PURPOSES ONLY. <br />REFERENCE DRAWINGS <br />CONSTRUCTION NOTES <br />C 10.04.19 <br />SHEET <br />1 E500 <br />JOB NO. W264D474 COMP NO. <br />EVERETT, WA. DWG "D' 40-054-1E500 <br />