Laserfiche WebLink
PROVIDE SMOKE DETECTORS IN <br />ELEVATOR PIT FOR ELEVATOR RECALL. <br />CONNECT TO FIRE ALARM PANEL — <br />30 <br />0 <br />1ST FLOOR <br />PROVIDE A 135 DEG HEAT DETECTOR LOCATED <br />WITHIN 24" OF EACH SPRINKLER HEAD IDENTIFIED <br />WITH A NAMEPLATE THAT READS: "ELEVATOR LIGHT SWITCH LOCATED ADJACENT TO ACCESS <br />CONTROL ONLY - DO NOT TEST" H S DOOR <br />PROVIDE LIGHT FIXTURES IN ELEVATOR PIT. WALL ELEVATOR PIT 3/4" RGS 2V54-2C6.6/26a <br />BRACKET MOUNTED WITH GUARDS. SPECTRUM OR 26 26 <br />EQUIVALENT. 28 ° GFCI 26 <br />GFCI <br />PROVIDE GFCI DUPLEX RECEPTACLE IN PIT <br />3 4" RGS 2V54-2C6.6/28b WITH CIRCUIT SUPPLYING BOTH PIT LIGHT AND <br />/ / RECEPTACLE FOR SUMP PUMP. RECEPTACLE. <br />PROVIDE A SINGLE RECEPTACLE FOR <br />AN ELEVATOR PIT SUMP PUMP WITH <br />A SEPARATE 20A 120V CIRCUIT. <br />ELEVATION — ELEVATOR HOISTWAY tl 2 <br />SCALE: N.T.S. 1 E65 E506 <br />SYM <br />I REVISION <br />BY APPROVED <br />DATE SYM REVISION BY APPROVED DATE <br />- <br />LEGEND <br />J1567957 HGI <br />05.16.08 <br />A <br />40-054 BUILDING MODIFICATIONS <br />10153855 CASNE CEC <br />SEE SHEET EIA FOR SYMBOLS AND ABBREVIATIONS <br />PROVIDE 135 DEG. HEAT DETECTOR WITHIN <br />RECORD DRAWING <br />10153855 OUR GROUP RJV <br />BUSSMANN POWER <br />MODULE SWITCH <br />B <br />EVERETT FIRE PANEL REPLACEMENT <br />18" OF EACH SPRINKLER HEAD. HEAT <br />05.29.19 <br />C <br />SHOP DRAWINGS <br />AGOW/HG <br />10.04.19 <br />DETECTORS PROVIDE AUXILIARY FUNCTION OF <br />ELEVATOR HYDRAULIC <br />2a,4b,6c <br />R P <br />PHENOLIC <br />30c <br />THE ELEVATOR EQUIPMENT AND SHALL BE <br />POWER UNIT <br />3b <br />ELEVATOR CONTROLLER <br />NAMEPLATE <br />7a,9b <br />IDENTIFIED WITH A NAMEPLATE THAT READS <br />(TYPICAL) <br />"ELEVATOR CONTROL ONLY - DO NOT TEST" <br />AUXILIARY CONTACT TO SIGNAL ELEVATOR <br />XE2V54-1MD6.6/3b <br />ELEVATOR <br />100A, 3P 70A <br />TO ELEVATOR <br />RECALL PROVIDE 1/2"C WITH (3)#1.4 AWG <br />3/4"C, 2#12 & 1#12 GND <br />POWER <br />CONTROLLER <br />CONDUCTORS TO ELEVATOR CONTROLLER <br />PROVIDE CONNECTION FROM BUSSMANN <br />SOURCE <br />(FURNISHED <br />- <br />POWER MODULE TO FIRE ALARM PANEL W/8 <br />BY OTHERS) <br />SMOKE DETECTOR IN ELEVATOR <br />#14 IN 3/4"C. <br />MACHINE ROOM FOR ELEVATOR RECALL. <br />CONNECT TO FIRE ALARM PANEL <br />PROVIDE 1" CONDUIT W/PULL STRING FROM <br />SHUNT TRIP WITH MECH. <br />FIRE ALARM PANEL TO ADT PANEL ON 2ND <br />INTERLOCKED AUX. <br />3/4"C-2#10 & 1#12 GND 2V54-2C6.6/25a <br />FLOOR AT COLUMN LINE A-10. <br />CLEARING CONTACT <br />ELEVATOR CAR HVAC ACU -1 DISCONNECTING <br />PROVIDE CONNECTION FROM ELEVATOR <br />GENERAL NOTES <br />MEANS. PROVIDE 20A 1P LOCKABLE ENCLOSED <br />E L EV CONTROLLER TO FIRE ALARM PANEL W/8 #14 <br />CIRCUIT BREAKER. PROVIDE ENGRAVED LABEL <br />F IN 3/4"C. <br />1. ELEVATOR SHUNT -TRIP CONTROL SYSTEM SHALL BE <br />PROVIDE DEDICATED 20A 120V CIRCUIT AND S <br />H C 6 FIRE ALARM PANEL <br />INSTALLED AND TESTED PER NFPA 72. <br />LOCKABLE 20A 1P ENCLOSED CIRCUIT <br />BREAKER FOR ELEVATOR CAR LIGHT SOURCE <br />+48 <br />PROVIDE ENGRAVED LABEL <br />120V <br />EN <br />LEVATOR CONTROLLER <br />(FURNISHED OTHERS) <br />KB_ --- I <br />"SHUNT TRIP READY" <br />3/4"C 3#12 & 1#12 GND <br />ELEVATOR CAR TELEPHONE J -BOX PROVIDE <br />G <br />XE2V54-iMD6.6/7a,9b <br />3/4"C TO CABLE TRAY ABOVE CEILING <br />PILOT LIGHT <br />3/4"C-2#10 & 1#12 GND <br />2V54-2C6.6/31a <br />3/4"C-2#10 & 1#12 GND 2V54-2C6.6/29c <br />R P <br />HEAT DETECTOR <br />ELEVATOR SHUNT TRIP CONTROL PANEL <br />PROVIDE CONNECTION FROM POWER <br />BUSSMANN MODULE TO FIRE ALARM PANELFIRE <br />Dm <br />CONTACTS IN <br />PARALLEL <br />BUSSMANN POWER MODULE SWITCH (MODEL <br />ALARM <br />PS) WITH CONTROL POWER TRANSFORMER. <br />PROVIDE 3#14 IN 3/4"C. <br />INTERFACE <br />GREEN PILOT LIGHT. KEY OPERATED TEST <br />ELEVATOR POWER SOURCE <br />K RELAY <br />REFERENCE DRAWINGS <br />SWITCH. AUXILIARY CONTACTS AND FIRE ALARM <br />1 1/2"C, 3#2 & 1#8 GND <br />KEY OPERATED <br />INTERFACE RELAY. SWITCH RATING AND FUSE <br />4V54-2MD6.6/2a,4b,6c <br />R p <br />TEST SWITCH <br />40-054-1E15 <br />SIZE AS INDICATED ON CONTROL DIAGRAM <br />40-054-1E65 <br />40-054-1E115 <br />R1 CLEARING SHUNT ELEVATOR <br />FLOOR PLAN — <br />ELEVATOR E UIPMENT ROOM z <br />CONTACT TRIP —CONTROLLER <br />SCALE: N.T.S. <br />1E115 E506 <br />AUXILIARY AUXILIARY <br />CONTACTS <br />jR2A R3ACONTACTS <br />(ELEVATOR (FUTURE <br />RECALL R38 REMOTE <br />LIGHT SWITCH AT HOISTWAY ACCESS POINT (TYP) <br />30� <br />SIGNAL) �� MONITORING) <br />SMOKE DETECTORS IN ELEVATOR MACHINE <br />3/4" RGS 2V54-2C6.6/30c <br />ROOM AND IN ELEVATOR LOBBIES WITHIN 21 <br />FEET OF CENTERLINE OF ELEVATOR DOOR <br />PROVIDE FIVE (5) LIGHT FIXTURES IN HOISTWAY. <br />FOR ELEVATOR RECALL CONNECT TO FIRE <br />ALARM PANEL (TYPICAL). <br />LOCATE ON 1ST AND 2ND FLOOR ON OPPOSITE <br />S <br />ELEVATOR <br />SHUNT—TRIP CONTROL DIAGRAM 3 <br />WALLS AND ON CEILING OF HOISTWAY. PROVIDE <br />SCALE: N.T.S. <br />1E65 E506 <br />SWITCHES TO CONTROL FIXTURES AT EACH HOIST <br />MEZZANINE <br />CONSTRUCTION 'NOTES <br />WAY ACCESS POINT. FIXTURES SHALL BE <br />METALUX VT2 SERIES OR EQUIVALENT. <br />30 130 <br />PROVIDE SMOKE DETECTORS IN <br />ELEVATOR PIT FOR ELEVATOR RECALL. <br />CONNECT TO FIRE ALARM PANEL — <br />30 <br />0 <br />1ST FLOOR <br />PROVIDE A 135 DEG HEAT DETECTOR LOCATED <br />WITHIN 24" OF EACH SPRINKLER HEAD IDENTIFIED <br />WITH A NAMEPLATE THAT READS: "ELEVATOR LIGHT SWITCH LOCATED ADJACENT TO ACCESS <br />CONTROL ONLY - DO NOT TEST" H S DOOR <br />PROVIDE LIGHT FIXTURES IN ELEVATOR PIT. WALL ELEVATOR PIT 3/4" RGS 2V54-2C6.6/26a <br />BRACKET MOUNTED WITH GUARDS. SPECTRUM OR 26 26 <br />EQUIVALENT. 28 ° GFCI 26 <br />GFCI <br />PROVIDE GFCI DUPLEX RECEPTACLE IN PIT <br />3 4" RGS 2V54-2C6.6/28b WITH CIRCUIT SUPPLYING BOTH PIT LIGHT AND <br />/ / RECEPTACLE FOR SUMP PUMP. RECEPTACLE. <br />PROVIDE A SINGLE RECEPTACLE FOR <br />AN ELEVATOR PIT SUMP PUMP WITH <br />A SEPARATE 20A 120V CIRCUIT. <br />ELEVATION — ELEVATOR HOISTWAY tl 2 <br />SCALE: N.T.S. 1 E65 E506 <br />SYM <br />I REVISION <br />BY APPROVED <br />DATE SYM REVISION BY APPROVED DATE <br />- <br />RECORD DRAWING <br />J1567957 HGI <br />05.16.08 <br />A <br />40-054 BUILDING MODIFICATIONS <br />10153855 CASNE CEC <br />06.04.10 <br />- <br />RECORD DRAWING <br />10153855 OUR GROUP RJV <br />04.07.11 <br />B <br />EVERETT FIRE PANEL REPLACEMENT <br />W2640474 SAZAN/ZO <br />05.29.19 <br />C <br />SHOP DRAWINGS <br />AGOW/HG <br />10.04.19 <br />o�--AffdffAlIFAfW"° <br />EQUIPMENT <br />PANEL <br />CIRCUIT <br />ELEVATOR PIT RECEPTACLE <br />2V54 -2C6.6 <br />26a <br />ELEVATOR PIT SUMP RECEPTACLE <br />2V54 -2C6.6 <br />28b <br />ELEVATOR PIT LIGHT <br />2V54 -2C6.6 <br />26a <br />ELEVATOR EQUIPMENT ROOM LIGHT <br />2V54 -2C6.6 <br />27b <br />ELEVATOR EQUIPMENT ROOM OUTLET <br />2V54 -2C6.6 <br />29c <br />ACU -1 (ELEV EQUIP ROOM (EER) <br />2V54 -2C6.6 <br />25c <br />ELEVATOR CAR LIGHT <br />2V54 -2C6.6 <br />31a <br />BUSSMAN POWER MODULE SWITCH <br />4V54-2MD6.6 <br />2a,4b,6c <br />ELEVATOR SHAFT LIGHTS <br />2V54 -2C6.6 <br />30c <br />ELEVATOR FIRE PANEL <br />X2V54-1MD6.6 <br />3b <br />ELEVATOR CONTROLLER <br />X2V54-1MD6.6 <br />7a,9b <br />208Y /120V CIRCUIT & PANEL SCHEDULE <br />SCALE: N.T.S. 1E115 & 1E6 <br />,5 E506 <br />FOR REFERENCE ONLY <br />DRAWN <br />ACCEPTABILITY C. CLEVER JLB 07.10.07 "'rrLE <br />THIS DESIGN AND/OR P. TSCHERNEGA oz2s.o7 - ELECTRICAL DETAILS <br />m SPECIFICATION 15 APPROVEDERMREErwLE <br />APPROVED BY DEPT. DATE R. HURST 07.25.07CHECKED <br />EVERETT FIRE PANEL REPLACEMENT <br />D. LEAVTT 07.25.07 BUILDING 40-054 <br />APPR <br />S. HODGE 07.25.07 <br />R. cwINN 07.25.07 ELECTRICAL MASTER <br />„­ „CVIS M„VL G IAIL 10.04.19 <br />SHEIE <br />E506 <br />JOB NO. 567957 COMP N0. <br />EVERETT, WA, MG NO. 40-054-E506 <br />