PLAN SYMBOLS DIAGRAM SYMBOLS GENERAL NOTES <br /> GROUNDING POWER (CONT) LIGHTING SINGLE LINE SCH MATIC SCHEMATIC 1. CONDUIT: 1/2" MINIMUM - TYPE AND SIZE IN ACCORDANCE <br /> WITH PLAN DRAWINGS AND THE SPECIFICATIONS. <br /> ® TELEPHONE/POWER POLE REFER TO SHEETS E501 & E502 FOR DETAILED FIXTURE <br /> G DISCONNECT SWITCH FLOW SWITCH - N.C. 2. CONDUCTORS SHOWN: #12 AWG, STRANDED COPPER,INSULATION <br /> SCHEDULE WITH SYMBOLS <br /> - r- GROUND CABLE CONNECTION TC TIME CLOCK � OPENS ON INCREASE IN FLOW TYPE THHN/THWN, UNLESS OTHERWISE NOTED. <br /> O GROUND ROD CONNECTION © CONTACTOR HIGH INTENSITY DISCHARGE (HID) POTENTIAL TRANSFORMER - FUSE 3. COLOR CODE CONDUCTORS: IDENTIFY CONDUCTORS WHICH DO <br /> ® SAINO WALL SWITCH #32116 FIXTURE 2 480.120 QUANTITY & RATIO o- FLOW SWITCH - N.O. NOT HAVE APPROPRIATELY COLORED INSULATION WITH COLOR <br /> -�� GROUND CABLE PIGTAIL AS SHOWN = CIRCUIT BREAKER CLOSES ON INCREASE IN FLOW TAPE WHEREVER CONDUCTORS ARE ACCESSIBLE. IDENTIFY <br /> FLOODLIGHT - WALL MTD. <br /> / POLE MTD. INSULATED GROUND CONDUCTORS PER NEC 250-57(b) <br /> -G- GROUND CABLE (UNDERGROUND) POWER RECEPTACLES LIGHTING FIXTURE - 2' x 4' LAYIN 800:5 CURRENT TRANSFORMER Lj EXCEPTION #1,b OR c (USING TAPE). COLOR CODE AS <br /> -G- INSULATED GROUND BUS BAR SEE SHEET E1B & E1C FOR DETAILED RECEPTACLE ® FLUORESCENT WITH 3 TUBES QUANTITY & RATIO TRANSFORMER TEMPERATURE SWITCH - N.C. FOLLOWS: <br /> SCHEDULE AS SHOWN �� OPENS ON RISING TEMP 208Y/120V 48 7 <br /> POWER LIGHTING FIXTURE - 2' x 4' LAYIN A 0 �LCEEZERJSBUS <br /> IN PNL) BLACK BROWN <br /> ® FLUORESCENT WITH 4 TUBES A AS AMMETER w/SWITCH -1- GROUND CONNECTIONS TEMPERATURE SWITCH - N.O. B 0 IN PNL) RED ORANGE <br /> PANELBOARD, 208Y/12OV, 3 PHASE POWER OR TELEPHONE OUTLET MOUNTED - CLOSES ON RISING TEMP C 0 RIGHT BUS IN PNL) BLUE YELLOW <br /> O INDICATES SHUNT-TRIP ® IN DOUBLE BOX ATTACHED TO UNDER- LIGHTING FIXTURE - 2' x 2' LAYIN V VS VOLTMETER w SWITCH / NEUTRAL WHITE GRAY <br /> ( ) SIDE OF RAISED FLOOR. TYPICAL OF ® FLUORESCENT WITH 2 TUBES / PI OT LIGHT COLOR -p-Q� LIMIT SWITCH - N.C. ISOLATED GROUND GROUND GREEN GRN/YEL* GRNE/YEL* <br /> ® PANELBOARD, 480Y/277V, 3 PHASE ALL OUTLET TYPES. REF. DETAILS 1 / <br /> © PANELBOARD, 400 HZ, 200Y 115V AND 2, SHEET E538 ® LIGHT FIXTURE - 1' x 4' SURFACE OR HM WATTHOUR METER *GREEN WITH YELLOW TRACER <br /> / PENDANT FLUORESCENT WITH 2 TUBES -L PUSHBUTTON o- LIMIT SWITCH - N.O. <br /> O PANELBOARD, 28 VDC ® OUTLET MOUNTED IN BOX ATTACHED TO -o 0- MOMENTARY CONTACT 4. LABEL EACH RECEPTACLE, JUNCTION/OUTLET BOX AND SWITCH <br /> UNDERSIDE OF RAISED FLOORI LIGHTING FIXTURES WIRED IN MASTER/ BUS DUCT RELAYS & COILS NORMALLY OPEN WITH CIRCUIT IDENTIFICATION AS SCHEDULED ON SHEETS E1 B <br /> ® DC PANEL POWER SUPPLY, SIZE AS NOTED TYPICAL FOR ALL OUTLET TYPES SLAVE BALLAST CONFIGURATION AF _ *_ & E1C, USING TYPED SCHEDULED ON SHEETS ElB & E1C, <br /> REF. DETAIL 1, E534 FOR PANELS LOCATED REF. DETAIL 4, SHEET E534 III III III III 111111111111 (3 2-LAMP BALLASTS FOR 2 3-LAMP �,T800 <br /> 00 AT WITH BREAKER PUSHBUTTON `J TYPE USING TYPED LABEL. <br /> IN RAISED FLOOR AREAS IN <br /> _n- MOMENTARY CONTACT M=MOTOR STARTER® 5. INSTALL NEW OR REVISED PANEL SCHEDULES UPON COMPLETION <br /> LIGHT FIXTURE - FLUORESCENT WITH <br /> OUTLET MOUNTED IN BOX ON SLAB NORMALLY CLOSED CR=CONTROL RELAY OF JOB. <br /> e EQUIPMENT IDENTIFICATION TYPICAL FOR ALL OUTLET TEES OR ® ALL BALLASTS ON EMERGENCY CIRCUIT C=CONTACTOR <br /> "X" DENOTES EQUIPMENT NUMBER REF. DETAIL 3, SHEET E534 480V OR 480Y/277V OFF ON TR=TIME DELAY OR TIMING 6. PANELS ARE TO BE IDENTIFIED BY LAMINATED PHENOLIC <br /> Y" DENOTES HP, KVA OR KW RATING OR BATTERY PACK. R �/ SELECTOR SWITCH <br /> 1D10-1 PANELBOARD RELAY NAMEPLATES AS DETAILED ON SHEET E1B AND AS SHOWN IN <br /> 600 A MAINTAINED CONTACT <br /> (RATINGS AS y THE SPECIFICATIONS. <br /> COMMUNICATIONS LIGHT FIXTURE TAP 1/2" FLEXIBLE -� 0- TWO POSITION SEE SHEET E508-1 FOR <br /> ® CIRCUIT BREAKER ENCLOSURE METAL CONDUIT - 4 #12: TWO PHASE M.L.O. NOTED) N.O. CONTACT q F C * ADDITIONAL FIRE ALARM SYSTEM <br /> T TELEPHONE OUTLET CONDUCTORS, ONE NEUTRAL, ONE GROUND <br /> 3 PH, 3 W 2 AB B R EV A �O N S ABBREVIATIONS <br /> O' CKT. BKR. ENCLOSURE WITH SHUNT-TRIP PROVIDE 1/2" CONDUIT STUBBED (3 #12 FOR SINGLE OR COMMON BALLAST 1 �I3 -o�o- N.C. CONTACT <br /> BELOW FLOOR OR ABOVE CEILING FOR SWITCHING) 208V OR 208Y/120V - _� SELECTOR SWITCH <br /> D DISCONNECT SWITCH (FUSED OR UNFUSED) TWO TWISTED PAIR CAT. 3 CABLE iD10-2 PANELBOARD _ MAINTAINED CONTACT AFF ABOVE FINISHED FLOOR <br /> 30/20 SWITCH RATING/FUSE RATING UNLESS INDICATED OTHERWISE. INDIRECT LIGHTING FIXTURE 225 A (RATINGS AS i-2 THREE POSITION °- N.O. - ON DELAY CONTACT AHC ABOVE HUNG CEILING <br /> ®' MOTOR STARTER (COMBINATION) Z DUPLEX TELEPHONE OUTLET M. BKR. AL ALUMINUM <br /> NOTED) a ATS AUTOMATIC TRANSFER SWITCH B <br /> PROVIDE 1/2" CONDUIT STUBBED 3PH, 4 W N.C. - ON DELAY CONTACT <br /> ® MANUAL MOTOR STARTER BELOW FLOOR OR ABOVE CEILING EXIT SIGN, WALL MOUNTED AWG AMERICAN WIRE GAUGE <br /> SOLENOID VALVE CB CIRCUIT BREAKER <br /> TW WALL MOUNTED TELEPHONE OUTLET ®+ EXIT SIGN, CEILING MOUNTED �� 400 HZ ACo- N.O. - OFF DELAY CONTACT C.O. CO CONDUIT ONLY <br /> MT TRANSFORMER (SIZE AS SHOWN, IN KVA) PROVIDE 1/2" CONDUIT STUBBED 3012-2 PANELBOARD CRU COMPUTER ROOM UNIT <br /> O JUNCTION BOX BELOW FLOOR OR ABOVE CEILING FIXTURE IDENTIFICATION 150 A (RATINGS AS PRESSURE SWITCH - N.C. DED DEDICATED <br /> MOUNT AT 607AFF X" DENOTES FIXTURE TYPE OPENS ON RISING PRESSURE <br /> Y M.BKR. NOTED) � N.C. - OFF DELAY CONTACT DP DISTRIBUTION PANEL BOARD <br /> ® EQUIPMENT CONNECTION IF FLOOR MOUNTED TELEPHONE OUTLET "Y" DENOTES TOTAL FIXTURE WATTAGE 400 HZ EF EXHAUST FAN <br /> PRESSURE SWITCH - N.O. EMCS ENERGY MANAGEMENT CONTROL SYSTEM <br /> (LOCATION DIAGRAMMATIC) <br /> © FLUSH MOUNTED SIGNAL BELL CLOSES ON RISING PRESSURE EMT ELECTRICAL METALLIC TUBING <br /> ® ON-OFF SELECTOR SWITCH ALLEN-BRADLEY TOGGLE SWITCHES - LINE VOLTAGE, + - 28 VDC EPO EMERGENCY POWER OFF <br /> 8OOT-1ZT FLUSH BACK BOX W/ 8007-R2TC I<I<K DATA OUTLET, REF. DETAIL 5 SINGLE POLE/ 3-WAY/ 4-WAY. NUMBER 2C4-1 PANELBOARD ES EPO SWITCH <br /> E550, NUMBER INDICATES NUMBER OF OF SWITCHES UNDER COMMON PLATE FLOAT OR LEVEL SWITCH - N.C. <br /> SELECTOR SWITCH W/ "ON-OFF" NAMEPLATE CAT. 5 PAIR. F INDICATES 4-FIBER. AS INDICATED 28 VDC (RATINGS AS OPENS ON RISING LEVEL B EW <br /> C ELECTRIC WATER COOLER <br /> 200 A NOTED) FACP FIRE ALARM CONTROL PANEL <br /> MOMENTARY PUSH BUTTON STATION ALLEN- OO VOLUME CONTROL 2$L" 3$u• LOW-VOLTAGE LIGHTING CONTROL M.BKR. <br /> %< BRADLEY 800T-1ZT FLUSH BACK BOX W/ SWITCHES. NUMBER OF SWITCHES UNDER o- FLOAT OR LEVEL SWITCH - N.O. FA FRE R TE INA CA IN <br /> 8007-1KTG SERIES EMERGENCY PUSH- ® SPEAKER, CEILING MOUNTED COMMON PLATE AS INDICATED FILTER RF FILTER (SIZE AS NOTED) CLOSES ON RISING LEVEL <br /> BUTTON W/ BOOT-N143 GAURD AND REF. DETAIL A SHEET E570 a,b,c LOWER CASE LETTER INDICATES SWITCHING FDP FIRE DETECTION PANEL <br /> "EMERGENCY EXHAUST" RED NAMEPLATE. LOWBAY SPEAKER, DUTY COMBINATION STARTER FGROUND FAULT INTERRUPTER <br /> NR NON-REVERSING <br /> EVERING <br /> HORN TYPE PROVIDE LOW-VOLTAGE SWITCH CONTROL PANEL NOMENCLATURE GFI GND, G GROUND <br /> PUSHBUTTON STOP-START STATION WIRING AS 3/13 #18 AWG IN 1/2" MIN. C 3A CONTROLLER OR MCC XE 3 V03-1 U D12-1-D HP HORSEPOWER <br /> MID HEIGHT SPEAKER FROM EACH LOW VOLTAGE SWITCH CUBICLE NUMBER T T IMC INTERMEDIATE METAL CONDUIT <br /> 460 VOLT MOTOR (SIZE AS NOTED) M HORN TYPE TO THE LIGHTING CONTROL PANEL SUFFIX "-D" INDICATES DISTRIBUTION PANEL <br /> B UNLESS OTHERWISE NOTED. I MLOW VOLTAGE <br /> 208 VOLT OR 240 V MOTOR CLUSTER HORNS, REF. DETAILS SUFFIX "-1, -2, -3, ETC." IS USED TO INDICATE MULTIPLE M. BKR. MAIN BREAKER <br /> (SIZE AS NOTED) ON SHEET E571 2$M $m MOTION SENSOR SWITCH CONTROL l OR PANELS AT SAME LOCATION WHICH ARE SAME VOLTAGE, FED MCC MOTOR CONTROL CENTER <br /> REF. DETAIL 1A, SHEET E506 / FROM SAME VAULT AND LOCATED ON SAME FLOOR MCM MILLION CIRCULAR MILS <br /> 115 VOLT MOTOR (SIZE AS NOTED) MLO MAIN LUGS ONLY <br /> FIRE ALARM SYSTEM FOR ASSEMBLY NOTE: IF SUFFIX "-A, -B, -C, ETC." IS BEING USED NACB NON-AUTOMATIC CIRCUIT BREAKER <br /> ® POWER FACTOR CORRECTION CAPACITORELEVATOR ALARM BELL $m LUTRON NTHF-40 HI-LUME FLUORESCENT 2 INSTEAD OF "-1, -2, -3, ETC.", THEN CONTINUE USING NEC NATIONAL ELECTRICAL CODE <br /> I <br /> F DIMMING CONTROL AND BALLAST STSTEM. SUFFIX LETTERS FOR CLARITY N/A NOT APPLICABLE <br /> LDC 400 HZ LINE DROP COMPENSATOR CABINET FIRE ALARM HORN STROBE, WALL OR CEILING STARTER SIZE PANEL LOCATION AT NEAREST COLUMN NC NORMALLY CLOSED <br /> W/O TRANSFORMER / <br /> 0 SMOKE DETECTOR, SUBSCRIPT $- REFERENCE DETAIL 2, SHEEP E506. NO NORMALLY OPEN <br /> x:xx LOCATION OF PANEL WHEN NOT ON FIRST FLOOR: PA PAGING SYSTEM <br /> XLDC 400 HZ LINE DROP COMPENSATOR WITH X:XX = DEVICE ADDRESS, "D" = DUCT SMOKE DETECTOR $uIu INCANDESCENT DIMMER LUTRON M = MEZZANINE U = 2ND FLOOR PH PHASE <br /> STEP DOWN TRANSFORMER NTLV 600 SERIES POWER FACTOR P = PENTHOUSE UT = UTILIDOR PNL PANEL <br /> N HEAT DETECTOR, SUBSCRIPT X:XX = DEVICE ADDRESS CORRECTION CAPACITORR = Pt PARKING FLOOR V = 3RD FLOOR PVC POLY-VINYL CHLORIDE (CONDUIT) <br /> CONDUIT NOT BURIED <br /> OH $oM INCANDESCENT DIMMMER, WATTAGE AS RF RETURN FAN <br /> (INCLUDING ABOVE SUSPENDED ® , REMOTE RELAY, SUBSCRIPT X:XX = DEVICE ADDRESS S = P2 PARKING FLOOR W = 4TH FLOOR <br /> CEILING & UNDER RAISED FLOOR) x.xx NOTED. LUTRON MODEL NUMBERS: HP MOTOR HORSEPOWER T = TRUSS LEVEL X = 5TH FLOOR <br /> RVNR REDUCED VOLTAGE, NON-REVERSING <br /> F MANUAL STATION, SUBSCRIPT X:XX = DEVICE ADDRESS NT-1000 SRP SMOKE REMOVAL PANEL <br /> �x:xx TN = TUNNEL <br /> BURIED CONDUIT WIRING WF WATERFLOW SWITCH, SUBSCRIPT X:XX = DEVICE ADDRESS, NT-1500 SWBD SWITCHBOARD <br /> MWF SWGR SWITCHGEAR <br /> (UNDERGROUND & IN FLOOR SLAB) x:xx "P" = PRESSURE TYPE, "PD" = PRESSURE TYPE W/DELAY $ MAGNETIC LOW VOLTAGE DIMMER. LL ELECTRICAL POWER SOURCE OF POWER: VAULT NO. SF SUPPLY FAN <br /> LUTRON P/N NT-1003 FILTER FLIGHTLINE EXAMPLE: VS38 FOR SUBSTATION S38 ST SHUNT TRIP CIRCUIT BREAKER <br /> FLEXIBLE METAL CONDUIT ®x:xx HI/LO AIR PRESSURE SWITCH $LVR .MAGNETIC LOW VOLTAGE TOUCH SWITCH. 01.13.15 TO BE DETERMINED <br /> SUBSCRIPT X:XX = DEVICE ADDRESS T VOLTAGE AND ASSOCIATED PANEL SYMBOL: <br /> CONDUIT HASH MARK DESIGNATIONS LUTRON P/N NTETS-1 T.D. TIME DELAY <br /> PHASE CONDUCTOR Wx.xx TAMPER SWITCH (VALVE SWITCH) FUSED SWITCH ® 4•= 48OV, 3PH, 3W THHN WIRE INSULATION TYPE REFER TO N.E.C. <br /> SINGLE LINE ® 3 = 480Y/277V, 3PH, 4W THWN WIRE INSULATION TYPE REFER TO N.E.C. <br /> ��NEUTRAL CONDUCTOR SUBSCRIPT X:XX = DEVICE ADDRESS v 2 = 208Y/12OV, 3PH, 4W OR 120/24OV, 1 PH, 3W T/S TWISTED AND SHIELDED PAIR <br /> GROUND CONDUCTOR FATC FIRE ALARM TERMINAL CABINET � �d � � © 5 = 400 HZ, 575Y 331V, 3PH, 4W UH UNIT HEATER <br /> \_JSOLATED GREEN GROUND CONDUCTOR o IlAJ.1 TRANSFORMER (DASHED LINE I/ / WP WEATHER PROTECTED <br /> FACP FIRE ALARM CONTROL PANEL INDICATES ELECTROSTATIC f DISCONNECT SWITCH © 2 = 400 HZ, 200Y/115V, 3PH, 4W XFMR TRANSFORMER <br /> CIRCUIT SOURCE 1Y� SHIELD) 1 = 28 VDC' AF AMPS-FRAME <br /> PANEL/CIRCUIT BREAKER N0.(S) ® GENERATOR AT AMPS-TRIP <br /> 1D6-1/1,3,5 SURGE ARRESTER / <br /> PREFIX: (BLANK) = NORMAL POWER PANEL <br /> "I" = ISOLATED GND PANEL <br /> TRANSFER SWITCH <br /> CONDUIT TURNS DOWN - � "Z" = 400 HZ PANEL <br /> -�� CONDUIT TURNS UP )` CIRCUIT BREAKER "XE" = EMERGENCY PANEL <br /> T ELECTRICAL OPERAT R DISCONNECT SWITCH "XL" = LEGALLY REQUIRED STANDBY PANEL <br /> -� CONDUIT ONLY / E LT = LONG T.D. TRIP UNIT "XS" = OPTIONAL STANDBY PANEL <br /> ST = SHORT T.D. TRIP UNIT INTERLOCK <br /> = _INSTANT. TRIP UNIT <br /> -E- EMERGENCY CIRCUIT Y LT GF== GND. FAULT TRIP UNIT EEL CTRCALKEY <br /> L 1!;:ww_i_i <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE <br /> ACCEPTABILITYDRAWN DATE suenTLe cuRRENr RensloN mneoLDATE <br /> - RECORD DRAWING J#567957 HGI 05.16.08 APPROVED BY DEPT.SPEWS DEIST NS APD/ROVED GATE OR ELECTRICAL LEGEND&ABBREVIATIONS BN CEMENT E 1 A C 10.04.19 <br /> A RFID SCANNER RECEPTACLES- RECORD DRAWING 1211218 SAZAN/PT 01.13.15 /�/(\ TRLE EVERETT FIRE PANEL REPLA <br /> B EVERETT FIRE PANEL REPLACEMENT W2640474 SAZAN/ZO 05.29.19 1/ HECKED <br /> `�/J_- Ai <br /> A R BUILDING 40-054 JOB NO. COMP NO. <br /> C SHOP DRAWINGS AGOW/HG 10.04.19 <br /> ELECTRICAL MASTER EVERETT, WA._N0• 40-054-ElA <br />