Laserfiche WebLink
■ Shallow Foundations on Glaciolacustrine Deposits: For foundations bearing on competent <br />undisturbed glaciolacustrine deposits, foundations may be designed using an allowable soil bearing <br />pressure of 4,000 psf for isolated spread footings and continuous footings. <br />■ Shallow Foundations on Structural Fill: For foundations bearing on properly placed and compacted <br />structural fill extending down to dense to very dense glacial soils, foundations may be designed using <br />an allowable soil bearing pressure of 3,000 psf for isolated spread footings and continuous footings. <br />The allowable bearing pressures presented above apply to the total dead and long-term live loads and may <br />be increased up to one-third for short-term live loads such as wind or seismic forces. <br />Overexcavated areas must be backfilled with: (1) CDF having a design strength of at least 200 pounds per <br />square inch (psi) where 6,000 psf bearing pressures are used or, (2) structural fill consisting of suitable <br />on -site soils or imported gravel borrow where 3,000 and 4,000 psf is used, respectively. Where structural <br />fill is placed below footings, the fill should extend beyond the edges of the foundations by the depth of the <br />overexcavation. <br />All footings near below -grade walls should be embedded to a depth that is at least below a 1H:1V (horizontal <br />to vertical) line projected up from the bottom of the closest section of wall, otherwise the below -grade walls <br />need to be designed for lateral loads from the footings. <br />4.2.2. Settlement <br />Post -construction settlement of shallow footings supported on native soils or on properly compacted <br />structural fill as recommended above should be limited to less than 1 inch, and differential settlement <br />between comparably loaded column footings or along a 25-foot section of continuous wall footing should <br />be less than 1/2 inch. We expect most of the footing settlements will occur as loads are applied. Loose or <br />disturbed soils not removed from footing excavations prior to placing concrete will result in additional <br />settlement. <br />4.2.3. Lateral Resistance <br />Lateral foundation loads may be resisted by passive resistance on the sides of the footings and by friction <br />on the base of the footings. Frictional resistance may be computed using a coefficient of friction of 0.4 <br />applied to vertical dead -load forces. Passive resistance may be computed using an equivalent fluid density <br />of 350 pcf. The allowable passive resistance is for horizontal soil conditions in front of the footing and is <br />applicable provided that the footings are surrounded by structural fill or constructed neat against native <br />glacial soils. The structural fill should be compacted to at least 95 percent of the maximum dry density <br />(MDD) determined in accordance with ASTM D 1557. Passive pressure resistance should be calculated <br />from the bottom of adjacent floor slabs or below a depth of 1 foot where the adjacent area is unprotected, <br />as appropriate. The allowable frictional resistance and passive resistance values presented above include <br />a factor of safety of about 1.5. <br />If soils adjacent to footings are disturbed during construction, the disturbed soils must be recompacted, <br />otherwise the lateral passive resistance value must be reduced. <br />GMENGINEERs October 30, 2019 Page 7 ' <br />File No. 21288.00200 <br />