FIRE ALARM CONTROLPANEL <br /> SK-4 & SK-4E <br /> Fire Control Panel <br /> Engineering Specifications <br /> The contractor shall provide a completely electrically supervised fire alarm control panel Silent Knight Model SK-4/E.The system shall <br /> contain a fire alarm control panel capable of operating and supervising smoke detection devices, alarm notification devices, and an on- <br /> board annunciator. It shall be compatible with a digital communicator accessory. <br /> The fire alarm control panel shall have a power limited supply,four Class B initiation circuits which shall accommodate heat detectors, <br /> smoke detectors, and manual pull stations. Smoke detection shall be achieved with either 2-or 4-wire detectors that are compatible with <br /> the system.The initiation inputs shall be programmable as 1)verification zones in which detectors are automatically reset one time <br /> before signaling an alarm condition; or 2)combination waterflow supervisory zones that allows the FACP to distinguish between an alarm <br /> switch (waterflow device)and a supervisory switch (tamper) installed on the same circuit.The FACP shall have two 2.5 amp or 5 amp <br /> (with an additional optional standard transformer) programmable notification outputs. It shall have dedicated relays for alarm,trouble,and <br /> supervisory. It shall have two power outputs, one resettable and one non-resettable,each rated at 500 mA. <br /> The FACP shall have an on-board annunciator to indicate alarm, supervisory,trouble, and maintenance conditions.The annunciator must <br /> include LEDs for AC, GENERAL TROUBLE,ALARM SILENCE,WALK TEST, EARTH FAULT,AND LOW BATTERY.The annunciator <br /> shall also contain LEDs to annunciate fire alarms,troubles, supervisory,and maintenance by zone.The FACP must be fully operational <br /> from the annunciator and include buttons for ACKNOWLEDGE,ALARM, SILENCE, RESET, and WALK TEST.The annunciator must also <br /> have separate DISABLE switches for each zone and notification circuit. <br /> Electrical Specifications (cont) <br /> Battery Approvals <br /> Type: Sealed lead acid only M <br /> LED Int <br /> NFPA 72; UL Listed; LED Interface Module. <br /> Charging Circuit: 27.6 VDC @ 0.8A CSFM 7165-0559: 145; <br /> max normal flat charge MEA 297-01-E-3 SK-XRM24 <br /> Charging Capacity: 18 AH 110 Volt Transformer 3-6A. <br /> Size: 7 AH max allowed in FACP. Ordering Information <br /> Larger batteries can housed SK-4 SK-XRM24E <br /> in an RBB accessory cabinet 120 VAC Four Zone Conventional 220 Volt Transformer 3-6A. <br /> Compatible Initiating and NAC FACP SK-RZA4 <br /> Devices Remote Annunciator. <br /> See SK document PN 52612. SK-4E <br /> 240 VAC Four Zone Conventional SK-4XZM <br /> Mechanical Specifications FACP Zone Relay Module. <br /> Cabinet Backbox Dimensions: <br /> 14.5"W x 15" H x 3" D Accessories RBB <br /> (36.83 W x 38.10 H x 7.62 D cm) SK-DP2/4 Remote Battery Box Accessory <br /> Cabinet Door: Dress Panel.Allows access to the Cabinet. Use if back up batteries are <br /> 14.677"W x 15.342" H x 0.375" D panel controls but restricts access to too large to fit into FACP cabinet. <br /> (37.28 W x 38.97 H x 0.95 D cm) system wiring. Dimensions: 16"W x 10"H x 6"D <br /> Cabinet Color: Red SK-CAC4 Digital Communicator Accessories <br /> Installation Class A Convertor. Converts Style B 5104B <br /> The SK-4/E can be surface mounted (Class B) IDCs to Style D (Class A)and Six-zone fire control communicator <br /> using two key slots at the top of the Style B (Class B) NACs to Style Z <br /> backbox and two additional 0.25" (Class A) 5129 <br /> diameter holes at the bottom, or semi- Four channel slave fire communicator <br /> flush mounted using the optional Trim SK-4XTM <br /> Ring P/N TR-1-R Transmitter Module. Provides a <br /> supervised output for local energy <br /> municipal box transmitter and alarm <br /> and trouble reverse polarity. <br /> SILENT This document is not intended to be used for installation purposes.We try MADE IN AMERICA <br /> to keep our product information up-to-date and accurate.We cannot cover <br /> KNIGHT all specific applications or anticipate all requirements.All specifications are FORM#350305 Rev. E <br /> subject to change without notice. For more information,contact Silent <br /> by Honeywell Knight 12 Clintonville Road, Northford, CT 06472-7161 ©2012 Honeywell International Inc. <br /> Phone: (800)328-0103, Fax: (203)484-7118.www.silentknight.com <br />