Laserfiche WebLink
• • <br /> ACpT Powered by Experience. <br /> Driven by Excellence.TM <br /> Commercial <br /> SYSTEM DESCRIPTION <br /> Scope of Work: <br /> ADT to provide cellular communicator Napco Starlink SLE-LTEV-CFBPS (SOLE Path) <br /> supervision by UL Listed Central Station replacing the existing means of communication <br /> to an existing fire alarm system. The cellular communicator will have a single 12vdc, <br /> 7amp hour battery capable of meeting/exceeding the 24hr standby period followed by 5 <br /> minutes of alarm at maximum system load as well. There will be no changes to the <br /> existing fire alarm system or occupancy classification of this space within this scope of <br /> work. <br /> The modification design is by Milissa Johnson, NICET level III <br /> Staff Designer for ADT Commercial <br /> Email: milissajohnson@ADT.com <br /> Ph. direct line: (214) 907-2437 <br />