Laserfiche WebLink
(E) POTTER SignaLinkT" Bridge <br /> The symbol of Protection Wireless Supervisory System <br /> Optional Model PMK Post Mounting Kit for Repeaters <br /> Fig 6 <br /> a1111111414444444440400000 <br /> w1111111444444444440000004 �� <br /> PRY-OFF TAMPER <br /> BRACKET/ACTUATOR <br /> Notes:Kit includes pry-off tamper bracket/actuator. <br /> Kit does not include hose clamps for mounting to post. <br /> 2 hose clamps required.Clamps can be up to 9/16"wide <br /> Troubleshooting and LED Operation <br /> The WRX-R contains the following LEDs to aid in troubleshooting: <br /> LED Signal Color Indication <br /> POWER Green 24 VDC is applied to the receiver <br /> SETUP MODE Amber Indicates when the system is in setup mode <br /> ALARM/SUPERVISORY Red The relay on the WRX-R is activated indicating that the sprinkler switch has activated. <br /> WTX-M Amber Lights steady to indicate the issue initiated from the WTX-M. <br /> WR Amber Flashes to indicate which WR the issue initiated from.One(1)flash means repeater 1 <br /> TAMPER Amber Indicates the cover is removed from WTX-M or WR or the WR has been removed from its mounting location <br /> COM ERROR Amber Communication has been lost from WTX-M or WR <br /> The batteries are low and must be replaced ASAP. <br /> LOW BATTERY Amber Note:All batteries in a device must be replaced at the same time and with the batteries specified in this <br /> document. <br /> EOLR ERROR Amber I There is an open circuit in the wiring between the WTX-M and the sprinkler device to which it is connected. <br /> Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com <br /> 5401587-REV B 6/21 PAGE 9 OF 10 <br />