Laserfiche WebLink
• • <br /> Response :See added Energy Credit Specification table in All. <br /> Comment 5. See energy credits on Sheet All. To qualify to claim credit 3.6,the building <br /> permit drawings shall specify the option being selected,the heating equipment type(s),the <br /> minimum equipment efficiency, and total installed heat capacity(by equipment type). WSEC <br /> Table R406.3 <br /> Response: See added Energy Credit Specification table in All. <br /> Comment 6. See energy credits on Sheet All. To qualify to claim this credit,the building <br /> permit drawings should specify the option being selected and should specify the water <br /> heater equipment type and the minimum equipment efficiency. WSEC Table R406.3 <br /> Response : See added Energy Credit Specification table in All. <br /> Comment 7. The roof details should comply with the ventilation requirements of IRC Section <br /> R806 and WSEC Section R402.2.3. Include a calculation for the minimum required ventilation <br /> area in the drawings. The vents should be equally distributed between the roof eaves and <br /> ridge, and around the building perimeter. <br /> Response : See added Roofing notes on the bottom of A10. <br /> Sincerely, <br /> Soniya From Blue Moon Realty LLC <br /> Attachments : Revised copies of Architectural Plans <br />