Laserfiche WebLink
GENERAL PERFORMANCE AND ELECTRICAL DATA - MODEL PTC . <br /> sgODINE <br /> Table 5.1 - Propeller Unit Heater Model PTC General Performance Data <br /> Model PTC Sizes <br /> 55 65 85 110 135 156 180 215 260 310 <br /> BtulHr Input i0 55,000 65,000 85,000 110,000 135,000 155,000 180,000 215,000 260,000 310,000 <br /> Btu/Hr Output CD 51,150 60,450 79,050 102,300 125,500 144,150 167,400 199,950 241,800 288,300 <br /> Condensate Production(Gal./Hr.) 0.3 0.4 0.5 0.7 1.0 1.1 1.3 1.6 1.9 2.3 <br /> Entering Airflow(CFM)@ 70°F OO 1097 1141 1650 1750 2160 2600 3020 3865 4585 5400 <br /> Outlet Velocity(FPM)OO 618 650 619 668 719 862 676 699 831 765 <br /> Air Temp.Rise(°F) 43 49 44 54 54 51 51 48 49 49 <br /> Max.Mounting Height(Ft.) 20 12 12 13 13 14 18 15 17 20 19 <br /> Heat Throw(Ft.)@ Max. Mtg Ht 43 43 48 46 51 62 53 60 70 67 <br /> Motor Type O PSC PSC PSC PSC PSC PSC PSC PSC PSC PSC <br /> Motor HP 1/8 1/8 1/8 1/3 1/3 1/3 1/3 1/2 3/4 3/4 <br /> Motor RPM 1440 1440 1550 1075 1075 1075 1075 1075 1125 1125 <br /> O Ratings shown are for elevations up to 2,000 ft.For elevations above 2,000 feet,ratings should be reduced at the rate of 4%for each 1,000 feet above <br /> sea level(in Canada see rating plate).Reduction of ratings requires use of a high altitude kit. <br /> ©Data taken at 65°F ambient and unit fired at full-rated input.Mounting height as measured from bottom of unit,and without deflector hoods. <br /> s All motors used are produced,rated and tested by reputable manufacturers in accordance with NEMA standards and carry the standard warranty of both <br /> the motor manufacturer and Modine.All motors are totally enclosed and all single phase motors have built-in thermal overload protection. <br /> Table 5.2 - Model PTC Operating Electrical Data © <br /> Supply Model PTC Sizes <br /> Voltage Power Code <br /> 9 55 65 85 110 135 156 180 215 260 310 <br /> Motor Amps 2.20 2.20 2.20 4.60 4.60 4.60 4.60 7.00 8.80 8.80 <br /> 115V 01 (115V) Total Amps 4.35 4.35 4.35 6.75 6.75 6.75 6.75 9.15 10.95 9.85 <br /> 1 Phase <br /> Transformer kVA n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a <br /> 208V 01 (115V)with Transformer kVA 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.50 1.50 1.50 <br /> 1 or 3 Phase Transformer 208V Total Amps 2.41 2.41 2.41 3.73 3.73 3.73 3.73 5.06 6.05 5.45 <br /> 230V 01 (115V)with Transformer kVA 0.75 0.75 0.75 1.00 1.00 1.00 1.00 1.50 1.50 1.50 <br /> 1 or 3 Phase Transformer 230V Total Amps 2.18 2.18 2.18 3.38 3.38 3.38 3.38 4.58 5.48 4.93 <br /> 460V 01 (115V)with Transformer kVA 0.75 0.75 0.75 1.00 1.00 1.00 1.00 1.50 1.50 1.50 <br /> 3 Phase Transformer 4.60V Total Amps 1.09 1.09 1.09 1.69 1.69 1.69 1.69 2.29 2.74 2.46 <br /> 575V 01 (115V)with Transformer WA 0.75 0.75 0.75 1.00 1.00 1.00 1.00 1.50 1.50 1.50 <br /> 3 Phase Transformer 575V Total Amps 0.87 0.87 0.87 1.35 1.35 1.35 1.35 1.83 2.19 1.97 <br /> ©Amp draw data shown is operating amp draw at incoming power.For units that use a field installed accessory step-down transformer as noted,the amp draw shown is <br /> the primary side operating amp draw.For sizing of circuit protection for equipment with transformers,please refer to the National Electric Code. <br /> 6-170.7 5 <br />