Laserfiche WebLink
SPRINKLER SYSTEM INPUT DATA Page 1 <br /> DATE: 6/9/2023 C:\USERS\CHUCKB\DESKTOP\DATA\F23019.SDF <br /> JOB TITLE: Res Pend 2 heads of 1" <br /> Source Nodes <br /> Node Tag Elevation Static Residual Flow Hose Stream <br /> Pressure Pressure Allowance <br /> (ft) (psi) (psi) (gpm) (gpm) <br /> SRC'. -5.00 60.0 20.0 1500 100 <br /> Node Data <br /> Node Tag Elevation K Node Tag Elevation K <br /> (ft) (ft) <br /> SRC -5.0 SOURCE TW 11.00 0.00 <br /> BOR 1.00 0.00 21 11.00 0.00 <br /> BFI 3.00 0.00 25 11.00 0.00 <br /> BFO 3.00 0.00 4 11.00 4.02 <br /> 88 3.00 0:00 3 \ 11.00 4.02 <br /> FPI 3.00 0.00 2 11.00 4.02 <br /> FPO 3.00 0.00 1 11.00 4.02 <br /> Pipe Data <br /> Pipe Tag End Node Tags Length Fittings Diameter HWC <br /> (ft) (ft) (in) <br /> 1 SRC BOR 99.00 2ETG 6.280 (D6.000) 140 <br /> 2 BOR BFI 5.00 2E 6.357 (B6.000) 120 <br /> 3 BFI BFO Fixed Loss Device -9.000 psi <br /> 4 BFO 88 11.00 2E2T 6.357 (86.000) 120 <br /> 5 '88 FPI 11.00 2E 4.260 (B4.000) 120 <br /> 6 FPI FPO Pump 45.0.0 gpm 75.psi <br /> 7 FPO TW 22.00 3E2TB 4.260 (B4.000) 120 <br /> 8 TW 25 44.00. 8E 2.635 (82.500) 120 <br /> 9 25 21 222.00 9E 2.635 (82.500) 120 <br /> 10 21 4 11.00 2T 1.380 (A1.250) 120 <br /> 11 4 3 11.00 0.0 1.380 (A1.250) 120 <br /> 12 3 2 11.00 0.0 1.049 (A1.000) 120 <br /> 13 2 1 11.00 0.0 1.049 (A1..000) 120 <br />