Laserfiche WebLink
Document management portal powered by Laserfiche WebLink 9 © 1998-2015 Laserfiche. All rights reserved.
* NOT FOR SUBMITTAL * SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 <br /> DATE: 6/9/2023 C:\USERS\CHUCK9\DESKTOP\DATA\F23019.SDF <br /> JOB TITLE: Res Pend 2 heads of 1" <br /> PIPE TAG END NODE TAGS FLOW VEL DIA LENGTH PF/FT PF PE <br /> 1 SRC BOR 85.1 0.9 6.280 195.00 0.000 0.0 -2.6 <br /> 2 BOR BFI 85.1 0.9 6.357 41.00 0.000 0.0 -0.9 <br /> 3 BFI BFO Fixed pressure loss device: 9.0 psi, 85.1 gpm <br /> 4 BFO 88 85.1 0.9 6.357 123.00 0.000 0.0 0.0 <br /> 5 88 FPI 85.1 1.9 4.260 37.00 0.002 0.1 0.0 <br /> 6 FPI FPO Fire pump rating: 450 gpm, 75 psi Act. flow 85 <br /> 7 FPO TW 85.1 1.9 4.260 129.00 0.002 0.3 -3.5 <br /> 8 TW 25 85.1 5.0 2.635 108.00 0.021 2.3 0.0 <br /> 9 25 21 85.1 5.0 2.635 294.00 0.021 6.3 0.0 <br /> 10 21 4 85.1 18.2 1.380 23.00 0.498 11.5 0.0 <br /> 11 4 3 61.9 13.3 1.380 11.00 0.276 3.0 0.0 <br /> 12 3 2 39.8 14.8 1.049 11.00 0.46.4 5.1 0.0 <br /> 13 2 1 19.6 7.3 1.049 11.00 0.125 1.4 0.0 <br /> Maximum water velocity is 18.2 ft/sec. at pipe 10. <br />