Laserfiche WebLink
Kidde Fire Systems Kidde <br /> System Component Datasheet � Fire Systems <br /> Stackable Electric Control Head Kits Effective: October 2019 <br /> with Control Head Monitor K-85-3002 Rev AD <br /> FEATURES <br /> • UL Listed, ULC Listed,and FM Approved for use with systems listed in the Table, "COMPATIBILITY",on page 2. <br /> P/N: 85-486500-010 <br /> ORDER INFORMATION <br /> Part Number Description <br /> 85-486500-010 Kit, Includes: <br /> Electrical Control Head, 24 VDC, Stackable, (Ex. Proof), P/N: 82-486500-010 <br /> Control Head Monitor, P/N 85-100000-100 <br /> (for more information, see data sheet K-85-3000) <br /> Lever Operated Control Head, P/N WK-870652-000 <br /> (for more information, see data sheet K-85-6005) <br /> Note: This kit is UL listed and FM Approved. <br /> 85-486500-020 Kit, Includes: <br /> Electrical Control Head, 24 VDC, Stackable, (Ex. Proof), P/N: 82-486500-010 <br /> Control Head Monitor, P/N 85-100000-100 <br /> (for more information, see data sheet K-85-3000) <br /> Note: This kit is UL listed but Not FM Approved. <br /> Note: Both kits are not suitable for 600/900/1100 Ib ECS Cylinders,ADS Cylinders, Nitrogen drivers, Nitrogen pilot cylinders, <br /> and FE-13 Cylinders. <br /> MO-- <br /> 1.25-18 UNEF-2A <br /> CONNECTION <br /> I <br /> I <br /> I <br /> 1/2"-14 NPT <br /> CONDUIT <br /> CONNECTION <br /> ELECTRIC CONTROL HEAD,PART <br /> NO.486500-01 IS RATED FOR USE <br /> IN HAZARDOUS(CLASSIFIED) <br /> LOCATIONS CLASS 1,DIV.I, <br /> GROUPS C,D AND CLASS II,DIV.II, 5.28" <br /> GROUPS E,F,G BETWEEN <br /> -40F AND 140F.USE CONDUIT <br /> SEAL WITHIN 18 IN.(45-)OF <br /> THIS DEVICE. (8)16 AWG-LEADS <br /> 18"LONG <br /> SWIVEL NUT <br /> 1.25-18 UNEF-2B <br /> CONNECTION <br /> Note: This control head is polarized. Improper wiring will result in failure of this device to operate. <br /> Electric control head, P/N: 82-486500-010, is designed for installation directly on 487 Series Halon and <br /> © Kidde Fire Systems ECSTm agent valves only to a maximum size of 350 lbs. This control head must not be <br /> installed on any other type of halon or agent cylinder valve, nitrogen valve, carbon dioxide cylinder valve, <br /> WARNING FE-13TH cylinder valve or Stop(Directional)valve. Installation of this control head to any other device(e.g., <br /> pressure operated control head)will result in failure of device to operate. <br /> MATERIAL SPECIFICATIONS <br /> Body: Brass Voltage: 24 VDC <br /> Current: 0.2A Continuous Draw <br /> 1 <br />