Laserfiche WebLink
�KiddeFire Systems Consolidated Report <br /> Minimum: 68 F Width: <br /> 0.0 ft <br /> Maximum: 70 F Length: 0.0 ft <br /> Max. Concentration: 6.96% (At 70 F) Height: 0.0 ft <br /> Design Concentration: Volume: 1051.7 ft 3 <br /> Adjusted: 6.93 % Non-permeable: 0.0 ft 3 <br /> Minimum: 4.50 % Total Volume: 1051.7 ft 3 <br /> Min. Agent Required: 43.1 Ib <br /> Adjusted Agent Required: 68.0 Ib <br /> Concentration Profile: UL/FM Class C, (4.5 %) <br /> Agent Source Report <br /> Agent: 3M" Novec'm 1230 Fire Protection Fluid <br /> Cylinder Name: 70 Ib Cylinder <br /> Cylinder Part Number: 45-550070-001 <br /> Agent Per Cylinder: 68.0 Ib <br /> Fill Density: 68.0 Ib/cubic ft <br /> Number of Main Cvlinders: 1 <br /> Number of Reserve Cylinders: 0 <br /> Cylinder EmptV Weight: 52.0 Ib <br /> Weight, All Cylinders +Agent: 120.0 Ib <br /> Floor Area Per Cylinder: 0.44 ft Z <br /> Floor Loading Per Cylinder: 273 Ib/ft Z <br /> Calculation Date/Time: Friday,June 9, 2023, 10:31:24 AM <br /> Copyright(c)JENSEN HUGHES,Inc. Licensed to:Kidde-Fenwal <br /> KeyID:92152844 <br /> Page:2 of 8 <br />