Laserfiche WebLink
SYSTEM VALVE ACTUATOR, P/N 87-120042-001 Range Guard cylinder and valve assemblies. The Dis- <br /> A System Valve Actuator (SVA) must be mounted to charge Adapter Kit (DAK) consists of a valve outlet <br /> every Range Guard cylinder valve assembly (see adapter, o-ring and steel flange plate. The valve outlet <br /> Figure 2). The SVA contains a pneumatically operated adapter has a 3/4" NPT male thread and 1/2" NPT female <br /> piston, which depresses the cylinder valve stem to open thread for connection to system piping. <br /> the valve and discharge the wet chemical. The SVA has The Discharge Adapter can also be used as a recharge <br /> ports for connection of actuation tubing or braided hose adapter to pressurize Range Guard cylinders with nitro- <br /> to the Badger control system. Nitrogen from the control gen after re-filling with Karbaloy wet chemical. <br /> head flows through the actuation tubing, pressurizing the <br /> SVA(s), thereby extending the internal SVA piston. The A Discharge Adapter Kit is required for every cylinder and <br /> piston is equipped with a spring-loaded plunger, which must be ordered separately. <br /> locks the piston in the actuated position, ensuring a com- FLANGE PLATE <br /> plete cylinder discharge. <br /> 3/4 in.NPT <br /> 1/8 in. <br /> NPT PORT - <br /> �y <br /> ADAPTER <br /> O-RING <br /> SPRING LOADED <br /> PISTON IN ACTUATED � PLUNGER Figure 4. Discharge Adapter Kit <br /> POSITION(TOWARDS <br /> CYLINDER VALVE) <br /> Figure 2. System Valve Actuator NUT 5/16-18- SHIPPING CAP <br /> NUT 5/16-18 <br /> ANTI-RECOIL AND VALVE PROTECTION O-RING <br /> PLATES DISCHARGE ADAPTER x <br /> Each Range Guard cylinder is factory equipped with an FLANGE PLATEJ <br /> anti-recoil plate and valve protection plate (see Figure 3). <br /> The anti-recoil plate is a safety feature attached to the 5/16-18 X1 in.BLGONG� <br /> valve outlet port. In the event of an accidental actuation <br /> of a cylinder that is not properly secured and connected <br /> CYLINDER AND VALVE <br /> to system piping, the anti-recoil plate will provide a con- ASSEMBLY <br /> trolled, safe discharge. Figure 5. Discharge Adapter Kit Installation <br /> The valve protection plate is installed on the valve actua- <br /> tion port to prevent tampering or accidental depression of VENT PLUG, P/N 60-9196984-000 <br /> the valve actuation pin. The Vent Plug (see Figure 6) is installed in the discharge <br /> VALVE PROTECTION piping near a Range Guard cylinder to prevent pressure <br /> PLATE build up in the system piping, caused by heat, from rup- <br /> turing the foil seals on the nozzles. The Vent Plug has a <br /> ANTI-RECOIL 1/2-inch NPT male thread, and must be installed in an <br /> PLATE <br /> upright or horizontal position, one per pipe network. <br /> VALVE AND <br /> CYLINDER ASSEMBLY 1/2 in. <br /> - � (13 mm) <br /> NPT 1-1/8 in. <br /> (29 mm) <br /> Figure 3. Anti-Recoil and Valve Protection Plates <br /> DISCHARGE ADAPTER KIT, P/N 83-844908-000 <br /> The Discharge Adapter (see Figure 4 and Figure 5) pro- Figure 6. 1/2-inch Vent Plug, P/N 60-9196984-000 <br /> vides a means to connect agent distribution pipe to <br /> - 3 - <br />