Laserfiche WebLink
Test Equipment <br />The following test equipment was used in the performance of the enclosure integrity tests. <br />Gauge <br />Fan <br />Fan serial <br />Fan calibration <br />Gauge <br />Gauge Calibration <br />serial <br />#1 <br />Retrotec 6000 <br />3PH600147 <br />DM32 <br />Fan Calibration Certificate Retrotec 6000: <br />Retrotec 6000 3PH600147 <br />Range <br />n <br />K <br />K1 <br />K2 <br />K3 <br />K4 <br />Open <br />0.498 <br />548 <br />0 <br />0.5 <br />0 <br />1 <br />A <br />0.502 <br />287 <br />0 <br />0.5 <br />0 <br />1 <br />B8 <br />0.54 <br />113.25 <br />0 <br />0.8 <br />0 <br />1 <br />{1- <br />{1-CalibKl- <br />CalibRange- <br />{1-CalibN-4} <br />{1-CalibK-4} <br />{1-CalibK2-4} <br />{1-CalibK3-4} <br />{1-CalibK4-4} <br />41 <br />4} <br />{1- <br />{1-CalibKl- <br />CalibRange- <br />{1-CalibN-5} <br />{1-CalibK-5} <br />{1-CalibK2-5} <br />{1-CalibK3-5} <br />{1-CalibK4-5} <br />51 <br />5} <br />{1- <br />{1-CalibKl- <br />CalibRange- <br />{1-CalibN-6} <br />{1-CalibK-6} <br />{1-CalibK2-6} <br />{1-CalibK3-6} <br />{1-CalibK4-6} <br />6} <br />61 <br />{1- <br />CalibKl- <br />CalibRan e- <br />g <br />1-CalibN-7 <br />{ } <br />1-CalibK-7 <br />{ } <br />7} <br />1-CalibK2-7 <br />{ } <br />1-CalibK3-7 <br />{ } <br />{ 1-CalibK4-71 <br />7} <br />{1- <br />{1-CalibKl- <br />CalibRange- <br />{1-CalibN-8} <br />{1-CalibK-8} <br />{1-CalibK2-8} <br />{1-CalibK3-8} <br />{1-CalibK4-8} <br />81 <br />8} <br />{1- <br />{1-CalibKl- <br />CalibRange- <br />{1-CalibN-9} <br />{1-CalibK-9} <br />{1-CalibK2-9} <br />{1-CalibK3-9} <br />{1-CalibK4-9} <br />91 <br />9} <br />{1- <br />{1-CalibKl- <br />{1-CalibK2- <br />11-CalibK3- <br />11-CalibK4- <br />CalibRange- <br />{1-CalibN-10} <br />{1-CalibK-10} <br />101 <br />101 <br />101 <br />101 <br />10} <br />Page 11 of 12 <br />