Fire Alarm System Secondary Battery-set Calculation Worksheet <br /> Standby Total Alarm <br /> Total Standby Alarm/Transmit <br /> AES Product Current QTY QTY Current <br /> (Amps) Current(Amps) Current (Amps) (Amps) <br /> 7707P-88-ULP-1 0.4000 X 1 = 0.400 1.5500 X 1 = 1.550 <br /> Total System Total System <br /> Standyby Current (Amps) 0.400 Alarm Current (Amps) 1.550 <br /> ## Hour Standby Required Required <br /> Standby Time Current Standby Capacity Required Alarm Time Alarm/Transmit Alarm <br /> `**" (Amps) (Amp-Hours) (Hours) Current(Amps) Capacity <br /> (Amp-Hours) <br /> 24 X 0.400 = 9.600 1 X 1.5500 y = 1.550 <br /> Ili <br /> Required <br /> Standby Required Total Capacity <br /> Capacity Alarm Capacity (Amp-Hours) <br /> (Amp-Hours) (Amp-Hours) <br /> 9.60 + 1.550 = 11.150 <br />