Drew Martin <br /> From: Drew Martin <br /> Sent: Monday, May 16, 2022 2:39 PM <br /> To: Adam Clark <br /> Subject: City of Everett Permit Services: 8717 7th Avenue SE (132204-070) - First Building Review <br /> Hello,Adam. <br /> This email recaps our conversation and will serve as the review letter for this project. Pending the resolution of the <br /> comments below,you can provide direction for me to apply redlines, or provide two revised hard copies of the <br /> drawings. In either case, please provide brief itemized responses to clarify any changes required or performed. <br /> Comments: <br /> 1. The plumbing facilities counts should be verified to comply with the minimum requirements of Chapter <br /> 29. Where the existing counts are less than required,the design should not further reduce the count. <br /> 2. Verify if the door for the accessible compartment in Partial Plan 2/A3.1 should be reversed (i.e., locate hinge in <br /> corner of compartment) to comply with ICC A117.1-09. <br /> 3. The typical water closet details should specify the flush control on the open side. <br /> 4. The grab bar details should include a note requiring blocking capable of supporting a minimum 250-pound load. <br /> Please let me know if you have questions. <br /> — Drew Martin, P.E.,S.E. <br /> Associate Engineer—Commercial Plans Examiner I Permit Services <br /> 425.257.8810 13200 Cedar Street, 2nd Floor, Everett,WA 98201 <br /> EVERETT Phone Hours: M/W/T: 8 am - 12 pm & 1 pm—3 pm;Tu: 1:00pm-3:00pm <br /> everettwa.gov/permits I Facebook I Twitter <br /> Note:Emails and attachments sent to and from the City of Everett are public records and may be subject to disclosure pursuant to the Public <br /> Records Act. <br /> 1 <br />