Laserfiche WebLink
SYSTEM RECORD OF COMPLETION (continued) <br /> 5. SYSTEM POWER <br /> 5.1 Control Unit <br /> 5.1.1 Primary Power <br /> Input voltage of control panel: 120yac Control panel amps: 3 <br /> Overcurrent protection: Type: BREAKER Amps: 20 <br /> Branch circuit disconnecting means location: BREAKER Number: <br /> 5.1.2 Secondary Power <br /> Type of secondary power: BATTERY BACK-UP <br /> Location,if remote from the plant: IN FACP <br /> Calculated capacity of secondary power to drive the system: <br /> In standby mode(hours): 24 In alarm mode(minutes): 5 <br /> 5.2 Control Unit <br /> ❑ This system does not have power extender panels <br /> ® Power extender panels are listed on supplementary sheet A <br /> 6. CIRCUITS AND PATHWAYS <br /> Pathway Type Dual Media Pathway Separate Pathway Class Survivability Level <br /> Signaling Line B 1 <br /> Device Power B 1 <br /> Initiating Device B 1 <br /> Notification Appliance B 1 <br /> Other(specify): <br /> 7. REMOTE ANNUNCIATORS <br /> Type Location <br /> GAMEWELL RA-1000R MAIN ENTRY <br /> 8. INITIATING DEVICES <br /> Addressable or <br /> Type Quantity Conventional Alarm or Supervisory Sensing Technology <br /> Manual Pull Stations 1 ADDRESSABLE ALARM <br /> Smoke Detectors 8 ADDRESSABLE ALARM PHOTO <br /> Duct Smoke Detectors ADDRESSABLE SUPERVISORY <br /> Heat Detectors ADDRESSABLE ALARM <br /> Gas Detectors ADDRESSABLE ALARM <br /> Waterflow Switches 3 ADDRESSABLE ALARM <br /> Tamper Switches 7 ADDRESSABLE SUPERVISORY <br /> eot <br /> Copyright 02012 National Fire Protection Association.This form maybe copied for individual use other than for resale.It may not be copied for commercial sale or distribution. <br />