Laserfiche WebLink
AIR TERMINAL SCHEDULE bassetti <br /> NECK architects <br /> AIRFLOW CAPACITY LIMITS NOMINAL SIZE DIMENSIONS MAX <br /> (CFM) (IN) (IN) TSP DROP BASIS OF DESIGN <br /> CALLOUT AIR TERMINAL DESCRIPTION MAXIMUM MINIMUM LENGTH WIDTH DIAMETER MAX NC (IN. W.G.) MATERIAL OBD FINISH MANUFACTURER MODEL NOTES 71 Columbia Street,Suite 500 <br /> EG-1 CEILING MOUNTED EGGCRATE RETURN GRILLE 150 60 8 8 - 22 0.08 ALUMINUM NO #26 WHITE PRICE 80 Seattle,Washington 98104 <br /> T(206)340 9500 <br /> EG-2 CEILING MOUNTED EGGCRATE RETURN GRILLE 350 200 10 10 - 22 0.08 ALUMINUM NO #26 WHITE PRICE 80 www.bassettiarch.com <br /> RG-1 CEILING MOUNTED EGGCRATE RETURN GRILLE - - 24 24 - - - ALUMINUM NO #26 WHITE PRICE 80 [1] <br /> SD-1 CEILING MOUNTED MODULAR CORE DIRECTIONAL DIFFUSER 150 50 24 24 8 17 0.08 ALUMINUM NO #26 WHITE PRICE SMCD MECHANICAL ENGINEER <br /> FSi <br /> SD-2 CEILING MOUNTED MODULAR CODE DIRECTIONAL DIFFUSER 325 150 24 24 10 20 0.08 ALUMINUM NO #26 WHITE PRICE SMCD SeattleAlaskan98104 Suite 200 <br /> Seattle WA 98104 <br /> SD-3 CEILING MOUNTED MODULAR CORE DIRECTIONAL DIFFUSER 500 345 24 24 12 28 0.12 ALUMINUM NO #26 WHITE PRICE SMCD T(206)385 6124 <br /> SD-4 CEILING MOUNTED MODULAR CORE DIRECTIONAL DIFFUSERS 150 50 8 1 8 6 X 6 28 0.012 ALUMINUM NO #26 WHITE PRICE SMCD ELECTRICAL ENGINEER <br /> SCHEDULE NOTES: Hargis <br /> 1201 Third Avenue,Suite 600 <br /> [1] PROVIDE WITH DUCT LINED RETURN AIR BOOT PER DETAIL 1 ON M2.01 Seattle WA98101 <br /> T(206)436 0457 <br /> FOOD SERVICE <br /> EXHAUST FAN SCHEDULE 55RDesign Group <br /> 557 Roy St.Suite 175-A <br /> Seattle,WA 98109 <br /> CALLOUT FAN BASIS OF DESIGN 7(206)6250070 <br /> E.S.P MOTOR ELECTRICAL[4] MAX SOUND <br /> DRIVE (IN WC) TIP SPEED FEG LEVEL <br /> TYPE MARK LOCATION FAN TYPE SERVICE CFM TYPE [1] (FPM) RPM [3] SPEED HP BHP V HZ 4 (DBA) MANUFACTURER MODEL NOTES PE <br /> EF 1 CEILING INLINE KITCHEN HOOD 400 DIRECT 0.50 - 1563 N/A ECM .102 N/A 120 60 1 56 COOK 100SQN17DH (VF) [2],[5] iiR4 <br /> EF 2 CEILING INLINE RESTROOMS 575 DIRECT 0.75 - 2031 N/A ECM .222 N/A 120 60 1 64 COOK 100SQN28DO80VF [2],[6] Seattle//Spokane//IBaltimore <br /> SCHEDULE NOTES: <br /> 1 STATIC PRESSURE EXTERNAL TO FAN. <br /> 2 PROVIDE WITH ECM MOTOR. <br /> ONE INCH <br /> 3 AS RATED PER AMCA 205. <br /> 4 SINGLE POINT CONNECTION AND UNIT PROVIDED WITH INTEGRAL DISCONNECT. AT FULL SIZE <br /> 5 PROVIDE WITH COOK VARI-FLOW CONTROLLER (VFF2SC) FOR EXHAUST DAMPER AND START/STOP CONTROL (VIA RESIDENTIAL HOOD CONTROLLER). <br /> 6 PROVIDE WITH COOK VARI-FLOW CONTROLLER (VFF2SC) FOR EXHAUST DAMPER AND START/STOP CONTROL (VIA 7-DAY PROGRAMMABLE CONTROLLER). M• C114 <br /> P�Or NA$y� O <br /> LOUVER SCHEDULE s Y <br /> AIRFLOW CAPACITY LIMITS NOMINAL SIZEIT <br /> MOUNTING fssioNa <br /> CALLOUT (CFM) (IN) [5] FACE PRESSURE HEIGHT BASIS OF DESIGN = <br /> FREE AREA VELOCITY DROP RAPE OF <br /> FRAME AND (FT) s� <br /> TYPE MARK DESCRIPTION MAXIMUM MINIMUM LENGTH WIDTH (SQ. FT.) (FPM) (IN. W.G.) MOUNTING [1] SERVICE MATERIAL MANUFACTURER MODEL NOTES <br /> L 1 DRAINABLE STATIONARY EXTRUDED LOUVER 1000 0 40 36 5 500 0.08 CHANNEL SEE ARCH EXHAUST AIR ALUMINUM RUSKIN ELF445DXH [2], [3], [4] <br /> SCHEDULE NOTES: REVISIONS DATE <br /> 1 MOUNTING HEIGHT MEASURED FROM BOTTOM OF LOUVER TO TOP OF FINISHED FLOOR. REFER TO ARCHITECTURAL PLANS FOR FINISHED MOUNTING HEIGHT AND LOCATION. <br /> 2 PROVIDE WITH EXTENDED SILL. <br /> 3 PROVIDE WITH ALUMINUM BIRD SCREEN. <br /> 4 PROVIDE WITH 70% KYNAR FINISH. COLOR TO BE SELECTED BY ARCHITECT. <br /> 5 COORDINATE EXACT SIZE OF LOUVER WITH ARCHITECTURAL PLANS. <br /> EXISTING SERIES FAN POWERED VAV BOX SCHEDULE <br /> CALLOUT FAN MOTOR CHARACTERISTICS HEATING COIL <br /> INLET STATIC MIN. OUTSIDE <br /> PRIMARY AIR PRESUURE INLET RADIATED NUMBER OF AIR QTY. <br /> TYPE MARK (CFM) (IN. WG) SIZE NC LEVEL HP FLA VOLTS/PH/HZ KW STAGES VOLTS/PH/HZ (CFM) SIZE Owner <br /> FPB 1-1 400 1.0 8 - 1/6 1.3 277/1/60 2,7 1 480/3/60 145 2 BEZOS- <br /> FPB 1-2 1250 1.0 12 31 1/3 3.3 277/1/60 12 2 480/3/60 300 5 EVERETT TRANSIT <br /> FPB 1-2A 1250 1.0 12 31 1/3 3.3 277/1/60 6 1 480/3/60 300 5 STATION <br /> FPB 1-3 1250 1.0 12 31 1/3 3.3 277/1/60 12 1 480/3/60 300 1 5 <br /> FPB 1-3A 1250 1.0 12 31 1/3 3_ 277/1/60 6 1 480/3/60 300 5 <br /> FPB 1-4 700 1.0 10 25 1/4 2.4 277/l/60 5.5 1 480/3/60 230 3 <br /> FPB 1-5 1000 1.0 12 28 1/3 3.3 277/l/60 8,0 1 480/3/60 200 5 3291 SMITH AVE. <br /> FPB 1-6 500 1.0 1 8 26 1 1/6 1 1.3 277/l/60 4.0 1 1 480/3/60 145 2 EVERETT WA 98201 <br /> FPB 1-13 840 1.0 12 28 1/3 3.3 277/1/60 HWC MBH 1.28.4 480/3/60 325 5 JOB NO: 2018 <br /> FPB 1-17 200 1.0 8 - 1/6 1.3 277/l/60 1.5 1 480/3/60 145 1 2 ISSUE DATE: 05/12/2022 <br /> Jurisdiction Stamp Area <br /> r <br /> W <br /> U) HVAC <br /> 9 SCHEDULES <br /> m <br /> 0 <br /> N N <br /> N a M6.01 <br />