Laserfiche WebLink
i Permit Inspections <br /> V E R E T T City of Everett <br /> WASHINGTON <br /> Properly wet vent kitchen and lav per chapter 9 vents on vertical wet venting.Wet vented section needs to increase by one pipe size. <br /> 3/8/2023 3/8/2023 PLUMB 08-FINAL JASON CORRECTION see notes <br /> MORRISSEY REQUIRED <br /> Notes: <br /> 206-856-8935 <br /> RYAN0982@LIVE.COM <br /> Cannot use double San tee needs to be double fixture fitting per the UPC for back to back kitchen sink and lay.-2018 UPC 704.2 Single Vertical Drainage <br /> PipeTwo fixtures set back-to-back,or side-by-side,within the distance allowed between a trap and its vent,shall be permitted to be served by a single <br /> vertical drainage pipe provided that each fixture wastes separately into an approved double-fixture fitting having inlet openings at the same level.- <br /> Replace 2"firnco with steel shielded mission coupling per the UPC and per the listing for the fittings.-Kitchen sink trap arm is back graded.Grade to2% <br /> slope per the UPC 708.1 Grade of Pipe.-Install clean-out on kitchen drain per the UPC 704.7 Cleanouts <br /> 3/14/20233/14/2023 PLUMB 08 FINAL JASON APPRVD-PERMIT <br /> MORRISSEY FINAL <br /> Notes: <br /> 206-856-8935 <br /> RYAN0982@LIVE.COM <br /> I <br /> Printed:Tuesday,23 April,2024 2 of 2 rk <br /> SUPERION <br />