ierracon <br /> 3.0 TEST RESULTS & SUMMARY <br /> The test results are tabulated below. To summarize the results, four of the double-sleeve <br /> anchors failed before reaching load; the remaining two double-sleeve anchors and all six <br /> of the single-sleeve anchors held the required 570 Ib-f load for the test duration of one <br /> minute without failure or indication of overstress. <br /> Test Anchor Type Maximum Load Achieved lb- <br /> �1� Double Sleeve 546 <br /> 2 Double Sleeve 448 <br /> 3 Double Sleeve 479 <br /> 4 Double Sleeve 570 <br /> 5 Double Sleeve 570 <br /> 6 Double Sleeve 344 <br /> 7 Single Sleeve 570 <br /> 8 Single Sleeve 570 <br /> 9 Single Sleeve 570 <br /> 10 Single Sleeve 570 <br /> 11 Single Sleeve 570 <br /> 12 Single Sleeve 570 <br /> We trust this report provides you with the information that you require at this time. Please <br /> do not hesitate to contact us if you have any questions or if we can be of further <br /> assistance. <br /> Respectfully submitted, <br /> OFAM <br /> WichaelE. pson, E.I.T. Eric D. Kunz, P. <br /> Field Engineer Senior Engineer <br /> Enclosed: <br /> Anchor Testing Locations <br /> Explore with us 2 <br />