Laserfiche WebLink
NEUD QRFER m <br /> ENGINEERS AN Integra co PANv <br /> W W W.NEUDDRFERENGINEERS.COM <br /> PROJECT Boeing 40-92 Safety Center Upgrade (Project# 2024-0125) <br /> LOCATION Everett, WA <br /> FCU-07: This fan coil unit serves the exhibition 250. The design airflow is 880 CFM and actual <br /> airflow is 850 CFM (97%). <br /> FCU-08: This fan coil unit serves the exhibition 250. The design airflow is 880 CFM and actual <br /> airflow is 880 CFM (100%). <br /> FCU-09: This fan coil unit serves the Hallway 228. The design airflow is 600 CFM and actual airflow <br /> is 630 CFM (105%). <br /> FCU-11: This fan coil unit serves the server room. The design airflow is 1,415 CFM and actual <br /> airflow is 1,465 CFM (104%). <br /> National Environmental Balancing Bureau <br /> Page 10 of 41 <br />