NEUDORFER r - <br /> NE�B:B <br /> ENGINEERS <br /> WWW.NEUDDRFERENGINEERS,COM <br /> AN Integra COMPANY <br /> Fan Unit <br /> PROJECT: Boeing 40-92 Safety Center Upgrades DATE: 2/22/2024 <br /> LOCATION: Everett,WA CONTACT: Moon Kim <br /> PROJECT#: 2024-0125 AUTHOR: <br /> SYSTEM/UNIT: BCU-01/Total Airflow Tested By: Moon Kim <br /> Date: 2/21/2024 <br /> Unit Data Final Data <br /> Type of Traverse Rectangular Sum of Readings 15664 FPM <br /> Instrument Used Pitot Tube Average Reading 1305 FPM <br /> Outer Height 17.00 in. Reading Std. Dev. 108.009 FPM <br /> Outer Width 20.00 in. Design Total Flow 2550 CFM <br /> Insulation Width 1 in. Actual Total Flow 2453 CFM <br /> Rect.Correction Factor 1 Static Pressure 0.54 in. <br /> Air Flow Area 1.88 sq.ft. <br /> Number Of Rows 3 <br /> Readings Per Row 4 <br /> Total Readings 12 <br /> Location of Holes 1 Right <br /> Traverse Data Points <br /> Cf N r <br /> O O O O <br /> V V V U <br /> . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . <br /> 10 <br /> 131fi 1339 1319 1375 Row 1 <br /> F1 31-41 1394 1 1399 F1 3-5-8-1 Row 2 <br /> F1 1301 1151 1131 1438 Row 3 <br /> 20 <br /> Neudorfer Engineers <br /> Page 15 of 41 <br />