NEUDORFER r - <br /> NE�B:B <br /> ENGINEERS <br /> WVAMNEUDDRFERENGINEERS,COM <br /> AN Integra COMPANY <br /> Fan Unit <br /> PROJECT: Boeing 40-92 Safety Center Upgrades DATE: 2/22/2024 <br /> LOCATION: Everett,WA CONTACT: Moon Kim <br /> PROJECT#: 2024-0125 AUTHOR: <br /> SYSTEM/UNIT: RFU-01/Total Airflow Tested By: Moon Kim <br /> Date: 2/16/2024 <br /> Unit Data Final Data <br /> Type of Traverse Rectangular Sum of Readings 19782 FPM <br /> Instrument Used Pitot Tube Average Reading 791 FPM <br /> Outer Height 24.00 in. Reading Std. Dev. 377.061 FPM <br /> Outer Width 24.00 in. Design Total Flow 2500 CFM <br /> Insulation Width 1 in. Actual Total Flow 2658 CFM <br /> Rect.Correction Factor 1 Static Pressure 1.41 in. <br /> Air Flow Area 3.36 sq.ft. <br /> Number Of Rows 5 <br /> Readings Per Row 5 <br /> Total Readings 25 <br /> Location of Holes 1 Bottom <br /> Traverse Data Points <br /> 24 <br /> . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . <br /> Cols 1239 940 551 342 <br /> Co14 1105 1050 852 438 00 <br /> Co13 1211 984 819 750 <br /> N <br /> Col t 1106 1 947 1 947 1 727 1 623 <br /> Col F 1651 1126 1022 802 <br /> O O O O O <br /> cr x cr <br /> Neudorfer Engineers <br /> Page 18 of 41 <br />