Laserfiche WebLink
NEUDORFER Rip-"ENGINEERS <br /> WWW.NEUDORFERENGINEERS,COM <br /> AN Integra COMPANY <br /> Fan Coil <br /> PROJECT: Boeing 40-92 Safety Center Upgrades DATE: 2/22/2024 <br /> LOCATION: Everett,WA CONTACT: Moon Kim <br /> PROJECT#: 2024-0125 AUTHOR: <br /> SYSTEM/UNIT: FCU-01/Total Airflow Tested By: Moon Kim <br /> Date: 2/16/2024 <br /> Unit Data Final Data <br /> Type of Traverse Round Sum of Readings 13609 FPM <br /> Instrument Used Pitot Tube Average Reading 680 FPM <br /> Diameter 18 in. Reading Std. Dev. 79.568 FPM <br /> Insulation Width 0 in. Design Total Flow 1300 CFM <br /> Rect.Correction Factor 1 Actual Total Flow 1204 CFM <br /> Air Flow Area 1.77 sq.ft. Static Pressure 0.03 in. <br /> Number Of Rows 2 <br /> Readings Per Row 10 <br /> Total Readings 20 <br /> Location of Holes 1 Left <br /> Location of Holes 2 Bottom <br /> Traverse Data Points <br /> 18 <br /> 710 <br /> 687 <br /> 7-1 <br /> 687 <br /> 7-1 <br /> 624 <br /> 4n <br /> Hole 1 624 I ® 750 730 741 507 I 613 652 726 740 00 <br /> 750 <br /> 756 <br /> 736 <br /> 740 <br /> 5-1 <br /> 672 <br /> N <br /> O <br /> O <br /> Neudorfer Engineers <br /> Page 20 of 41 <br />