NOTES
<br /> I THE (2) CONDUITS WITH (4) CURRENT CARRYING CONDUCTORS EACH, SHALL APPLY •
<br /> T _ I PROPOSED POWER PROTECTIVE CABINET CHARLES NETWORK CABINET THE ADJUSTMENT FACTOR OF 80% PER 2014/17 NEC TABLE 310.15(B)(3)(0) OR
<br /> LJ�IMJ EXISTING 120/240V, 1pw, unu7Y UTILITY SERVICE ENTRANCE 1p LUL1 p POWER SERVICE 2020 NEC TABLE 310.15(C)(1) FOR UL1015 WIRE
<br /> rY y-1 COMPANY TRANSFORMER 1 120/240 VAC 1PH N3R, 65K/IOK ACd „„,, sh
<br /> " /12 FOR 15A-20A/1P BREAKER: 0.8 x 30A = 24.0A
<br /> I [ BACKUP MAIN BREAKER WITH #10 FOR 25A-30A/2P BREAKER: 0.8 x 40A = 32.0A
<br /> GENERATOR 200A 200A INTERLOCKED GENERATOR (2) PROPOSED #8 FOR 35A-40A/2P BREAKER: 0.8 x 55A - 44.0A
<br /> NEW WIRE AND CONDUIT PER UTILITY CAMLOCK FEED, 200A 65K NC #6 FOR 45A-60A/2P BREAKER: 0.8 x 75A - 60.OA
<br /> COMPANY REQUIREMENTS GEN PLUG 0.75' EMT CONDUITS whims_
<br /> O N CONDUIT SIZING: AT 40% FILL PER NEC CHAPTER 9, TABLE 4, ARTICLE 358.
<br /> SURGE SUPPRESSION 0.5' CONDUIT - 0.122 SQ. IN AREA
<br /> DEVICE 100KA SAD4AOV 0.75' CONDUIT - 0.213 SQ. IN AREA 5701 SOUTH SANTA FE DRIVE
<br /> 2.0' CONDUIT - 1.316 SQ. IN AREA LITTLETON, CO 80120
<br /> GFCI 15A 01 02 30A PROPOSED 2 #10, 1 #10 CU GND. r FOR RECTIFIER 1 3.0' CONDUIT - 2.907 SQ. IN AREA
<br /> NEW 200A, 120/240V, 1+3W, SERVICE RATED, 15A-' �� CABINET CONVENIENCE OUTLET CONDUCTORS (1 CONDUIT): USING THWN-2, CU.
<br /> FUSIBLE DISCONNECT(NBA 3R).
<br /> (SQUARE D MODEL No. D224NR8/OR EQUIVALENT). 5p ��30A PROPOSED 2 #10 s FOR RECTIFIER 2 #10 - 0.0211 SQ. IN X 2 - 0.0422 SQ. IN
<br /> VERIFY COMPA1181LTIY WITH LOCAL UTILITY COMPANY. f�07 08 f� J #10 - 0.0211 SQ. IN X 1 - 0.0211 SQ. IN <GROUND
<br /> I LOCATION OF AWN BONDING JUMPER.
<br /> SPACE 09 10� PROPOSED 2 #10, 1 #10 CU GND. TOTAL - 0.0633 SO. IN O
<br /> 200 SPA-CE 30A _. A s FOR RECTIFIER 3
<br /> _ �11 12� 0.5' EMT CONDUIT IS ADEQUATE TO HANDLE THE TOTA_OF(3) WIRES,
<br /> #4 CU (GROUNDING SPACE INCLUDING GROUND WIRE,AS INDICATED ABOVE. O At
<br /> ELECTRODE CONDUCTOR) (3) 3/0 WITH#6 GROUND f�13 14f� PROPOSED 2 #10
<br /> IN 3'SOT 40 CONDUIT SPACE5 16�30A J s FOR RECTIFIER 4 RECTIFIER CONDUCTORS (2 CONDUITS): USING UL1015, CU.
<br /> SPACE 17 18 f� #10 - 0.0266 SQ. IN X 4 - 0.1064 SQ. IN
<br /> SPACE SPACE #10 - 0.0082 SQ. IN X 1 - 0.0082 SQ. IN <BARE GROUND 1000 HOLCOMB WOODS PKWY,
<br /> I f-�19 20fm, (1) PROPOSED SUITE 210
<br /> SPACE SPACE 0.5' EMT CONDUIT TOTAL = 0.1146 SO. IN ROSWELL, GA 30076
<br /> GROUNDING ELECTRODE SHALL BE-17
<br /> E f�21 22 f� 678-280-2325
<br /> (2) 5/8'0 X 10' LONG GROUND ROD SPACE 23 24f-SPACE 0.75'EMT CONDUIT IS ADEQUATE TO HANDLE THE TOTAL OF (5) WIRES,
<br /> SPACED MINIMUM 6'APART SPA-CE SPACE INCLUDING GROUND WIRE,AS INDICATED ABOVE.
<br /> PROPOSED 2 #10, 1 #10 CU GND. 0 s FOR CONVENIENCE OUTLET PPC FEED CONDUCTORS (1 CONDUIT): USING TWIN, CU.
<br /> 3/0 - 0.0507 SQ. IN X 3 - 0.0507 SQ. IN 60
<br /> 9 .
<br /> #6 - 0.0507 SQ. IN X 1 = 0.0507 SQ. IN <GROUNDBM
<br /> FINAL REFER TO CIRCUIT WIRING SUPPLYING RECTIFIERS ARE TO BE RATED UL1015, 105'C, 600V, AND PVC INSULATED, IN THE SIZES SHOWN TOTAL - 0.8544 SQ. IN ;_ Q�_
<br /> IN THE ONE-UNE DIAGRAM. CONTRACTOR MAY SUBSTITUTE UL1015 WIRE FOR THWN-2 FOR CONVENIENCE OUTLET BRANCH CIRCUIT.
<br /> BREAKERS REQUIRED 3.0'SCH 40 PVC CONDUIT IS ADEQUATE TO HANDLE THE TOTAL OF(4) WIRES,
<br /> INCLUDING GROUND WIRE,AS INDICATED ABOVE. i )'
<br /> (4) 30A, 2P BREAKER - SQUARE D P/N:Q0230 a�
<br /> (1) 15A, IP BREAKER - SQUARE D P/N:Q0115 N _
<br /> ,,,, 44941.099396,
<br /> 470
<br /> 'VIAL°
<br /> .3110(2022
<br /> PPC ONE-LINE DIAGRAM No SCALE 1 UBI NUMBER: 604-106-184
<br /> IT IS A VIOLATION OF LAW FOR ANY PERSON,
<br /> UNLESS THEY ARE ACTING UNDER THE DIRECTION
<br /> OF A LICENSED PROFESSIONAL ENGINEER,
<br /> TO ALTER THIS DOCUMENT.
<br /> DRAWN BY: CHECKED BY:APPROVED BY:
<br /> JDJ/LTH DM MSB
<br /> RFDS REV #: ---
<br /> CONSTRUCTION
<br /> DOCUMENTS
<br /> PROPOSED CHARLES PANEL SCHEDULE SUBMITTALS
<br /> VOLT AMPS VOLT AMPS REV DATE DESCRIPTION
<br /> LOAD SERVED (WATTS) TRIP C# PHASE Co TRIP (WATTS) LOAD SERVED A 06/03/21 ISSLIFD FOR RFVdI
<br /> L1 L2 L1 L2
<br /> PPC GFCI OUTLET 180 .. 15A 1 r- A � 2 30A 2880 ABB/GE INFINITY B 10/0S/21 REVISED PER CONENIS
<br /> CHARLES GPO OUTLET - 180 15A 3 r- B 4 "' 2880 RECTIFIER 1
<br /> 0 03/10/22 ISSUED FOR COl6TRUCTgN
<br /> -SPACE- .. - 5 -/". A -fp- 6 2880 ABB/GE INFINITY
<br /> -SPACE- 7 r- B ,,N... 8 - 2880 RECTIFIER 2 -
<br /> _
<br /> -SPACE- 9 -EN- A 10 2880 ABB/GE INFINITY
<br /> -SPACE- 11 r- B 12 .;_':_. 2880 RECTIFIER 3
<br /> -SPACE- 13 r- A 14 2880 ABB/GE INFINITY
<br /> -SPACE- 15 r- 8 16 ....._._. 2880 RECTIFIER 4
<br /> -SPACE- _. 17 r- A r.18 ..:_._. -SPACE-
<br /> -SPACE- 19 r- B r-20 -SPACE- A&E PROJECT NUMBER
<br /> -SPACE- 21 r- A r-22 -SPACE-
<br /> -SPACE- 23 r- 8 ..rti 24 . .. -SPACE- 21 CCD5N-001 7
<br /> VOLTAGE AMPS I 180 1 180 1 11520 1 11520 ,
<br /> 200A MCB, If,24 SPACE,120 240V L1 L2
<br /> TAB RATING: 65,000 AID 11700 11700 VOLTAGE AMPSDISHWireless L.L.C.
<br /> 98 98 AMPS PROJECT INFORMATION
<br /> 98 MAX AMPS
<br /> 123 MAX 125% SESEA00152A
<br /> 2215 MERRILL CREEK PKWY
<br /> EVERETT, WA 98203
<br /> SHEET TITLE
<br /> ELECTRICAL ONE-LINE, FAULT
<br /> CALCS & PANEL SCHEDULE
<br /> SHEET NUMBER
<br /> E-3
<br /> PANEL SCHEDULE NO SCALE 2 NOT USED NO SCALE 3
<br />
|