Ms. Cassandra Cheatham <br /> Kilburn Architects, LLC <br /> Plan Check Number: B2208-006, First Building Review <br /> October 20, 2022 <br /> Architectural <br /> Fire Protection: <br /> 4. The existing bedroom is being converted to additional space for the west lobby. Wall Type <br /> "W2" providing a one-hour rating is specified only at the door infill. The following comments <br /> should be addressed: <br /> a. The wall type should be specified along all walls separating the dwelling from the lobby. <br /> See IBC Section 420.2. <br /> b. The drawings should include penetration details for the walls separating the dwelling and <br /> the lobby. See IBC Section 714.4. <br /> c. Wall Type"W2" indicates an STC rating of 30 to 34. However, the listed assembly GA File <br /> No. WP3605 does not indicate this rating. The walls separating the dwelling and the lobby <br /> are required to have a minimum rating of 50. See IBC Section 1206.2. <br /> 5. The proposed construction will require repair to the horizontal assembly. The assembly <br /> requires a minimum one-hour construction. The required construction should be determined <br /> based on the configuration of the building, and a detail included in the construction drawings. <br /> See IBC Section 420.2 and Table 601. <br /> Structural <br /> General: <br /> 1. The project includes modifications to the structural systems. Structural drawings sealed and <br /> signed by a professional engineer licensed in the state of Washington are required. See IBC <br /> Section 107.1 and RCW 18.43. <br /> Foundations: <br /> 2. The proposed project includes modifications that may require the construction of new <br /> foundations. A foundation plan may be required. Calculations substantiating the new <br /> foundations should be submitted for review. See IBC Sections 107.2.1, 1603.1, 1604.1, and <br /> 1604.4. <br /> Gravity System: <br /> 3. The proposed project includes walls that are load bearing. Structural framing plans are <br /> required. Calculations substantiating the modifications to the load path should be submitted for <br /> review. See IBC Sections 107.2.1, 1603.1, 1604.1, and 1604.4. <br /> Lateral System: <br /> 4. The proposed project includes demolition of a lateral shear wall. Note that this wall also serves <br /> as a load-bearing wall for the stories above. Structural framing plans are required. Calculations <br /> 3200 Cedar Street © 425.257.8810 O everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov/permits <br /> Page 2 of 3 <br />