Laserfiche WebLink
Chvac-Full Commercial HVAC Loads Calculation Program Elite Software Development,Inc. <br /> Pacific Air Control, Inc. AL Maritime Institute <br /> Bothell WA 98021 Pae 13 <br /> Room Detailed Loads (At Room Peak Times) (cont'd) <br /> Load Radian <br /> Description Unit U.Fac/ Conv. t Total Lat. Htg. Htg. <br /> Quan Usage S.Gain S.Gain S.Gain Gain Mult. Loss <br /> Sub-total 3,260 400 2,445 <br /> Safety factors: +0% +0% +0% <br /> --------- --------- --------- <br /> Total w/ safety factors: 3,260 400 2,445 <br /> Room 9-110 Open Office peaks (sensible) in September at 1 pm, Air Handler 1 (RTU-1), Zone 1, <br /> 36.0 x 20.0, Construction Type: 8 (Exterior, Medium Construction, With Carpet, 50% Glass), SIDB: <br /> 70°F WIDB: 72°F <br /> Roof-1-UP-Type:7 720 0.053 62 123 185 2.678 1,928 <br /> Wall-1-S-Type:18 189 0.053 29 59 88 2.683 507 <br /> GIs-S-1-0%S 90.0 0.530 1,606 2,208 3,814 27.030 2,433 <br /> Unshaded Beam 90.0 0 0 0 <br /> Lights-Prof=2 792 1.000 892 1,811 2,702 <br /> Equipment-Prof=2 720 1.000 1,965 491 2,457 0 <br /> People-Prof=2 8.0 1.000 840 1,160 2,000 1,600 <br /> Sub-total 11,246 1,600 4,868 <br /> Safety factors: +0% +0% +0% <br /> --------- --------- --------- <br /> Total w/ safety factors: 11,246 1,600 4,868 <br /> S:\Engineering\Chvac 8 Projects\Maritime Institute.CH8 Monday, October 23,2023,01:54 PM <br />