Laserfiche WebLink
NEUDORFER r - <br /> NE�B:B <br /> ENGINEERS <br /> WWW.NEUDDRFERENGINEERS,COM <br /> AN Integra COMPANY <br /> Fan Unit <br /> PROJECT: PAC Maritime Institure Change Order DATE: 12/22/2023 <br /> LOCATION: Everett, CONTACT: Alex Lebedev <br /> PROJECT#: 2023-1510 <br /> SYSTEM/UNIT: EF-01 Tested By: Alex Lebedev <br /> AREA: Unisex 107 Date: 12/22/2023 <br /> Unit Data Motor Data <br /> Fan Manufacturer Broan Motor Rated Volts 115 Volts <br /> Fan Model Number AE110B Motor Phase 1 <br /> Fan Discharge Horizontal Motor Hertz 60 Hz <br /> Drive Type Direct Drive Motor Full Load Amps 0.30 Amps <br /> Fan Speed Single <br /> Test Pressures <br /> Test Data Fan Suction SP -0.02 in.we <br /> Total Design Flow 110 CFM Fan Discharge SP 0.20 in.we <br /> Total Actual Flow 75 CFM Actual Total SP 0.22 in.we <br /> Motor Volts T1-T2 122 Volts <br /> Motor Amps T1 0.20 Amps <br /> Log: EF-01 12/22/2023 Alex Lebedev Back draft dampet is open. Fan has a flex duct <br /> installed on the discharge side to connect fan to <br /> outside of the building. <br /> EF-01 Exhaust Inlet Summary <br /> System/Unit Area Served Type of Inlet Size LxW/D AK Design Prelim Final Final% Remarks <br /> Readinq Type Airflow Airflow Airflow <br /> Inlet-01 Unisex 107 Flowhood EG 9x9 1.00 110 75 75 68 <br /> Totals: - 110 75 75 68 <br /> Neudorfer Engineers <br />